LNG storage tanks with a capacity of 5,000 barrels (795 cubic meters) or more must be equipped with means to mitigate a potential for rollover and overpressure such as:

(a) Selective filling at the top and bottom of the tank;

(b) Circulating liquid from the bottom to the top of the same tank; or



## Document text

LNG storage tanks with a capacity of 5,000 barrels (795 cubic meters) or more must be equipped with means to mitigate a potential for rollover and overpressure such as:

(a) Selective filling at the top and bottom of the tank;

(b) Circulating liquid from the bottom to the top of the same tank; or

(c) Transferring liquid selectively from the bottom of the tank to the bottom or top of any adjacent storage tank.

[45 FR 9203, Feb. 11, 1980, as amended by Amdt. 193-16, 63 FR 37505, July 13, 1998]

## Provenance

- Official: Yes
- Source: <https://www.govinfo.gov/app/details/CFR-1999-title49-vol3/CFR-1999-title49-vol3-sec193-2191>
- Source ID: `govinfo-cfr`
- SHA-256: `9564f4b9da5c43b5a723ac655c42d437d42c9773fd52f67b074855aaadbcd45b`
- Retrieved: 2026-08-12T01:41:23.231Z
- Exported: 2026-08-23T16:43:50.294Z
- Document slug: `49-cfr-193-2191`

### Source metadata

```json
{
  "part": "193",
  "section": "193.2191",
  "subpart": "Subpart C—Design",
  "annualEdition": 1999,
  "revisedAsOf": "1999-10-01",
  "govInfoPackage": "CFR-1999-title49-vol3",
  "legalStatus": "official-annual-cfr-edition",
  "effectiveDateNote": null,
  "historicalAnchor": true,
  "historicalAnchorNote": "The section appears in an official annual CFR edition but is absent from the connected current eCFR corpus.",
  "jurisdiction": "US"
}
```