# Building Explosion and Fire

**Citation:** DCA16FP003  
**Type / status:** incident / current  
**Agency:** National Transportation Safety Board  
**Effective:** 2016-08-10  
**Published:** 2019-04-29

Accident. in Silver Spring, MD, USA. on 2016-08-10. Washington Gas Light Company. Leak/explosion/fire

## Document text

NTSB investigation DCA16FP003.

Event Type: Accident

Event Date: 2016-08-10

Event City: Silver Spring

Event State Or Region: MD

Event Country: USA

Pipeline Operator: Washington Gas Light Company

Pipeline Type: Distribution

Accident Type: Leak/explosion/fire

Completion Status: Completed

Report Number: PAR1901

Report Date: 2019-04-29

Probable cause: The National Transportation Safety Board determines that the probable cause of the explosion in building 8701 of the Flower Branch apartment complex was the failure of an indoor mercury service regulator with an unconnected vent line that allowed natural gas into the meter room where it accumulated and ignited from an unknown ignition source. Contributing to the accident was the location of the mercury service regulators where leak detection by odor was not readily available.

Tier1Name: System operating

Tier2Name: Explosion

Tier1Name: Post-release

Tier2Name: Fire/explosion (post-release)

Tier1Name: Emergency response

Tier2Name: Emergency shutoff

Tier1Name: System operating

Tier2Name: Product leak/release

Tier1Name: System operating

Tier2Name: System/equipment malf/failure

Tier1Name: Emergency response

Tier2Name: Inspection event

Finding Tier1Name: Organizational

Finding Tier2Name: Management

Finding Tier3Name: Policy/procedure

Finding Modifier Name: Pipeline operator

Finding Report Text: Organizational - Management - Policy/procedure - Pipeline operator

Finding Tier1Name: Organizational

Finding Tier2Name: Support/oversight/monitoring

Finding Tier3Name: Documentation/record keeping

Finding Modifier Name: Pipeline operator

Finding Report Text: Organizational - Support/oversight/monitoring - Documentation/record keeping - Pipeline operator

Finding Tier1Name: Organizational

Finding Tier2Name: Support/oversight/monitoring

Finding Tier3Name: Enforcement

Finding Modifier Name: Federal agency

Finding Report Text: Organizational - Support/oversight/monitoring - Enforcement - Federal agency

Finding Tier1Name: Organizational

Finding Tier2Name: Support/oversight/monitoring

Finding Tier3Name: Documentation/record keeping

Finding Modifier Name: Not specified

Finding Report Text: Organizational - Support/oversight/monitoring - Documentation/record keeping - Not specified

Finding Tier1Name: Organizational

Finding Tier2Name: Support/oversight/monitoring

Finding Tier3Name: Enforcement

Finding Modifier Name: State/Local agency

Finding Report Text: Organizational - Support/oversight/monitoring - Enforcement - State/Local agency

Finding Tier1Name: Organizational

Finding Tier2Name: Support/oversight/monitoring

Finding Tier3Name: Documentation/record keeping

Finding Modifier Name: State/Local agency

Finding Report Text: Organizational - Support/oversight/monitoring - Documentation/record keeping - State/Local agency

Finding Tier1Name: Organizational

Finding Tier2Name: Development

Finding Tier3Name: Design

Finding Modifier Name: Inspection organization

Finding Report Text: Organizational - Development - Design - Inspection organization

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipline systems/equipment

Finding Tier3Name: Regulator

Finding Modifier Name: Failure

Finding Report Text: Pipeline - Pipline systems/equipment - Regulator - Failure

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipline systems/equipment

Finding Tier3Name: Venting

Finding Modifier Name: Malfunction

Finding Report Text: Pipeline - Pipline systems/equipment - Venting - Malfunction

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipeline structure

Finding Tier3Name: Pipe

Finding Modifier Name: Design

Finding Report Text: Pipeline - Pipeline structure - Pipe - Design

Finding Tier1Name: Environment/Infrastructure

Finding Tier2Name: Operating environment/control system

Finding Tier3Name: Sensor/detector coverage/availability

Finding Modifier Name: Awareness of condition

Finding Report Text: Environment/Infrastructure - Operating environment/control system - Sensor/detector coverage/availability - Awareness of condition

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipeline handling/service

Finding Tier3Name: Operating information

Finding Modifier Name: Not inspected

Finding Report Text: Pipeline - Pipeline handling/service - Operating information - Not inspected

Finding Tier1Name: Personnel

Finding Tier2Name: Action/decision

Finding Tier3Name: Information processing/decision making

Finding Modifier Name: Pipeline maintenance personnel

Finding Report Text: Personnel - Action/decision - Information processing/decision making - Pipeline maintenance personnel

Finding Tier1Name: Personnel

Finding Tier2Name: Action/decision

Finding Tier3Name: Information processing/decision making

Finding Modifier Name: Emergency services personnel

Finding Report Text: Personnel - Action/decision - Information processing/decision making - Emergency services personnel

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipline systems/equipment

Finding Tier3Name: Regulator

Finding Modifier Name: Design

Finding Report Text: Pipeline - Pipline systems/equipment - Regulator - Design

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipline systems/equipment

Finding Tier3Name: Regulator

Finding Modifier Name: Malfunction

Finding Report Text: Pipeline - Pipline systems/equipment - Regulator - Malfunction

Official NTSB investigation data. NTSB findings determine probable cause and make safety recommendations; they do not adjudicate civil liability or regulatory violations.

What Happened
On August 10, 2016, at 11:51 p.m., eastern daylight time, a 14-unit apartment building, located at 8701 Arliss Street, in the unincorporated community of Silver Spring, in Montgomery County, Maryland, partially collapsed due to a natural gas-fueled explosion and fire.
The explosion and fire also heavily damaged an adjacent apartment building, 8703 Arliss Street, which shared a common wall with building 8701.
As a result of this accident, 7 residents died, 65 residents were transported to the hospital, and 3 firefighters were treated and released from the hospital. The damage from the accident exceeded $1 million.

What We Found
The probable cause of the explosion in building 8701 of the Flower Branch apartment complex was the failure of an indoor mercury service regulator with an unconnected vent line that allowed natural gas into the meter room where it accumulated and ignited from an unknown ignition source. Contributing to the accident was the location of the mercury service regulators where leak detection by odor was not readily available.

What We Recommended
As a result of this investigation, we made the following new safety recommendations.

To the Pipeline and Hazardous Materials Safety Administration:

Require that all new service regulators be installed outside occupied structures. (P-19-001)

Require existing interior service regulators be relocated outside occupied structures whenever the gas service line, meter, or regulator is replaced. In addition, multifamily structures should be prioritized over single-family dwellings. (P-19-002)

To the Public Service Commission of Maryland, the Commonwealth of Virginia State
Corporation Commission Division of Public Utility Regulation, and the Public Service
Commission of the District of Columbia:

Following Washington Gas’s successful completion of Safety Recommendation P-19-009, audit and verify the performance of Washington Gas’s mercury service regulator replacement program, including its recordkeeping. (P-19-003)
Oversee the replacement process for the mercury service regulators that Washington Gas has in service. (P-19-004)

To the International Academies of Emergency Dispatch: Revise Protocol-60 Gas Leak/Gas Odor (Natural and Liquified Petroleum Gases) to direct dispatchers to notify the gas company when any odor call is received. (P-19-005)

To the International Code Council: In coordination with the Gas Technology Institute and the National Fire Protection Association, incorporate provisions in the International Fuel Gas Code that requires methane detection systems for all types of residential occupancies with gas
service. At a minimum, the provisions should cover the installation, maintenance, placement of the detectors, and testing requirements. (P-19-006)

To the National Fire Protection Association: In coordination with the Gas Technology Institute and the International Code Council, revise the National Fuel Gas Code, National Fire Protection

Association 54 to require methane detection systems for all types of residential occupancies with gas service. At a minimum, the provisions should cover the installation, maintenance, placement of the detectors, and testing requirements.
(P-19-007)

To the Gas Technology Institute: In coordination with the National Fire Protection Association and the International Code Council, work to develop standards for methane detection systems for all
types of residential occupancies in both the International Fuel Gas Code and the National Fuel Gas Code, National Fire Protection Association 54. At a minimum, the provisions should cover the installation, maintenance, placement of the detectors, and testing requirements. (P-19-008)

To Washington Gas Light Company:

Throughout the Washington Gas network, implement an audit program to verify the data on the service forms used to determine the location and condition of mercury service regulators to ensure the accuracy of this safety-critical data. (P-19-009)
Revise your procedures and field forms to require technicians to verify the integrity of vent lines following the testing of indoor service regulators throughout the Washington Gas network. (P-19-010)
Establish a time frame with specific dates and milestones for the replacement of mercury service regulators throughout the Washington Gas network that recognizes the need to expedite this program and that prioritizes multifamily dwellings where mercury service regulators are located inside the property. (P-19-011)
Install all new service regulators outside occupied structures. (P-19-012)
Relocate existing interior service regulators outside occupied structures whenever the gas service line, meter, or regulator is replaced. In addition, multifamily structures should be prioritized over single-family dwellings. (P-19-013)

PAR-19-01
<<<PAGE 1>>>

Building Explosion and Fire
Silver Spring, Maryland
August 10, 2016
Accident Report
NTSB/PAR-19/01
PB2019-100722
National
Transportation
Safety Board

<<<PAGE 2>>>

NTSB/PAR-19/01
PB2019-100722
Notation 58957
Adopted April 24, 2019
Pipeline Accident Report
Building Explosion and Fire
Silver Spring, Maryland
August 10, 2016
National
Transportation
Safety Board
490 L’Enfant Plaza, S.W.
Washington, D.C. 20594

<<<PAGE 3>>>

National Transportation Safety Board. 2019. Building Explosion and Fire, Silver Spring, Maryland,
August 10, 2016. NTSB/PAR-19/01. Washington, DC.
Abstract: On August 10, 2016, at 11:51 p.m. eastern daylight time, a 14-unit apartment building,
located at 8701 Arliss Street, in Silver Spring, Montgomery County, Maryland, partially collapsed
due to a natural gas-fueled explosion and fire. The explosion and fire also heavily damaged an
adjacent apartment building which shared a common wall with building 8701. As a result of this
accident, 7 residents died, 65 residents were transported to the hospital, and 3 firefighters were
treated and released from the hospital. The investigation focused on the following safety issues: the
location and inspection of service regulators within a structure; the inspection of the gas meter
assembly; the notification of the natural gas odor to Washington Gas Light Company; and the
detection of natural gas through odorants and methane. As a result of this investigation, the
National Transportation Safety Board (NTSB) makes new safety recommendations to the Pipeline
and Hazardous Materials Safety Administration; the Public Service Commission of Maryland, the
Commonwealth of Virginia State Corporation Commission Division of Public Utility Regulation,
and the Public Service Commission of the District of Columbia; the International Academies of
Emergency Dispatch; the International Code Council; the National Fire Protection Association; the
Gas Technology Institute; and Washington Gas Light Company.
The National Transportation Safety Board (NTSB) is an independent federal agency dedicated to promoting
aviation, railroad, highway, marine, and pipeline safety. Established in 1967, the agency is mandated by Congress
through the Independent Safety Board Act of 1974 to investigate transportation accidents, determine the probable
causes of the accidents, issue safety recommendations, study transportation safety issues, and evaluate the safety
effectiveness of government agencies involved in transportation. The NTSB makes public its actions and decisions
through accident reports, safety studies, special investigation reports, safety recommendations, and statistical
reviews.
The NTSB does not assign fault or blame for an accident or incident; rather, as specified by NTSB regulation,
“accident/incident investigations are fact-finding proceedings with no formal issues and no adverse parties … and
are not conducted for the purpose of determining the rights or liabilities of any person.” 49 C.F.R. § 831.4.
Assignment of fault or legal liability is not relevant to the NTSB’s statutory mission to improve transportation safety
by investigating accidents and incidents and issuing safety recommendations. In addition, statutory language
prohibits the admission into evidence or use of any part of an NTSB report related to an accident in a civil action for
damages resulting from a matter mentioned in the report. 49 U.S.C. § 1154(b).
For more detailed background information on this report, visit http://www.ntsb.gov/investigations/dms.html and
search for NTSB accident ID DCA16FP003. Recent publications are available in their entirety on the Internet at
http://www.ntsb.gov. Other information about available publications also may be obtained from the website or by
contacting:
National Transportation Safety Board
Records Management Division, CIO-40
490 L’Enfant Plaza, SW
Washington, DC 20594
(800) 877-6799 or (202) 314-6551
NTSB publications may be purchased from the National Technical Information Service. To purchase this
publication, order product number PB2019-100722 from:
National Technical Information Service
5301 Shawnee Rd.
Alexandria, VA 22312
(800) 553-6847 or (703) 605-6000
http://www.ntis.gov/

