Regulator Stations (a) Each Operator shall ensure that inspections conducted pursuant to 49 CFR 192.739(a), as amended from time to time, include: (1) removal, inspection, and replacement, if necessary, of all filters; (2) inspection, testing, and maintenance, if necessary, of any heating equipment; (3) verification of

## Document text

Regulator Stations (a) Each Operator shall ensure that inspections conducted pursuant to 49 CFR 192.739(a), as amended from time to time, include: (1) removal, inspection, and replacement, if necessary, of all filters; (2) inspection, testing, and maintenance, if necessary, of any heating equipment; (3) verification of compliance with section 16-280b-A21 of the Regulations of Connecticut State Agencies; and (4) a final inspection that ensures proper position of all valves and restoration of all security devices. (b) The Operator shall ensure that any deficiencies found during the inspections required pursuant to 49 CFR 192.739, as amended from time to time, and this section shall be remediated prior to the Gate Station or District Regulator Station being returned to service if the deficiency affects the safe operation of the station but in no case shall remediation occur later than 1 year from the date of inspection.

## Provenance

- Official: Yes
- Source: <https://eregulations.ct.gov/eRegsPortal/Search/getDocument?guid=%7BE04F6097-0000-CC1C-9D68-25A0BA411C82%7D>
- Source ID: `ct-sots-rcsa-16-280b`
- SHA-256: `566de8e06e3ce33df324cd2cb47e8622caf3c26cc8d4d595ba5f0d39e1ae6249`
- Retrieved: 2026-08-12T07:07:58.041Z
- Exported: 2026-08-23T07:30:35.369Z
- Document slug: `ct-rcsa-16-280b-a69`

### Source metadata

```json
{
  "jurisdiction": "US-CT",
  "subtitle": "16-280b",
  "series": "A",
  "sectionNumber": 69,
  "secretaryFileNumber": 6446,
  "trackingNumber": "PR2023-019",
  "effectiveDateEvidence": "Secretary of the State confirmation states that the regulation became effective June 11, 2025.",
  "scopeCaveat": "This corpus contains all 117 dedicated pipeline-safety sections newly codified as RCSA 16-280b-A1 through A75, B1 through B32, and C1 through C10 by Connecticut Secretary of the State File Number 6446. The filing also amends four adjacent legacy utility provisions and repeals eleven obsolete 16-11 provisions; those actions are retained as provenance and inventory rather than mixed into the dedicated searchable corpus.",
  "applicabilityCaveat": "Applicability varies by natural-gas or petroleum-gas operator, public-service-company status, pipeline facility, master-meter or petroleum-gas distribution system, activity, waiver, and federal jurisdiction. PURA states that Connecticut has no intrastate transmission or gathering lines and that hazardous-liquid pipelines remain under PHMSA jurisdiction.",
  "incorporationCaveat": "The rules supplement and repeatedly incorporate federal pipeline requirements, generally as amended from time to time, and rely on Connecticut statutes and external standards. References are recorded without reproducing incorporated material or deciding federal preemption or facility-specific legal effect.",
  "publicationCaveat": "The authenticated final filing was posted to the Connecticut eRegulations System and became effective June 11, 2025. It is used instead of the older browse pages, some of which still display pre-2025 text and stale update labels.",
  "rights": "Official Connecticut legal and agency materials are retained with attribution and cryptographic provenance. State marks, site presentation, forms, annotations, and incorporated federal or privately authored material require separate review.",
  "rightsReviewRequired": true,
  "region": "CT"
}
```