# Temperature derating factor (T) for steel pipe.

**Citation:** 49 CFR 192.115  
**Type / status:** regulation / current  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** 2026-08-18  
**Published:** Not stated

The temperature derating factor to be used in the design formula in § 192.105 is determined as follows:

Gas temperature in degreesFahrenheit (Celsius) Temperaturederating factor (T) 250 °F (121 °C) or less 1.000 300 °F (149 °C) 0.967 350 °F (177 °C) 0.933 400 °F (204 °C) 0.900 450 °F (232 °C) 0.867

## Document text

The temperature derating factor to be used in the design formula in § 192.105 is determined as follows:

Gas temperature in degreesFahrenheit (Celsius) Temperaturederating factor (T) 250 °F (121 °C) or less 1.000 300 °F (149 °C) 0.967 350 °F (177 °C) 0.933 400 °F (204 °C) 0.900 450 °F (232 °C) 0.867

For intermediate gas temperatures, the derating factor is determined by interpolation.

[35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-85, 63 FR 37502, July 13, 1998]