<<<PAGE 4>>>

NTSB Pipeline Accident Report
Contents
Figures ........................................................................................................................................... iii
Tables ............................................................................................................................................ iv
Abbreviations and Acronyms .......................................................................................................v
Executive Summary .................................................................................................................... vii
1. Factual Information and Analysis ..........................................................................................1
1.1 The Accident ............................................................................................................................1
1.2 Accident Site and Property Description ...................................................................................2
1.2.1 Gas Meter/Utility Room ................................................................................................5
1.3 The Investigation ......................................................................................................................5
1.3.1 Gas Odor Leak Calls ......................................................................................................5
1.3.2 Previous Gas Odor Calls ................................................................................................6
1.3.3 Emergency Response .....................................................................................................6
1.3.4 Postaccident Gas Leak Surveys and Odorant Testing ...................................................7
1.3.5 Fire and Arson Investigations ........................................................................................8
1.3.6 Explosion Damage and Evidence ..................................................................................8
1.3.7 Gas Service to the Flower Branch Apartment Complex ................................................9
2 Safety Issues ............................................................................................................................10
2.1 Introduction ............................................................................................................................10
2.2 Gas Meter Assembly Inspection .............................................................................................10
2.3 Service Regulators ..................................................................................................................12
2.3.1 Service Regulator Overview ........................................................................................12
2.3.2 NTSB Materials Laboratory Examination of the Mercury Service Regulators ...........17
2.3.3 Upper Regulator Union Assembly ...............................................................................19
2.3.4 Lower Regulator Union Assembly ..............................................................................21
2.3.5 Vent Line Inspection Practices ....................................................................................22
2.3.6 Examination and Exclusion of Gas Appliances in the Meter Room ...........................22
2.3.7 Mercury Service Regulator Testing .............................................................................24
2.3.8 Natural Gas Accumulation in the Meter Room of Building 8701 ...............................26
2.3.9 Mercury Service Regulator Replacement ....................................................................28
2.3.10 Location of Natural Gas Service Regulators ...............................................................29
2.4 Natural Gas Odor Notification ...............................................................................................30
2.4.1 Kay Management .........................................................................................................30
2.4.2 Washington Gas ...........................................................................................................31
2.4.3 Montgomery County Fire and Rescue Services ...........................................................31
2.5 Odorant and Methane Detection of Natural Gas ....................................................................32
2.5.1 Odorant Detection ........................................................................................................32
2.5.2 Methane Detection .......................................................................................................34
i

<<<PAGE 5>>>

NTSB Pipeline Accident Report
3 Postaccident Actions ..............................................................................................................39
4 Conclusions .............................................................................................................................40
4.1 Findings ..................................................................................................................................40
4.2 Probable Cause .......................................................................................................................41
5 Recommendations ..................................................................................................................42
6 Appendix .................................................................................................................................47
6.1 Appendix A: The Investigation ..............................................................................................47
6.2 Appendix B: Sample of 20 NTSB Investigations of Residential and Commercial Building
Pipeline Accidents Between 1971 and 2018 ..................................................................................47
References .....................................................................................................................................52
ii

<<<PAGE 6>>>

NTSB Pipeline Accident Report
Figures
Figure 1. The accident location, 8701 Arliss Street, before the August 10, 2016, explosion. ....... 1
Figure 2. Buildings 8701 and 8703 Arliss Street, Silver Spring, Maryland, after the explosion
and fire. ........................................................................................................................................... 2
Figure 3. Layout of the Flower Branch apartment complex. ......................................................... 3
Figure 4. A plan for the basement/terrace floor for 8701 Arliss Street and the shared-wall
portion of 8703 Arliss Street. .......................................................................................................... 4
Figure 5. Portions of mercury service regulators and gas meters in building 8701
showing heat/fire/explosion damage and the unconnected lower regulator vent line. ................. 11
Figure 6. Building 8701 after debris removal and ATF reconstruction. ...................................... 12
Figure 7. Exemplar configuration of a mercury service regulator assembly in a similar
Flower Branch apartment building. .............................................................................................. 14
Figure 8. Exemplar mercury service regulator taken from a nearby Flower Branch
apartment building. ....................................................................................................................... 15
Figure 9. Cross sectional image of a mercury service regulator. ................................................. 16
Figure 10. Mercury service regulators, service line, jurisdictional pipeline, and vent line after
the accident. .................................................................................................................................. 18
Figure 11. Photograph of the lower regulator union assembly parts. .......................................... 19
Figure 12. A photograph of the exposed external threaded nipple from the upper regulator
union assembly.............................................................................................................................. 20
Figure 13. Photograph of the disassembled union assembly for the accident lower gas regulator
after cleaning. ................................................................................................................................ 21
Figure 14. Hot water heater at the accident scene after the explosion. ........................................ 23
Figure 15. The main burner assembly, including the separated pipe and the gas control
valve assembly. ............................................................................................................................. 24
Figure 16. Three-dimensional visualization of the meter room. .................................................. 27
iii

<<<PAGE 7>>>

NTSB Pipeline Accident Report
Tables
Table 1. Valve seat obstruction failure test data. ......................................................................... 25
Table 2. Diaphragm tear failure test data for a torn upper regulator. ........................................... 25
Table 3. Loss of mercury failure test data. ................................................................................... 26
iv

<<<PAGE 8>>>

NTSB Pipeline Accident Report
Abbreviations and Acronyms
ANSI American National Standards Institute
ASME American Society of Mechanical Engineers
ATF US Bureau of Alcohol, Tobacco, Firearms and Explosives
BSI British Standards Institution
CFD computational fluid dynamics
CFH cubic feet per hour
CFR Code of Federal Regulations
COMAR Code of Maryland Regulations
DOT US Department of Transportation
ECC Montgomery County Emergency Communication Center
EPA US Environmental Protection Agency
GAO US Government Accountability Office
GTI Gas Technology Institute
IAED International Academies of Emergency Dispatch
ICC International Code Council
IFGC International Fuel Gas Code
LEL lower explosive limit
LP liquified petroleum
MAOP maximum allowable operating pressure
MCFRS Montgomery County Fire and Rescue Service
MCPD Montgomery County Police Department
NCSL National Conference of State Legislatures
NFPA National Fire Protection Association
v

<<<PAGE 9>>>

NTSB Pipeline Accident Report
NFPA 54 National Fuel Gas Code
NPS nominal pipe size
NTSB National Transportation Safety Board
OTD Operations Technology Development
PHMSA Pipeline and Hazardous Materials Safety Administration
PSC Public Service Commission of Maryland
psig pounds per square inch, gauge
RMD residential methane detectors
RSPA Research and Special Programs Administration
SCFH standard cubic feet per hour
UEL upper explosive limit
UL Underwriter’s Laboratories
WC water column
WG Washington Gas Light Company
WSSC Washington Suburban Sanitary Commission
vi

<<<PAGE 10>>>

NTSB Pipeline Accident Report
Executive Summary
On August 10, 2016, at 11:51 p.m., eastern daylight time, a 14-unit apartment building,
located at 8701 Arliss Street, in the unincorporated community of Silver Spring, in Montgomery
County, Maryland, partially collapsed due to a natural gas-fueled explosion and fire.
The explosion and fire also heavily damaged an adjacent apartment building, 8703 Arliss
Street, which shared a common wall with building 8701.
As a result of this accident, 7 residents died, 65 residents were transported to the hospital,
and 3 firefighters were treated and released from the hospital. The damage from the accident
exceeded $1 million.
The following are safety issues in this accident:
• the location and inspection of service regulators within a structure
• the inspection of the gas meter assembly
• the notification of the natural gas odor to Washington Gas Light Company
• the detection of natural gas through odorants and methane
The National Transportation Safety Board determines that the probable cause of the
explosion in building 8701 of the Flower Branch apartment complex was the failure of an indoor
mercury service regulator with an unconnected vent line that allowed natural gas into the meter
room where it accumulated and ignited from an unknown ignition source. Contributing to the
accident was the location of the mercury service regulators where leak detection by odor was not
readily available.
vii

<<<PAGE 11>>>

NTSB Pipeline Accident Report
1. Factual Information and Analysis
1.1 The Accident
On August 10, 2016, at 11:51 p.m., eastern daylight time, a 14-unit apartment building,
located at 8701 Arliss Street, in the unincorporated community of Silver Spring, in Montgomery
County, Maryland, partially collapsed due to a natural gas-fueled explosion and fire.1 (See
figure 1.)
Figure 1. The accident location, 8701 Arliss Street, before the August 10, 2016, explosion.
(Photograph from Google Earth, dated November 2015.)
The explosion and fire also heavily damaged an adjacent apartment building, 8703 Arliss
Street, which shared a common wall with building 8701. (See figure 2.)
1 All times mentioned in this report are eastern daylight time, unless otherwise specified.
1

<<<PAGE 12>>>

NTSB Pipeline Accident Report
Figure 2. Buildings 8701 (right-center) and 8703 (left) Arliss Street, Silver Spring, Maryland, after
the explosion and fire. (Photograph provided by the Public Service Commission of Maryland.)
As a result of this accident, 7 residents died, 65 residents were transported to the hospital,
and 3 firefighters were treated and released from the hospital.2 The damage from the accident
exceeded $1 million.
1.2 Accident Site and Property Description
Buildings 8701 and 8703 Arliss Street were part of the Flower Branch Apartments, a
26-building complex that was constructed in 1955. (See figure 3.) The apartment complex was
managed by Kay Management, a real estate management and development company.
2 Some of the injuries reported included respiratory problems from smoke inhalation and injuries from falling or
burns.
2

<<<PAGE 13>>>

NTSB Pipeline Accident Report
Figure 3. Layout of the Flower Branch apartment complex. Building 8701 is identified by a red
star. (Graphic provided by Kay Management.)
Building 8701 Arliss Street was a four-level structure with a basement and three floors.
Four apartments were located on each of the upper three levels. The basement/terrace level
consisted of one apartment, a meter room, a storage room, and a property management and rental
office. (See figure 4.)
3

<<<PAGE 14>>>

NTSB Pipeline Accident Report
Figure 4. A plan for the basement/terrace floor for 8701 Arliss Street and the shared-wall portion
of 8703 Arliss Street. (Graphic provided by Kay Management.)
According to Washington Gas Light Company’s (WG) construction and service records
for 8701 Arliss Street, between the years of 1955 and 1969 the natural gas main along Piney Branch
Road that supplied this address was a medium-pressure main constructed of 6-inch inside diameter
wrapped steel. The service line from the main that supplied 8701 Arliss Street was 2-inch nominal
pipe size (NPS) wrapped steel, connected to a 1-inch NPS inlet pipe and a 1-inch outlet pipe after
the service regulators.
3 The main had a maximum allowable operating pressure (MAOP) of
25 pounds per square inch, gauge (psig) and the operating pressure at the time of the explosion
was between 20 and 22 psig.4 This line had been servicing the address for over 60 years until the
explosion on August 10, which severed a portion of the service line. The service line construction
was completed on May 31, 1955, and the installation of the natural gas meters and regulators was
completed on June 15, 1955. The gas main and service line were buried about 3 feet below the
surface. The 2-inch service line ran along the front of the apartment buildings, including 8701
Arliss Street. On September 25, 1969, the service line was relocated about 80 feet and disconnected
3 NPS is nominal pipe size as defined the American Society of Mechanical Engineers (ASME) B36-10M-2018
standards for wrought steel pipe (ASME 2018).
4 MAOP refers to how much pressure the walls of the pipeline may safely hold in normal operations.
4

<<<PAGE 15>>>

NTSB Pipeline Accident Report
from the 6-inch medium-pressure wrapped steel main on Piney Branch Road. The service line was
then connected to a 4-inch medium-pressure wrapped steel main that ran along Arliss Street.
1.2.1 Gas Meter/Utility Room
The gas meters were located in the meter room in the basement of 8701 Arliss Street on
the north facing wall. The gas meter assembly included 15 meters that served 13 apartments, and
maintenance and management offices.
5 The electric meter panel and a commercial-grade gas water
heater were positioned about 6 feet away from the gas meter assembly. The room was also used
for equipment and supply storage. At the time of the accident, it contained supplies and equipment
needed for maintenance.
6
The meter room had restricted access and only two windows: one enclosed with glass and
the other covered with a piece of wood with two small holes for ventilation. The room was secured
by a knob lock, a vertical deadbolt lock, and was armed with an alarm system.7 Only Kay
Management staff and Montgomery County Fire and Rescue Service (MCFRS) responders were
authorized access to the meter room. In February 2016, the lock to the meter room was changed;
however, Kay Management had not placed a copy of the new key in the MCFRS Knox Box,
located on the premises.8
1.3 The Investigation
1.3.1 Gas Odor Leak Calls
Prior to the accident, several residents of buildings 8701 and 8703 reported to investigators
that they smelled gas in the weeks and months leading up to the explosion. One resident reported
that he smelled natural gas after returning from work around 11:30 p.m. on August 10. While he
was taking out the trash, around 11:50 p.m., he smelled a gas odor in the stairwell and walked
down to the basement to locate the source. He told National Transportation Safety Board (NTSB)
investigators that he found the odor became stronger as he walked into the basement and he could
hear a hissing noise from behind the locked doors of the meter room. He said that he planned to
call 9-1-1 to report the gas odor after he finished taking out the trash. However, before he could
report the leak, as he walked back from the community trash containers about 120 feet away, the
explosion occurred.9
5 The management office was an apartment converted for business purposes.
6 Kay Management provided an inventory list for the meter room in 8701 Arliss Street.
7 According to the US Bureau of Alcohol, Tobacco, Firearms and Explosions (ATF) Origin and Cause report, the
knob lock was locked, and the vertical dead bolt was not locked, prior to the explosion. For more information, see
“ATF Report” in NTSB Docket DCA16FP003.
8 A Knox Box system is an access box for fire departments to use in the event of an emergency to enter structures
or areas that are deemed difficult. This is required under National Fire Protection Association (NFPA) 1, which is a
comprehensive fire code that the State of Maryland has adopted by reference in its Fire Prevention Code.
9 For more information, see “Interview transcript with Resident A” in NTSB Docket DCA16FP003.
5

<<<PAGE 16>>>

NTSB Pipeline Accident Report
1.3.2 Previous Gas Odor Calls
Between September 2015 and June 2016, Kay Management received six gas odor calls
from residents of 8701 Arliss Street.
10 Members of its maintenance staff said that when they
investigated, they either did not detect gas through their gas-detection equipment or would report
that the painting of apartments was causing the smell. MCFRS fire personnel responded to an odor
call at building 8701 on July 25, 2016. According to interviews with Flower Branch residents and
employees from Kay Management, residents in the building typically called either the management
company or 9-1-1 to report gas odors. WG has no record of responding to or receiving any
notifications of gas odor calls from 8701 Arliss Street in the 5 years prior to the accident.
The same resident who detected the natural gas odor on the night of the explosion had
called 9-1-1 on July 25, 2016, to report a strong smell of natural gas both outside and inside of
building 8701. The resident told the 9-1-1 operator that the strongest smell of natural gas was
detected on the first level of the apartment building. The 9-1-1 operator told the resident not to
turn on anything that could create an ignition source, and to evacuate himself and others out of the
building. Neither the resident nor the 9-1-1 operator contacted the gas company.
On July 25, 2016, MCFRS fire personnel arrived at building 8701 around 10:20 p.m. They
approached the building using a calibrated four-gas multimeter.11 Residents directed the fire
personnel to the main hallway of the first floor, where no combustible gas readings or natural gas
odors were detected. Although one responder reported smelling “something,” it did not register on
his detection equipment. The fire personnel proceeded through the apartment building, checking
inside occupied apartments and underneath doors of unoccupied apartments. The fire personnel
moved to the basement to test the storage and meter rooms but were unable to gain access to the
meter room because the locks had recently been changed and the new key was unavailable. The
fire personnel wedged the top of the doors open but detected no gas. MCFRS departed at
10:33 p.m. because they did not detect any gas readings throughout the building.12 The Kay
Management property manager was not notified of the odor leak call and only learned of it after a
conversation with a resident days later.
13 There are no records of additional conversation between
Kay Management and MCFRS regarding the July 25 odor complaint.
1.3.3 Emergency Response
On August 10, 2016, at 11:52 p.m., the MCFRS Emergency Communication Center
received a 9-1-1 call reporting the explosion and fire. Buildings 8701 and 8703 Arliss Street were
evacuated by two Montgomery County Police Officers who were within 1,000 feet from them
10 For more information, see “Operations – Kay Management (All Work Orders 08-01-15 thru 08-25-16)” in
NTSB Docket DCA16FP003.
11 Four-gas multimeters are devices that measure the atmosphere for the following four parameters: oxygen
concentration (in percentage O2), flammability (in percentage of lower explosive limit [LEL]), carbon monoxide
concentration (in parts per million), and hydrogen sulfide concentration (in parts per million).
12 For more information, see “Reg. Oversight – MCFRS Statements on July 25, 2016, incident” and “Interview
of Montgomery County Fire and Rescue Lieutenant” in NTSB Docket DCA16FP003.
13 For more information, see “Interview of Manager of Flower Branch Apartments-Errata” in NTSB Docket
DCA16FP003.
6

<<<PAGE 17>>>

NTSB Pipeline Accident Report
when the explosion occurred. MCFRS dispatched units to the accident scene at 11:54 p.m., and
the first unit arrived at 11:58 p.m. to begin rescue and fire suppression efforts.14 Residents of
nearby apartment buildings within the complex voluntarily evacuated themselves.
The MCFRS Emergency Communication Center called WG at 12:08 a.m. on August 11,
2016. Within an hour of the initial notification, WG personnel arrived on scene and shut off the
4-inch diameter main supplying gas to the five apartment buildings along Arliss Street, and the
MCFRS responders extinguished the fire shortly thereafter.
The NTSB concludes that the postexplosion responses by both MCFRS and WG were
prompt and adequate.
1.3.4 Postaccident Gas Leak Surveys and Odorant Testing
NTSB investigators arrived on scene the morning of August 11, 2016. WG pressure tested
the main, which held pressure, indicating there was no leak.15 Soil bar hole tests were conducted
within 3 hours of the accident in areas adjacent to the main and the 2-inch service lines in the front
and back of buildings 8701 and 8703 detected no gas readings.16 Building 8701’s gas regulator
vent line, which is a pipe that directs the natural gas away from the building and into the
atmosphere in case of an over-pressure scenario, was also tested and showed no obstruction in the
vent line.
Overseen by the Public Service Commission of Maryland (PSC), WG performed
postaccident odorant testing at two different regulator stations in Silver Spring, Maryland, and
odorant levels were found compliant with Pipeline and Hazardous Materials Safety Administration
(PHMSA) regulations that require natural gas to be odorized and detected at 1/5th (or 20 percent)
of the lower explosive limit (LEL).
17 This safety feature is required for all distribution lines. The
State of Maryland has a more stringent requirement for odorant levels, which must be detectable
at 1/10th (10 percent) of the LEL.18 The testing indicated that the levels also complied with the
Code of Maryland Regulations (COMAR) requirement. At the Flower Branch complex, the natural
gas service lines were also tested for odorant levels and met the regulatory limits.19
14 For more information, see “Survival Factors” in NTSB Docket DCA16FP003 for detailed event chronology
and emergency response activities.
15 The operating pressure of the gas line that feeds into apartment buildings 8701 through 8711 Arliss Street was
measured to be 20 psig.
16 (a) Soil bar hole tests measure the amount of odorant in soil. (b) For more information, see “PSC Pipeline
Incident Investigation Report” in NTSB Docket DCA16FP003.
17 Odorant tests measure the amount of substances that have been added to gas provide a distinctive smell to
ensure regulatory safety requirements are met.
18 Title 49 Code of Federal Regulations (CFR) 192.625 and Code of Maryland Regulations (COMAR)
20.55.09.06.
19 For more information, see “Operations–DCA16FP003-OPS-Odorant Monitoring-1” in NTSB Docket
DCA16FP003.
7

<<<PAGE 18>>>

NTSB Pipeline Accident Report
1.3.5 Fire and Arson Investigations
During the incident, MCFRS requested the assistance of the US Bureau of Alcohol,
Tobacco, Firearms and Explosives (ATF). The ATF National Response Team responded to
investigate the source of the explosion and assist in locating the tenants of buildings 8701 and
8703. ATF conducted several interviews with residents in the days immediately following the
explosion. Both agencies concluded their field investigation on August 17, 2016. They found no
data to support the presence of explosives or a clandestine drug laboratory. In its report, ATF
concluded that the explosion was caused by a release of natural gas in the meter room of 8701
Arliss Street and excluded all other potential causes.20
The meter room of building 8701 had several potential natural gas ignition sources,
including open-flame ignition sources, such as burners on the water heater. Furthermore, electrical
equipment installed in the room could have produced electrical arcing (NFPA 2014).
1.3.6 Explosion Damage and Evidence
ATF documented and collected data to analyze the migration of the debris that projected
from the explosion. Debris from building 8701 was found as far as a parking lot 300 feet away.
The surrounding walls of the meter room on the north, south, and east sides were blown out and
into other apartments or adjacent rooms. The west wall of the meter room, which was below ground
level and backed by soil outside the building, did not appear to have any damage. The subsonic
pressure wave from the explosion also blew out windows from the apartment in the basement of
building 8701. Vehicles parked within the line of sight of the front entrance to building 8701 were
severely damaged due to explosion debris. Vehicles parked farther away from building 8701 were
found with significantly less or no damage.
The stairwell/hallway door to the meter room was the only door to have blown away from
its respective room, compared with the other stairway/hallway doors in building 8701 that had
separated from the frame and blown into their respective rooms. Also, according to the ATF report,
the concrete floor that separated the meter room and the above first-floor apartments had blown
upward and flipped over onto itself, which eliminated the scenario that an explosion could have
occurred above the meter room.21 Fire, heat, and structural damage in building 8703 was most
severe along the shared wall of the northwest quadrant of building 8701 and decreased in severity
farther away from the meter room. The shared north wall of the meter room blew away from the
meter room and into an apartment in building 8703. During the field inspection of the meter room,
an unconnected union of the vent line to the lower mercury service regulator was also found.
The victims of the explosion were found in the apartments closest to the meter room in
buildings 8701 and 8703. Autopsy reports identified the cause of death for each of the victims
from either impact from the explosion or from exposure from the intense heat. Based on the pattern
20 (a) ATF referred to the natural gas as “fugitive” in its report. (b) For more information, see “ATF Report” in
NTSB Docket DCA16FP003.
21 For more information, see “ATF Report” in NTSB Docket DCA16FP003.
8

<<<PAGE 19>>>

NTSB Pipeline Accident Report
of debris and the location of the victims, the NTSB concludes that the explosion radiated from the
meter room, where the gas meter assembly was located.
1.3.7 Gas Service to the Flower Branch Apartment Complex
Building 8701 received natural gas from a distribution system owned and operated by WG,
that also delivers natural gas to more than 1 million residential, commercial, and industrial
customers throughout Washington DC, and surrounding regions in Maryland and Virginia.22 WG
is required to comply with regulations from the US Department of Transportation (DOT), Title 49
Code of Federal Regulations (CFR) Part 192, and COMAR Title 20, Subtitle 55. In Maryland, WG
is periodically audited and inspected by the PSC to monitor compliance with both federal and state
regulations.
WG is required to service and maintain gas lines up to the outlet of the meter, also known
as “jurisdictional piping.
” All piping past the meter outlet to the appliances in the apartment, or
“house lines,
” are the responsibility of the property owners or the owners’ designee, such as Kay
Management, who install, operate, and maintain those lines in accordance with county regulations.
The local authority over Flower Branch Apartments is Montgomery County, which used the
2015 edition of the International Fuel Gas Code, as well as the 2015 Plumbing and Fuel Gas Code
of the Washington Suburban Sanitary Commission (WSSC) at the time of the incident (ICC 2015)
(WSSC 2015).
23
22 For more information, see https://www.washingtongas.com/about/company-profile. (Accessed August 26,
2016).
23 Washington Suburban Sanitary Commission is a water and wastewater utility that oversees water and sewer
pipelines in Prince George’s and Montgomery counties in Maryland.
9

<<<PAGE 20>>>

NTSB Pipeline Accident Report
2 Safety Issues
2.1 Introduction
The NTSB identified the following safety issues in the investigation of this accident:
(1) use of natural gas service regulators; (2) inspection of the gas meter assembly; (3) notification
of the gas odor to Kay Management, WG, and MCFRS; and (4) detection of natural gas through
odorants and methane.
2.2 Gas Meter Assembly Inspection
NTSB focused on the gas service equipment and appliances in the meter room because the
ATF’s investigation ruled out all other potential fuel sources in the room and the evidence indicates
that the explosion originated in the meter room. During the inspection of the basement level of
building 8701, NTSB investigators found burned and damaged components of the gas meter
assembly, which included the mercury service regulators. A detailed inspection revealed that the
vent line connection to the upper mercury service regulator was fractured below the coupling/union
assembly, and the lower mercury pressure regulator was not connected to the regulator vent line
at the coupling/union assembly, as shown in figure 5.
24
24 A union assembly is similar to a coupling and serves as an attachment between two external threaded pipes and
nipples. For more information, see “Materials Laboratory Factual Report No. 16-097” in NTSB Docket DCA16FP003.
10

<<<PAGE 21>>>

NTSB Pipeline Accident Report
Figure 5. Portions of mercury service regulators and gas meters in building 8701 showing
heat/fire/explosion damage and the unconnected lower regulator vent line.
ATF reconstructed the natural gas meter rack, piping, electric meters, and water heater.
The gas meters on the upper row of the meter rack near the regulators showed significant fire and
heat damage, particularly when compared with the gas meters farther away from the point of the
explosion at the west wall. (See figure 6.) The water heater showed significant fire and heat damage
and was found in the northeast quadrant of the meter room, about 6 feet from the nearest customer
gas meter. The water heater was placed by ATF at its pre-explosion location.
11

<<<PAGE 22>>>

NTSB Pipeline Accident Report
Figure 6. Building 8701 after debris removal and ATF reconstruction. The first two gas meters
(designated with a yellow arrow) show substantially more heat/fire damage than other meters.
(Photograph provided by ATF.)
2.3 Service Regulators
2.3.1 Service Regulator Overview
Service regulators are installed to a meter inlet to control the gas pressure into a building.
They reduce the high pressure used to transport natural gas through the delivery system to the
lower pressures used in homes and businesses. As a safety feature, regulators include a relief valve
that opens if the pressure of the regulated gas exceeds a specified pressure and the excess gas is
vented to the outside atmosphere.
Until the mid-1970s, some natural gas regulators included a reservoir, which is a cup-like
feature, filled with mercury. In such regulators, the mercury, which remains liquid at room
temperature, would serve as a liquid trap on the relief valve. If the gas pressure in the system was
too high, it would push the mercury aside, enabling the gas to pass through a vent and escape safely
outside of the building. In nonmercury service regulators, a spring mechanism with a diaphragm
is used as the safety relief valve.
12

<<<PAGE 23>>>

NTSB Pipeline Accident Report
According to WG, the regulators installed in building 8701 were also installed in all
26 buildings of the Flower Branch apartment complex between 1955-1956.25 The two mercury
service regulators and their associated piping in building 8701 will be referred to in this report as
the “upper” and “lower” service regulators. Based on similar installations in other nearby Flower
Branch apartments, it appears the lower regulator was installed about 2 feet above the floor, as
seen in figure 7.
25 (a) For more information, see “Operations – DCA16FP003 – Mercury Regulator Removal and Replacements”
in NTSB Docket DCA16FP003. (b) In the 1940s and 1950s, WG installed mercury service regulators manufactured
by Reynolds Gas Regulator Company, which is no longer in business. (c) The gas regulators from building 8701 were
marked “I-M-30,” which, according to WG, indicated they were a Reynolds Model 30, and were equipped with a
1/4-inch orifice. The same regulators also contained a metal tag indicating a 1955 manufacture date. (d) Although
some of these regulators were in the buildings in the Flower Branch apartment complex in 2016, they have all now
been removed and replaced.
13

<<<PAGE 24>>>

NTSB Pipeline Accident Report
Figure 7. Exemplar configuration of a mercury service regulator assembly in a similar Flower
Branch apartment building.
Figure 8 shows a close-up photograph of an exemplar mercury-filled service regulator.
14

<<<PAGE 25>>>

NTSB Pipeline Accident Report
Figure 8. Exemplar mercury service regulator taken from a nearby Flower Branch apartment
building.
Figure 9 shows a cross sectional image of the same regulator. A mercury service regulator
consists of the following moving internal parts:
1. Spring used to adjust the natural gas delivery pressure.
2. Leather diaphragm and metal diaphragm plate serve as the pressure-sensing elements
and translate pressure into a force to counterbalance the force of the spring.
3. Valve seat (also referred to as a disc) provides a positive shutoff under no-flow
conditions.
4. Linkage that transmits the motion of the diaphragm to the valve seat.
5. Orifice is the passageway where pressure is reduced as distribution gas flows.
6. Mercury cup to store a specified amount of mercury for overpressure protection.
15

<<<PAGE 26>>>

NTSB Pipeline Accident Report
Figure 9. Cross sectional image of a mercury service regulator. (Diagram provided by WG.)
In general, the gas regulator assembly operates as shown in figure 9. Under normal
operations, gas enters the regulator through the inlet and flows out of the outlet to the gas meter
and customer line. The size of the gap between the orifice and valve seat determines the amount
of gas that passes through the outlet. The size of the orifice also has a bearing on the outlet pressure,
but the size is predetermined prior to installation and remains fixed throughout the service life.
When there is no downstream demand for gas, the valve seat presses against the orifice,
and gas does not flow downstream. When downstream demand for gas increases (such as when
customer gas appliances are turned on), the pressure under the diaphragm decreases. This action
causes the diaphragm to move downward and the linkage to pivot so that the valve seat moves
away from the orifice, resulting in the gap between the orifice and valve seat.
As the valve seat moves away from the orifice, gas flow into the regulator increases.
Eventually, the downstream demand will decrease (fewer appliances are used or decreased usage),
and the pressure under the diaphragm will increase. This causes the valve seat to move closer to
the orifice and results in a reduced gas flow. The inlet pressure for the Flower Branch gas service
was 20 psig and the pressure downstream of the mercury service regulator ranged between 5 and
7 inches of water column (.20 -.25 psig).26
Mercury service regulators operate at a predetermined pressure set point. When the
pressure in the regulator exceeds its pressure set point, excess gas will flow through the mercury
and exit to the vent, which is often referred to as an overpressure or venting event. Gas vents
outside the building into the atmosphere through a vent line. As gas exits the vent line, the
houseline pressure stabilizes. A malfunctioning valve seat and orifice seal, a perforated diaphragm,
26 Inches of water column is a unit of pressure measurement for gas appliances.
16

<<<PAGE 27>>>

NTSB Pipeline Accident Report
and insufficient mercury can all lead to a venting event. Section 2.3.7 will discuss the rate of gas
flowing out of the vent under these three failure scenarios.
2.3.2 NTSB Materials Laboratory Examination of the Mercury Service Regulators
NTSB investigators recovered the gas regulator assembly from the basement of 8701 Arliss
Street and sent it to the NTSB Materials Laboratory in Washington, DC, for an examination.27
Figure 10 is a photograph of an approximate reconstruction of the preaccident
configuration of the service regulators, service line, pipeline to the meters, and vent line. The white
and yellow arrows pictured show the direction of the gas flow through the service line during
normal operation; the blue arrows show the direction of the gas flow under an over-pressure
scenario through the vent line.
27 For more information, see “Materials Laboratory Factual Report 16-097” in NTSB Docket DCA16FP003.
17

<<<PAGE 28>>>

NTSB Pipeline Accident Report
Figure 10. Mercury service regulators, service line, jurisdictional pipeline, and vent line after the
accident.
Investigators from the NTSB Materials Laboratory performed a compositional alloy
analysis on the mercury service regulators from the affected buildings and determined that the
body was made from a ferrous alloy, and the top cover and metal tags were made from an
aluminum alloy. The melting temperature of a typical aluminum alloy is about 1,220°F
18

<<<PAGE 29>>>

NTSB Pipeline Accident Report
(Moses 1978). The top cover and 2-inch diameter plug for the upper and lower gas regulator
assemblies were both melted from exposure to heat from the fire.28 Based on this observation, the
temperature in the general area of the gas regulator assemblies reached at least 1,220°F. This also
explains why mercury was not found in the reservoir cups of the upper and lower gas regulator
assemblies. Mercury exists as a liquid at room temperature and has a boiling point of about 674°F,
where it evaporates. The mercury most likely evaporated as a result of heat exposure from the fire.
The two regulators that serviced building 8701 were connected to one vent line, but each
regulator had its own union assembly. A union assembly is made up of three components: an
internal threaded nut, an insert, and a mating external threaded socket. Figure 11 shows a
photograph of the lower regulator union assembly parts before cleaning. The separation was
between the internal threaded nut (on the left) and the external threaded socket (on the right) of
the lower assembly.
Figure 11. Photograph of the lower regulator union assembly parts (before cleaning).
2.3.3 Upper Regulator Union Assembly
The vent port of the upper regulator contained internal threads. (See figure 12-C.) An
external threaded nipple and union assembly were separated from the vent port of the upper
regulator and the bottom end of the threaded nipple showed evidence of bending deformation
relative to the length of its axis. (See figure 12.) The bending deformation was in the general
direction as indicated by the arrow in figure 12-A. The first four internal threads on the vent port,
28 Plug is an access panel that allows for the service or inspection of the orifice and disc (valve seat). It is located
on one side of the regulator.
19

<<<PAGE 30>>>

NTSB Pipeline Accident Report
as shown in figure 12-C, showed thread damage that coincided with the damage observed on the
nipple. (See figure 12-B.) The observed damage is consistent with the damage that could occur if
the threaded nipple was forcefully pulled out of the mating regulator vent port.
Figure 12. A photograph of the exposed external threaded nipple from the upper regulator union
assembly.
NTSB investigators felt a slight looseness between the nut and insert portion when trying
to disconnect the union assembly between the nut and the external threaded socket; however, the
union assembly could not be rotated by hand. (See figure 12-A.) This indicated that the hermetic
seal between the ball portion of the union external socket and the nut was broken.29 This was
confirmed by a pressure test of the union assembly, which showed a leak at the nut and external
thread on the socket. The damage to the hermetic seal likely occurred from the force of the
explosion or intense heat exposure from the fire.
Therefore, the NTSB concludes that the upper mercury service regulator was most likely
connected to the vent line through the threaded nipple and union assembly prior to the explosion
in building 8701 and the regulator likely became separated from the vent line due to forces of the
explosion or from the building collapse.
29 Hermatic seal refers to something so tightly closed that no air or gas can enter or escape.
20

<<<PAGE 31>>>

NTSB Pipeline Accident Report
2.3.4 Lower Regulator Union Assembly
The separation of the union assembly for the lower regulator was between the external
threaded socket and internal threaded nut. The external threaded socket was attached to the
regulator vent port by an elbow and threaded nipple; and the mechanical connections between
them were firm. The union insert was connected to the vent line by a threaded nipple and a pipe
tee; and the mechanical connections between them were also firm.
Figure 13 shows the union assembly components after cleaning. The external threads of
the socket contained two dents; and the crown portion of the first two full external threads of the
socket showed minor deformation.
30 The external threaded socket showed no evidence of major
deformation. On one side of the nut, the crown portion of the first three internal threads showed
evidence of minor metal flow deformation; and NTSB investigators observed similar deformation
on an isolated area of only one thread on the diametrically opposite side. When mating threads are
pulled apart by force, fracture or deformation by shear of the threads can also be expected.31
However, NTSB investigators observed no evidence of deformation or fracture of the threads in
the nut and corresponding mating threads on the socket (compare figures 12 and 13 for thread
damage). Had the force of the explosion, falling debris, or a building collapse caused the
disconnection of the lower union assembly, there would be evidence of mechanical damage or
deformation through a significant portion of the engaged threads, as seen with the threaded nipple
for the upper regulator union assembly.
Figure 13. Photograph of the disassembled union assembly for the accident lower gas regulator
after cleaning.
30 Crown is the tip portion of a thread.
31 Shear stress occurs in mechanical components when coplanar forces are applied.
21

<<<PAGE 32>>>

NTSB Pipeline Accident Report
Therefore, the NTSB concludes that the external threaded socket of the lower mercury
service regulator union most likely was not threaded to the nut and, therefore, the lower mercury
service regulator was not connected to the vent line prior to the explosion.
2.3.5 Vent Line Inspection Practices
Records for the 5 years prior to the accident show that WG gas technicians had visited the
meter room at 8701 Arliss Street for different service calls on six occasions.32 In that time, WG
gas technicians visited the building twice to turn on gas service, which includes inspecting the
mercury regulator.33
WG written procedures required that a mercury service regulator be tested each time the
associated meter was set, reset, or changed. This procedure called to ensure that the vent line was
clear of debris and could appropriately direct the gas to the atmosphere during an overpressure
event. Part of the procedure for this test included disconnecting the vent line at the union, but did
not include verifying the line was reconnected. Although this procedure made no distinction
between single-family and multifamily structures, WG technicians told NTSB investigators that
this testing was, in practice, generally performed only on single-family homes. For multifamily
structures, such as apartment buildings, WG technicians only performed visual tests for debris and
the outdoor venting of lines.
34 They did not check whether or not lines were connected properly.
The NTSB concludes that without a requirement that technicians verify the connection of
vent lines for indoor service regulators, such vent lines could inadvertently be left open following
service work. Therefore, the NTSB recommends that WG revise its procedures and field forms to
require technicians to verify the integrity of vent lines following the testing of indoor service
regulators throughout the WG network.
2.3.6 Examination and Exclusion of Gas Appliances in the Meter Room
The only gas appliance in the meter room of building 8701 was the 81-gallon, natural
gas-fueled water heater that was installed on July 2, 2012.35 Kay Management maintenance staff
visually examined it every Monday to ensure it functioned properly through one on-off cycle. A
Kay Management maintenance engineer last inspected the water heater 2 days prior to the
explosion and found it to be in working order.
The water heater had an electronic pilot-light ignition. The main burner and pilot gases
would cut off during the off cycle when the tank water reached the preset temperature setting on
the thermostat. The main burner would not ignite if the pilot sensor did not first sense stable pilot
ignition. Changes in inlet gas pressure, negative air pressure into the ignition control module, and
the presence of a corrosive material/environment are all conditions that could activate the pilot
sensor and cause the pilot not to ignite. However, the pilot sensor could not detect flammable
32 WG records for meter room activity for 8701 Arliss Street.
33 WG turned on gas service for 8701 Arliss Street on September 27, 2012, and July 7, 2014.
34 For more information, see “Interview of Williams Meter Employee” in Docket DCA16FP003.
35 The water heater was State Water Heaters model SBD81-199-NE.
22

<<<PAGE 33>>>

NTSB Pipeline Accident Report
vapors and, therefore, it would allow the water heater to initiate operation and continue to operate
in the presence of flammable vapors.
In a postaccident examination, NTSB investigators observed that nearly half of the water
heater was covered with a U-shaped pattern of thermal damage. Visual examination of the water
heater by investigators showed no evidence of bulging or significant body deformation.
36 (See
figure 14.)
Figure 14. Hot water heater at the accident scene after the explosion. (Photograph provided by
ATF.)
In addition, a length of gas piping, which included the gas shut-off valve, was still attached
to the water heater. All the recovered piping associated with the water heater was heavily oxidized,
consistent with heat exposure, and all piping connections were found to be attached and threaded
completely. The recovered gas piping to the water heater had a full-diameter, through-thickness
fracture at the end of the section where the piping connected to the inlet on the gas control valve
assembly, near the bottom of the water heater. Figure 15 shows the main burner assembly and pipe
segment that separated from the gas control valve assembly. The fractured end of the pipe segment
36 For more information, see “Materials Laboratory Report 16-100 Hot Water Heater” in NTSB Docket
DCA16FP003.
23

<<<PAGE 34>>>

NTSB Pipeline Accident Report
showed evidence consistent with an overstress separation.37 Therefore, the NTSB concludes that
the gas piping to the water heater was most likely separated at the control valve due to overstress
forces resulting from the explosion. Furthermore, the NTSB concludes that the water heater did
not fail prior to the explosion and was not the source of the natural gas release in the meter room.
Gas control valve assembly
for the water heater
X1
X2
Main burner assembly
Figure 15. The main burner assembly, including the separated pipe and the gas control valve
assembly. The arrows labeled X1 and X2 indicate the pipe segment fractures at the threaded
portion.
2.3.7 Mercury Service Regulator Testing
The mercury service regulators sustained significant damage in the accident and could not
be functionally tested. Instead, the NTSB field tested mercury service regulators similar to the ones
damaged in the accident at the WG facility in Springfield, Virginia.
38 The testing included
regulator failure scenarios such as a complete loss of mercury in the reservoir, a malfunctioning
valve seat and orifice seal (valve seat obstruction), and a perforated diaphragm.39 The flowrates of
37 For more information, see “NTSB Materials Laboratory Factual Report No. 18-008” in NTSB Docket
DCA16FP003.
38 Detailed information on the testing can be found in “Washington Gas NTSB Party Submission re Building
Explosion Fire” in NTSB Docket DCA16FP003.
39 The exemplar gas regulator assembly was disassembled from another residence in the Flower Branch apartment
complex.
24

<<<PAGE 35>>>

NTSB Pipeline Accident Report
the mercury service regulators were measured under different loads, such as no houseline demand
and low-load houseline demand, and failure modes.
Valve seat obstruction failure testing was performed to measure the venting that followed
a small disruption at the regulator seal between the valve seat and the orifice seal. Table 1 shows
the results.
Table 1. Valve seat obstruction failure test data.
Houseline Demand
Relief or Houseline Pressure
(w.c.)
Relief Flowrate through Vent Line
(CFH)
No houseline demand 8 – 8.5 inches 165
Low-load houseline demand 7 – 7.5 inches 51
Investigators also tested the response of the regulator system to a diaphragm tear, a
“wide-open” failure where the valve seat pulled away from the orifice, allowing gas to freely flow
around the seat, into the houseline, and out of the vent line. During the testing, the vent lines were
metered with AC-250 diaphragm meters, which were necessary for flowrate determination. (See
table 2.) However, the meters did act as a slight restriction within the vent line. Meters are never
present on vent lines within an actual installation; with them removed, the houseline pressure
within a shut-in system dropped to 1.5 psig.40
Table 2. Diaphragm tear failure test data for a torn upper regulator.
Houseline Demand
Houseline
Pressure
(psig)
Relief Flowrate
Top Vent
(SCFH)a
Relief Flowrate
Bottom Vent
(SCFH)a
Combined
Flowrate
(SCFH)
No houseline
demand
1.75 1,170 1,020 2,190
Low-load houseline
demand
1.6 1,020 900 1,920
a The vent lines were metered with AC-250 diaphragm meters. These meters were necessary for flowrate determination; however,
they did act as a slight restriction within the vent line. Meters are never present on vent lines within an actual installation. With the
meters removed, the houseline pressure within a shut-in system dropped to 1.5 psig.
Investigators found through testing where mercury was completely removed from the
reservoir, the average mercury service regulator leakage rate through the vent piping was
331 standard cubic feet per hour (SCFH). This calculated average leakage rate was for testing
exemplar regulators 1, 2, and 3, and excluded exemplar regulator 4.41 Table 3 shows details on the
loss of mercury failure testing for each exemplar service regulator.
40 Houseline pressure is the natural gas pressure of the gas line leading into the home that connects the gas
appliances.
41 Exemplar regulators 1, 2, and 3 were Reynolds Model 30 mercury service regulators and exemplar regulator 4
was a Schlumberger Model B-39 nonmercury service regulator.
25

<<<PAGE 36>>>

NTSB Pipeline Accident Report
Table 3. Loss of mercury failure test data.
Exemplar
Regulator
System Pressure
(psig)
Ambient
Temperature
(°F)
Leakage through
Vent, observed Qobs
(CFH)
Pressure
Downstream
of Rotameter,
Pact
(psig)
Flow through
Vent
corrected
Qcorr
(SCFH)
1 20.1 61 197 344
2 20.5 64 163 18.9 320
3 20.5 65 184 13.4 330
4 20.4 65 260 2.4a 360
11.8 a A B-39 regulator seat was removed during testing, representing a system failure mode not expected in the field.
In addition, investigators pumped gas into the exemplar mercury service regulators at
20 psig⸺the same inlet pressure of the Flower Branch apartment complex⸺and observed how
they functioned under different load demands of gas. During the field testing, NTSB investigators
heard gas forcefully exiting the vent. This corroborated interview statements of a resident who
heard a “weeping” or hissing noise outside the basement on the day of the accident, and WG and
contractor service technicians who reported that when a mercury service regulator begins to fail
and venting gas, that type of noise is heard and a gas odor can be detected. The NTSB concludes
that the audible hissing noise heard by a resident, the evidence of past mercury service regulator
failures, the pre-existing unconnected vent line union, and the lack of evidence of any pre-existing
anomalies in the gas piping or gas appliances indicate that a failed mercury service regulator was
the most likely source of the natural gas release in the meter room of building 8701. Discussion of
past mercury service regulator failures is found in section 2.3.9.
2.3.8 Natural Gas Accumulation in the Meter Room of Building 8701
Natural gas is composed mostly of methane, with lesser amounts of nitrogen, ethane, and
propane, and traces of butane, pentane, hexane, carbon dioxide, and oxygen.42 Gas companies add
an odorant, such as methyl mercaptan, as a safety measure so it can be easily detected by smell if
there is a leak.43 The flammability range for natural gas has an LEL of 3.9 percent to 4.5 percent,
and an upper explosive limit (UEL) of 14.5 percent to 15 percent. Natural gas can be explosive if
it is in a confined area, if the concentration of gas is between the LEL and UEL, and an ignition
source is present (NFPA 2017).
The NTSB completed a study report using a computational fluid dynamics (CFD) model
to estimate the time for natural gas released from a failed mercury service regulator to create an
atmosphere in the meter room with a concentration sufficient to support an explosive event
(NTSB 2018a). The mercury service regulator failure mode selected for the model was the “valve
seat obstruction,” as described in section 2.3.8. The CFD model simulated two different cases
using the data from the valve seat obstruction failure testing. (See table 1.) One case assumed that
there was no demand for gas by the building appliances (no house load) and, therefore, the service
regulator had a constant vent leakage rate of 165 SCFH. The other case assumed a 165 SCFH
leakage rate and periodic demand for gas by the water heater, during which time the service
42 For more information on the composition of the gas at the Flower Branch Complex, see “Gas Composition on
August 10, 2016 to Flower Branch Complex (Silver Spring, MD)” in NTSB Docket DCA16FP003.
43 Methyl mercaptan is a colorless gas with a strong odor similar to that of rotten eggs.
26

<<<PAGE 37>>>

NTSB Pipeline Accident Report
regulator vent leak would reduce to zero. The water heater was assumed to be active 20 minutes
of every hour. WG provided gas composition analysis and the concentration for LEL for the gas
being delivered to the Flower Branch apartments on the day of the accident. The LEL was reported
to be 4.78 percent, which was used in the model. The general configuration of the meter room can
be seen in figure 16.
Figure 16. Three-dimensional visualization of the meter room.
According to the time stamp of the alarm records, the last maintenance person locked the
meter room at 8:42 p.m., and the explosion occurred at 11:51 p.m. There were no reports of gas
odors by residents or maintenance crew at or before 8:42 p.m. The next person to detect a gas odor
was a resident of building 8701 who arrived home about 30 minutes before the explosion.
Therefore, the natural gas had about 3 hours to accumulate to its explosive range.
Both cases of the scenario representing the valve seat obstruction failure of the mercury
service regulator yielded a buoyant natural gas leak that began filling the meter room from the top
down. In the case where the gas leak was continuous, a gas concentration greater than LEL formed
between the ceiling and 48 inches above the floor within the first hour. In the low-leakage rate
case where the gas leak was interrupted by the water heater’s operation, a gas concentration greater
than LEL formed between the ceiling and 48 inches above the floor within the first hour and a
half.
44 The mercury service regulator failure scenario for the low leakage rate case reached LEL
44 The average concentration of the gas in the room, from the ceiling to the floor, measured at about 12-inch
increments, reached LEL in 1 hour and 54 minutes when the leak was continuous and 2 hours 40 minutes when the
leak was being interrupted.
27

<<<PAGE 38>>>

NTSB Pipeline Accident Report
in the timeframe established in the investigation, and the other failure modes with higher leakage
rates would result in shorter time frames to support an explosive event.
Therefore, the NTSB concludes that a low leakage rate of venting natural gas from a
mercury service regulator with an obstructed orifice, and other regulator failure scenarios with
higher leakage rates, could have allowed the gas concentration to build up to an explosive
atmosphere in the meter room between 8:42 p.m. and the time of the explosion at 11:51 p.m.
2.3.9 Mercury Service Regulator Replacement
As of December 2018, WG has replaced about 175,000 mercury service regulators in total
and has about 125,000 mercury service regulators still in service throughout its system.
Within WG’s Operations and Maintenance Manual were specific procedures for mercury
service regulators. In addition, it specified conditions which required the mercury service
regulators to be replaced:
• The regulator has “blown” or is weeping gas through the vent.
• The regulator is being tested and fails the functional and lock-up test, or malfunctions.45
• The system is being uprated to a MAOP above 25 psig.
• The service is being replaced.
• The connecting piping is being altered or replaced, making it practical to change the
regulator.
• The regulator is scheduled for removal (WG 2016).
Mercury is a metal that is toxic to human health when exposed through inhalation or
ingestion. When released into the environment, mercury may evaporate and become an invisible,
odorless, toxic vapor. Between October 2011 and September 2016, WG replaced 12,174 mercury
service regulators in their system. Of those, 11,182 mercury service regulators were replaced to
mitigate potential environmental risks. The US Environmental Protection Agency (EPA) issued a
recommended management practice for the safe removal of mercury containing devices, such as
mercury service regulators in May 2011 (EPA 2011). The design of mercury service regulators
include materials such as leather diaphragms and rubber valve seats that are subject to age-related
deterioration. The remaining 992 regulators were replaced due to performance failure identified
by service technicians.46 Of those, 631 were caused by venting and 293 were caused by mercury
leaking out of the reservoir. Venting or a leaking body connection was found to be the cause of
failure in 63 percent of the mercury service regulators and mercury blew out of the reservoir in
about 30 percent of the failed mercury service regulators. Although WG identified a leaking or
45 These tests examine the functionality of the service regulators to ensure it does not exceed its set pressure or
leak gas.
46 In this report, WG technicians include both permanent WG and contract employees.
28

<<<PAGE 39>>>

NTSB Pipeline Accident Report
torn diaphragm as another possible failure, it was not recorded for any of the mercury service
regulator failures found in their system.
Furthermore, while reviewing WG field records for 8701 Arliss Street, NTSB investigators
discovered erroneous entries identifying mercury service regulators as nonmercury service
regulators.47 WG did not review field entry forms to ensure data entry accuracy and did not have
a system-wide master list identifying the location of each mercury service regulator. The NTSB
concludes that WG relied on unvalidated information to determine the location and condition of
mercury service regulators. Therefore, the NTSB recommends that throughout the WG network,
WG implement an audit program to verify the data on the service forms used to determine the
location and condition of mercury service regulators to ensure the accuracy of this safety-critical
data. In addition, the NTSB recommends that following WG’s successful completion of Safety
Recommendation P-19-009, PSC, the Commonwealth of Virginia State Corporation Commission
Division of Public Utility Regulation, and the Public Service Commission of the District of
Columbia audit and verify the performance of WG’s mercury service regulator replacement
program, including its recordkeeping.
2.3.10 Location of Natural Gas Service Regulators
Mercury service regulators, along with all types of natural gas service regulators, must
comply with 49 CFR Part 192, which is under the authority of PHMSA. In the regulation, they are
classified as “service regulators” and defined as a “device on a service line that controls the
pressure of gas delivered from a higher pressure to the pressure provided to the customer. A service
regulator may serve one customer or multiple customers through a meter head or manifold.”48
PHMSA regulations include minimum requirements for the location, protection, and
installation of service regulators. Service regulators must be installed in a “readily accessible
location and be protected from corrosion and other damage” and be located “as near as practical
to the point of service line entrance.”49 Service regulators must have vents that “terminate
outdoors” and vent “into the atmosphere and away from any opening into the building.” If located
outside, the regulators also must be protected from damage from flood or vehicle traffic.50
The service regulators in building 8701 were located inside the basement and were
connected to an outside vent line. When the mercury service regulator failed on August 10, the
excess natural gas flow was not properly vented to the outside because of the unconnected union
assembly from the lower service regulator. The natural gas accumulated in the basement until it
reached its explosive range and ignited from one of the many possible ignition sources in the room.
The NTSB concludes that the failure of a service regulator, combined with an unconnected
vent line, poses a significant threat to people and property with little warning. In particular, the
risk of mercury service regulator failure is increased because of their age. Therefore, the NTSB
recommends that WG establish a time frame with specific dates and milestones for the replacement
47 WG 5-year service records from October 2011 to September 2016 for 8701 Arliss Street.
48 Title 49 CFR 192.3, “Definitions.”
49 Title 49 CFR 192.353, “Customer meters and regulators: Location.”
50 Title 49 CFR 192.355, “Customer meters and regulators: Protection from damage.
”
29

<<<PAGE 40>>>

NTSB Pipeline Accident Report
of its mercury service regulators throughout the WG network that recognizes the need to expedite
this program and that prioritizes multifamily dwellings where mercury service regulators are
located inside the property. In addition, the NTSB recommends that the PSC, the Commonwealth
of Virginia State Corporation Commission Division of Public Utility Regulation and the Public
Service Commission of the District of Columbia oversee the replacement process for the mercury
service regulators that WG has in service.
Many dwellings that use natural gas have meters and service regulators outdoors, so that
should a regulator fail, the gas release is directed into the atmosphere and does not accumulate to
explosive levels inside a structure. However, in many multifamily structures, including the
buildings of Flower Branch apartments, service regulators are indoors, but isolated and
inaccessible to residents. The NTSB concludes that had service regulators been located outside
building 8701, the explosion would not have occurred because gas would have vented to the
atmosphere and dissipated. The NTSB recommends that PHMSA require that all new service
regulators be installed outside occupied structures. Additionally, the NTSB recommends that
PHMSA require existing interior service regulators be relocated outside occupied structures
whenever the gas service line, meter, or regulator is replaced. In addition, multifamily structures
should be prioritized over single-family dwellings. In addition, the NTSB recommends that WG
install all new service regulators outside occupied structures. Further, the NTSB recommends that
WG relocate existing interior service regulators outside occupied structures whenever the gas
service line, meter, or regulator is replaced. In addition, multifamily structures should be
prioritized over single-family dwellings.
2.4 Natural Gas Odor Notification
2.4.1 Kay Management
Kay Management staff reported that when residents applied for a rental apartment, they
would provide a “move-in package” to the new tenants. This included documents such as a copy
of their application, parking rules, permits, an amenity sheet, and floor plan. Residents were
verbally told that that if they had any problems, such as a gas odor or an appliance that is not
working, to call the 24-hour emergency number for Kay Management. Residents were provided a
telephone number for WG, but only for starting new gas service for their apartment. The package
did not provide any written guidance on how to report a gas odor to WG.
Kay Management provided in-house training to its maintenance staff to detect a gas leak
in an apartment. They were instructed to use a TIF gas detector to search for a leak after receiving
a gas odor call from a resident.
51 If staff members did not find a leak, they would continue to test
other apartments and rooms within the building. If gas was detected in the apartment, staff
members were instructed to check to see if they could make a quick repair, such as replacing a
knob on a gas stove or relighting the pilot light. The staff members may also do a soap test, if
51 TIF Instruments is an electronics company that develops leak detection instruments and lab technology for field
service technicians.
30

<<<PAGE 41>>>

NTSB Pipeline Accident Report
needed, to determine the source of the leak.52 If they were unable to do the repair, they would
schedule an appointment with a plumbing contractor who was certified to repair house lines. If the
plumbing contractor determined that the issue was not because of the house line, but a
jurisdictional line, the plumbing contractor would report the issue to Kay Management that would
then call WG.53
2.4.2 Washington Gas
WG is required by PHMSA to have a public awareness plan to keep the public and local
emergency responders aware of pipeline operations and related safety issues in the event of a gas
leak or fire.
54 Specifically, the company periodically mails information to its customers, such as a
pamphlet sent with monthly billing statements. In the event of a gas leak, the WG website directs
individuals to first call 9-1-1 and then WG. In addition, the company maintains a Gas Operations
Dispatch Center, staffed by trained personnel, that receives notification of gas-related emergencies
and immediately dispatches the closest service technician to the reported leak site. WG procedures
require that leaks and emergency orders be given priority over nonemergency work and calls
off-duty employees to perform additional work if the emergency exceeds the capacity of personnel
on duty.
WG technicians have expertise with gas infrastructure and are generally equipped with
instruments and detection methods that could identify methane at lower concentrations. WG
procedures require that when an odor complaint is received, technicians conduct a leak
investigation. When that occurs, the technician will not leave the area until the potential leak is
“investigated, graded, and/or repaired, or until confirming that there is not a gas leak.” If the
technician cannot gain access to the area of the suspected inside leak, the gas is required to be
turned off and a reasonable effort made to obtain access. If this cannot be accomplished, the
technician is to leave a contact card for the customer and notify dispatch that the gas is turned off
(WG 2016).
Had WG been notified of the July 25 odor complaint, they likely would have investigated
further to confirm a natural gas leak and take steps to stop it if one occurred.
2.4.3 Montgomery County Fire and Rescue Services
MCFRS has a specific policy and procedure for responding to natural gas incidents. The
procedure states that after a rescue unit is dispatched to a natural gas incident, a unit officer
confirms there is a gas leak and classifies it as either a “major” or “minor” leak, based on its
severity.
55 Examples of a major leak would be one that has migrated throughout an occupied
structure, health care facility, or high occupancy structure with high life-hazard risks or a leak from
52 (a) A soap test is a method in which a soap solution is used to detect leaks. It is commonly used in the gas
industry. (b) For more information, see interview transcripts of maintenance personnel for the Flower Branch
apartment complex for Kay Management employees in NTSB Docket DCA16FP003.
53 For more information, see the interview transcript of the president of Kay Management in NTSB Docket
DCA16FP003.
54 Title 49 CFR 192.616, “Public awareness.
”
55 According to MCFRS, a major leak is “a natural gas leak with an imminent threat of life safety,
” and a minor
leak is “a leak not believed to pose an imminent threat of life safety,” and that does not involve a fire.
31

<<<PAGE 42>>>

NTSB Pipeline Accident Report
a transmission (nonodorized) supply pipeline. Under MCFRS guidelines, the incident commander
is then required to establish a Level II Command and “request additional resources as needed.” In
addition, the guidelines state that gas personnel are to be considered the “expert natural gas
resource officer (MCFRC 1996).”
When a leak is confirmed, the incident commander sets up a hot zone and restricts the area
to fire service personnel in full protective turnout equipment and eliminates all ignition sources
within that zone. Fire personnel then checks all occupancies in the immediate vicinity for the
presence of natural gas and, if present, evacuates the occupants and ventilates the structure. The
minor gas leak procedure includes a provision for the gas company technician to report to the
incident commander upon arrival.
However, the MCFRS policy and procedure did not specify how and when to notify the
gas company. The NTSB believes the applicable gas company should be notified after responders
have been notified whenever a member of the public calls 9-1-1 to report a gas odor or a gas leak.
In this particular situation, those calls were received by the Montgomery County Emergency
Communication Center (ECC), which used specific protocols for their dispatchers. The ECC used
Protocol-60 Gas Leak/Gas Odor (Natural and LP [liquified petroleum] Gases) when receiving a
9-1-1 call for a gas odor/leak (IAED 2014). The ECC purchased its protocols from Priority
Dispatch, a research company that provided products and training for emergency call-taking
centers. Priority Dispatch worked in conjunction with the International Academies of Emergency
Dispatch (IAED), who authored the Protocol-60 Gas Leak/Gas Odor (Natural and LP Gases)
protocol. However, Protocol-60 Gas Leak/Gas Odor (Natural and LP Gases) did not direct the
dispatcher to contact the gas company during a gas odor/leak call. The NTSB concludes that had
WG been notified of the gas odor call on July 25, 2016, a service technician may have had the
opportunity to enter the meter room of building 8701, identify the unconnected vent line, and
remedy the situation, potentially preventing the gas release and explosion that occurred on
August 10, 2016. Therefore, the NTSB recommends that the IAED revise Protocol-60 Gas
Leak/Gas Odor (Natural and LP Gases) to direct dispatchers to notify the gas company when any
odor call is received.
2.5 Odorant and Methane Detection of Natural Gas
2.5.1 Odorant Detection
Natural gas regulations that have required the addition of odorant to natural gas distribution
pipelines were first promulgated by DOT in 1970 (Federal Register, 1970, 13247). Because these
gas systems are situated primarily in populated areas, the odorant can act as an early warning of a
gas release to prevent an explosion and fire. In the United States, all odorants contained sulfur
because of its unique odor that when detected could be associated with natural gas. Pipeline
operators selected a blend of a sulfur-based odorants that were the most appropriate for their
pipeline network. Odorant was the primary safety feature that members of the public relied upon
to detect a natural gas release (GAO 2018).
However, soon after the odorant regulations were issued, the Research and Special
Programs Administration (RSPA) observed problems with the odorization practices, the
32

<<<PAGE 43>>>

NTSB Pipeline Accident Report
effectiveness of commercial odorants in use, as well as odorant fading, and commissioned a study
by the Institute of Gas Technology to study these issues.
56 RSPA was particularly concerned about
odor fading because a number of uncontrolled releases of natural gas went undetected, leading to
explosions and fires that caused severe injury, death, and extensive property damage (RSPA 1975).
The study noted that odorant could be stripped from natural gas through the adsorption or
absorption on pipeline walls, particularly new main pipelines; oxidation by the presence of iron
oxide and traces of oxygen; and adsorption through the soil.57 The study recommended a solution
for odorant fade in new pipelines by applying coatings to the internal surface of gas mains to
prevent odorant adsorption. However, the study did not find a solution to address odorant
adsorption through soil, and the study recommended “research efforts for developing an odorant
blend that will have better soil penetration characteristics.”
In subsequent years since the RSPA study was published, government, industry, and
academia have researched the issue of odorant fade. In 1998, the DOT Transportation Safety
Institute recommended that gas companies develop odorization programs which would consist of
odorant selection criteria, method of injection, and verification of odor intensity (Bull 1998). That
same year, a chemical company, Elf Atochem North America, Inc., proposed that companies use
different mercaptans blended with sulfide components as an alternate odorant with effective soil
penetrability. Additionally, various odorant blends have been studied and distinguished by their
physical and chemical properties, which reflect their resistance to oxidation and ability to pass
through soil (Usher 1999). Despite these proposed solutions, PHMSA regulations do not address
methods for mitigating odorant fade when natural gas migrates through soil. Furthermore, NTSB
continues to recognize odorant fade as a contributing factor in many gas pipeline accidents.
Appendix B contains examples of 20 accidents between 1971 and 2018 where natural gas
had either migrated from an outside leak or within a structure and accumulated to dangerous
concentrations leading to explosions, fires, fatalities, injuries, and severe property damage. NTSB
identified within those investigations whether gas odorant played a significant role in warning the
occupants about the presence of gas in buildings. In some cases, the occupants smelled gas but
failed to report the odor due to a lack of awareness about the dangers of natural gas. In some cases,
gas odor was not detected by the occupants of the building in time for them to evacuate before the
explosion occurred, despite the odorant levels being compliant with regulatory requirements. In
several of these cases, the NTSB cited odorant fade due to soil adsorption as a contributing factor.
Since the Pipeline Safety Improvement Act of 2002 was signed into law, gas companies
have been required to educate the public through public information programs on the hazards of
natural gas and specifically outline steps for public safety in the event of a pipeline release.58
56 (a) Before PHMSA was created in 2004, RSPA was the entity within the DOT responsible for regulating the
pipeline industry. (b) The Institute of Gas Technology was founded in 1941 at the Illinois Institute of Technology. In
2000, the Institute combined with the Gas Research Institute to form the Gas Technology Institute.
57 Adsorption is the process by which a material such as a gas, liquid, or solute, adheres to the surface of another
material that is a solid or liquid. Absorption is the process in which a material is dissolved by another material, such
as a liquid or solid.
58 Section 5 of the Pipeline Safety Improvement Act of 2002 requires gas companies to have a public education
program to advise affected municipalities, school districts, businesses, and residents of pipeline facility locations.
33

<<<PAGE 44>>>

NTSB Pipeline Accident Report
However, as illustrated in this accident, as well as some of the accidents discussed in appendix B,
public awareness programs do not guarantee that gas odors will be appropriately reported.
Kay Management and WG staff provided information to residents of the Flower Branch
apartment complex on what to do if they detect gas odors. They were supposed to contact both
WG and the fire department. However, only one call was made to authorities⸺the call was made
only to the fire department⸺regarding the odor, despite several residents attesting to noticing the
odor for several weeks prior to the accident.
While olfactory senses can provide warning of a gas leak, they cannot be relied upon in
every situation as a primary means of detecting the presence of hazardous gas concentrations. As
illustrated in a 2016 document from the British Standards Institution (BSI), the European standard
for combustible gas detectors, EN 50244, states that most people may be able to detect gas odors
at very low levels of 2 percent LEL or less; however, this can depend on an individual’s sensitivity
to the odor, medical conditions, and the phenomena of olfactory fatigue (BSI 2016).
59 Although
in many cases, gas odorants effectively warn about the presence of gas leaks, too often personal
decisions to report gas leaks and evacuate buildings are connected to the intensity by which
individuals are able to smell gas odors. PHMSA odorant requirements rely on a person with a
“normal sense of smell” and assumes that when the odor is detected, there is adequate time to
evacuate, identify, and resolve the leak before the gas accumulates to explosive levels.
60 However,
as demonstrated by many NTSB investigations, gas odorant does not always provide sufficient
warning of gas leaks and hazardous conditions and, under certain conditions, a gas leak can go
undetected. For instance, in many multifamily structures gas regulators are located in locked
rooms, basements, or other areas that are not readily accessible to residents. Therefore, the NTSB
concludes that the use of gas odorants alone does not effectively mitigate the risk of death and
injuries caused by gas system leaks, such as the undetected leak that occurred at the Flower Branch
apartment complex.
2.5.2 Methane Detection
The seven fatalities in the August 10 explosion were residents located in apartments in
buildings 8701 and 8703, closest to the basement meter room. Had there been an alarm to warn of
a natural gas release, residents, especially those closest to the meter room, could have been notified
earlier to evacuate to a safe place away from the building, without relying on someone to smell
gas odors to identify the hazard. The NTSB concludes that had methane detectors been installed
at the Flower Branch apartment complex, an alarm would have alerted residents to a gas release
on either July 25, 2016, or August 10, 2016, reducing the potential and consequences of a natural
gas explosion.
The NTSB has recommended previously that “gas detectors” be required to provide early
warning of gas leaks in buildings. NTSB first issued this recommendation as a result of an
investigation into a gas explosion that occurred in a commercial building in New York City,
59 Olfactory fatigue is when a person’s sense of smell adapts to an odor after prolonged exposure and is unable to
recognize the smell temporarily.
60 According to 49 CFR 192.625 (a), “Odorization of gas,” “a combustible gas in a distribution line must contain
a natural odorant or be odorized so that at a concentration in air of one-fifth of the lower explosive limit, the gas is
readily detectable by a person with a normal sense of smell.”
34

<<<PAGE 45>>>

NTSB Pipeline Accident Report
New York, on April 22, 1974 (NTSB 1976). Building personnel had smelled gas odors in the
basement, but the explosion occurred before the gas could be shut off, injuring 70 people. The
report noted that many commercial buildings were required to have smoke or heat detectors placed
in strategic interior locations; therefore, it seemed logical for similar requirements to be adopted
for installing gas detectors. As a result of this investigation, the NTSB recommended the US
Department of Housing and Urban Development (HUD) to:
Investigate the practicality and the availability of gas vapor detection instruments
for installation at strategic locations in buildings. Based on the results of this
investigation, recommend guidelines to appropriate State and local government
agencies for regulations for the installation of gas detection instruments in
buildings. (P-76-12)
HUD responded that gas detectors were technically possible, but the agency did not believe
they were practical at the time. HUD responded that it would continue to review developments in
the field and would reevaluate their position “when a practical, cost effective natural gas detection
system is developed.”
NTSB made a similar safety recommendation from the investigation of a gas explosion and
fire that occurred in a retirement home in Allentown, Pennsylvania, on June 9, 1994 (NTSB 1996).
Workers hit a gas service line while performing excavation work; gas entered the home and ignited.
Although workers and residents inside the home smelled gas and reported it to the gas company,
they did not evacuate before the explosion occurred. The NTSB investigation found that the
performance and cost-effectiveness of gas detectors had improved in the 20 years since Safety
Recommendation P-76-12 was issued. Therefore, the NTSB recommended in Safety
Recommendation P-96-16 that HUD:
Evaluate the safety benefits of using gas detectors in buildings approved by the
Department for Federal rent subsidies as a means of providing building occupants
and local emergency-response agencies with early notice of released natural gas
within buildings; require that gas detectors be used in buildings in which the
Department has determined that a gas detector would be cost effective and
beneficial. (P-96-16)
For 5 years, HUD did not respond to this safety recommendation. In July 2001, HUD
declined to implement the recommendation because it claimed that it did not have the statutory
authority and that gas detection should be required in the National Fire Code.61 The NTSB
classified this safety recommendation as Closed⸺Unacceptable Action.
Currently, methane gas or combustible gas alarms are not required by federal or state
regulations, nor are they required in building or fire codes for residential occupancies. While
smoke and carbon monoxide alarm requirements have been incorporated into many state
regulations, methane detection alarms have not been widely adopted due to initial reservations
regarding the reliability of the technology (NCSL 2018). Although some states and cities have
considered requiring the use of this technology because of their own major natural gas incidents,
61 Letter from HUD to NTSB, July 19, 2001.
35

<<<PAGE 46>>>

NTSB Pipeline Accident Report
the proposed bills or state regulations have not been implemented. It is unlikely that these proposals
will be enacted until the devices perform more reliably and there is adequate industry guidance for
both performance and installation. For example, legislation has been proposed in the New York
Assembly that would require all temporary and permanent dwellings in the state to install an
operable combustible gas detector. Further, it would require that the detector be wirelessly
connected to the gas company. This legislation, A 2913, also requires gas companies to annually
publish a report of gas leaks broken down by county. A 2913 has been referred to the Assembly
Governmental Operations Committee, but the committee has not taken any action on the
proposal.
62 New York City went further and enacted a local law that revised its housing
maintenance and building codes to require the installation of natural gas detection devices once an
industry standard has been developed.63
Operations Technology Development (OTD), a membership-controlled partnership of
natural gas distribution companies that studies new technologies, is currently researching methane
detection technology in residential occupancies (OTD 2018).
64 OTD initiated the Residential
Methane Detectors (RMD) program, which is currently being overseen by one of its members, the
Gas Technology Institute (GTI). Other members, such as WG, are also providing funding for the
program. The program began in 2014 and involves researching and testing commercially available
methane detectors, evaluating consumer behavior for adoption of the technology, and reviewing
and developing industry standards for the installation and maintenance of methane detectors.
OTD presented the RMD program at a PHMSA Research and Development forum in
November 2016 (Wiley 2016). At these forums, representatives from academia or industry
proposes projects and PHMSA will follow with a solicitation for projects that aligns with its
research interests. However, PHMSA rejected the proposal and did not follow with a solicitation
for research on residential methane detection after the OTD program was presented. Therefore, the
RMD program has remained an industry-funded effort.
The RMD program evaluated commercially available metal oxide semiconductor methane
detectors that sound an alarm when gas concentrations exceed a specified set-point. In
December 2017, the RMD program completed its pilot testing phase of various commercially
available methane detectors using a nationally recognized testing laboratory (OSHA 2018).
65 As
documented in a GTI report, the devices were tested under different conditions such as extreme
temperatures and humidity, exposure to multiple chemicals, different detection limits for methane
(5 percent, 10 percent, and 25 percent LEL), and reduced voltage supply (GTI 2017). The program
found many commercially available methane detectors are not reliable and may be subject to false
alarms because of interference with household chemicals or exposure to extreme temperatures and
62 New York State Senate Bill A2913, https://www.nysenate.gov/legislation/bills/2019/A2913, Accessed April 9,
2019.
63 New York City Council, Local Law 157, Int 1100-2016, http://legistar.council.nyc.gov/LegislationDetail.aspx?
ID=2576426&GUID=D9EE7190-AF91-411D-A017-8305FF6D6F0D&Options=Advanced&Search. Accessed
November 5, 2018.
64 OTD is a member-driven, not-for-profit organization that identifies, selects funds, and oversees research
projects that are intended to improve safety, reliability, and operational efficiency in the gas utility industry.
65 OSHA certifies a private-sector organization that meets the legal requirements under 29 CFR 1210.7 to perform
testing and certification of procedures using consensus-based testing standards.
36

<<<PAGE 47>>>

NTSB Pipeline Accident Report
humidity. The next stages in the RMD program involve additional testing that is expected to be
completed in 2018, and also a placement study to develop a scientific rationale for
recommendations on where to best locate the residential methane detectors inside buildings.
One natural gas company, Consolidated Edison Company of New York, is participating
with a consortium of gas companies in the testing phase of the RMD program.66 The company
officially began a pilot program to install 9,000 units in New York City in November 2018.67 The
detectors trigger an alarm when a leak is detected at 10 percent LEL and communicates directly to
the gas company’s emergency response center, that dispatches a technician and notifies the local
fire department. The alarm also has a voice-activated message that alerts residents to evacuate and
to call 9-1-1.
To address methane detector reliability, the RMD program has identified an existing
industry standard, the American National Standards Institute (ANSI)-approved, product standard
by the Underwriter’s Laboratories, UL 1484 Safety for Residential Gas Detectors, which covers
electrically operated gas detectors that detect both propane and methane in residential occupancies
and recreational vehicles (UL 2016). This standard currently permits alarms to operate at a
detection limit of 25 percent of the LEL for methane, or 5 percent volume of air, which is the limit
where most commercially available alarms are set. The RMD program advocates lowering this
detection limit to 10 percent LEL for methane so that the alarms will provide earlier notification
of a gas release. Industry standards in other countries, such as Great Britain, have established lower
detection limits for natural gas detection alarms to provide early notification. The British standard
sets visual indicators and audible alarms for combustible gases to operate at “a volume ratio above
3 percent LEL and below 20 percent LEL (BSI 2009).”
The RMD program’s ongoing research and development of new and existing technology
is intended to resolve the uncertainties with methane detection. However, once the technology is
established, standards will need to be developed to ensure the proper installation, maintenance,
and testing requirements, including effective and safe detection limits. The NTSB concludes that
the development of a national code that establishes methane-detection performance criteria and
requires the technology to be installed in residential and commercial buildings with natural gas
service would provide a redundant means of leak detection to supplement the use of odorants.
In the United States, the National Fire Protection Association (NFPA) and the International
Code Council (ICC) are nationally recognized standard-setting bodies for both building and fire
codes, as well fuel gas codes such as the International Fuel Gas Code (IFGC) (ICC 2015) and the
National Fuel Gas Code (NFPA 54) (NFPA 2018). The IFGC and NFPA 54 provide minimum
safety requirements for the design and installation of fuel gas piping systems in homes and other
nonindustrial buildings, though, neither of them requires methane detection alarms. These codes
are adopted across the nation and incorporated either in state or local regulations. They also apply
66 As a result of the natural gas-fueled building explosion and fire in East Harlem, New York City on March 12,
2014, the New York State Public Service Commission agreed as part of the settlement to the Consolidated Edison
Company that the company provide improvements for detection and response to gas leaks, which included remote
methane detection equipment.(NTSB 2015).
67 (a) Letters from Consolidated Edison Company to the New York State Public Service Commission, January 3,
2017, and July 2, 2018; (b) “PSC Announces $25.5 Million East Harlem Settlement,” press release, July 12, 2018.
37

<<<PAGE 48>>>

NTSB Pipeline Accident Report
to gas service pipelines entering structures, which is under the jurisdiction of the local authority
and the responsibility of the owner to implement. For example, at the Flower Branch apartment
complex, the gas service piping after the gas meter is regulated by Montgomery County, which
has adopted the WSSC Code that incorporates by reference the 2015 International Fuel Gas
Code.68
The NTSB concludes that the scope of NFPA 54, IFGC, and their widespread adoption by
local authorities appear to be the most appropriate standards for requiring methane detector alarms,
with local jurisdictions enforcing the requirements and making them feasible. Therefore, the NTSB
recommends that, in coordination with NFPA and ICC, the GTI work to develop standards for
methane detection systems for all types of residential occupancies in both the IFGC and the
National Fuel Gas Code, NFPA 54. At a minimum, the provisions should cover the installation,
maintenance, placement of the detectors, and testing requirements. Further, the NTSB
recommends that, in coordination with GTI and ICC, the NFPA revise the National Fuel Gas
Code, NFPA 54 to require methane detection systems for all types of residential occupancies with
gas service. At a minimum, the provisions should cover the installation, maintenance, placement
of the detectors, and testing requirements. Lastly, the NTSB recommends that, in coordination
with GTI and NFPA, the ICC incorporate provisions in the IFGC that requires methane detection
systems for all types of residential occupancies with gas service. At a minimum, the provisions
should cover the installation, maintenance, placement of the detectors, and testing requirements.
68 Currently, the WSSC Plumbing and Fuel Gas Board is considering a proposal to adopt the 2018 IFGC.
38

<<<PAGE 49>>>

NTSB Pipeline Accident Report
3 Postaccident Actions
Since the explosion, WG has taken a number of initiatives involving safety messaging
when a release of natural gas is suspected, including:
• Distributing 10,000 door-hanging signs in multiple languages communicating the
importance of calling the gas company upon smelling natural gas to multifamily
buildings in Montgomery County, Maryland, that have gas service.
• Continuing to work closely with local fire departments in the Washington, DC,
region on improving communications to ensure WG is alerted each time the
jurisdiction received notice of a possible odor of natural gas.
• Developing a plan for a coordinated response with local first responders when a
possible odor of natural gas is detected.
In addition, WG is planning equipment improvements, including:
• Installing new service regulators to the exterior of 8701 Arliss Street and any new
multifamily dwelling construction projects in the Flower Branch apartment
complex, reducing the risk of high gas flow releasing into the interior of the
buildings.
• Simultaneously replacing all legacy multimeter sets with old service lines and
moving them to the exterior of the building.
Furthermore, WG has installed thermal safety valves in all new and replaced metered
facilities, which shut off the flow of gas in the event of a structure fire, reducing further damage
from an incident.69
69 Detailed information on the testing can be found in “Washington Gas NTSB Party Submission re Building
Explosion Fire” in NTSB Docket DCA16FP003.
39

<<<PAGE 50>>>

NTSB Pipeline Accident Report
4 Conclusions
4.1 Findings
1. The postexplosion responses by both Montgomery County Fire and Rescue Service and
Washington Gas Light Company were prompt and adequate.
2. Based on the pattern of debris and the location of the victims, the explosion radiated
from the meter room, where the gas meter assembly was located.
3. The upper mercury service regulator was most likely connected to the vent line through
the threaded nipple and union assembly prior to the explosion in building 8701 and the
regulator likely became separated from the vent line due to forces of the explosion or
from the building collapse.
4. The external threaded socket of the lower mercury service regulator union most likely
was not threaded to the nut and, therefore, the lower mercury service regulator was not
connected to the vent line prior to the explosion.
5. Without a requirement that technicians verify the connection of vent lines for indoor
service regulators, such vent lines could inadvertently be left open following service
work.
6. The gas piping to the water heater was most likely separated at the control valve due to
overstress forces resulting from the explosion.
7. The water heater did not fail prior to the explosion and was not the source of the natural
gas release in the meter room.
8. The audible hissing noises heard by a resident, the evidence of past mercury service
regulator failures, the pre-existing unconnected vent line union, and the lack of
evidence of any pre-existing anomalies in the gas piping or gas appliances indicate that
a failed mercury service regulator was the most likely source of the natural gas release
in the meter room of building 8701.
9. A low leakage rate of venting natural gas from a mercury service regulator with an
obstructed orifice, and other regulator failure scenarios with higher leakage rates, could
have allowed the gas concentration to build up to an explosive atmosphere in the meter
room between 8:42 p.m. and the time of the explosion at 11:51 p.m.
10. Washington Gas Light Company relied on unvalidated information to determine the
location and condition of mercury service regulators.
11. The failure of a service regulator, combined with an unconnected vent line, poses a
significant threat to people and property with little warning.
40

<<<PAGE 51>>>

NTSB Pipeline Accident Report
12. Had service regulators been located outside building 8701, the explosion would not
have occurred because gas would have vented to the atmosphere and dissipated.
13. Had Washington Gas Light Company been notified of the gas odor call on July 25, a
service technician may have had the opportunity to enter the meter room of building
8701, identify the unconnected vent line, and remedy the situation, potentially
preventing the gas release and explosion that occurred on August 10.
14. The use of gas odorants alone does not effectively mitigate the risk of death and injuries
caused by gas system leaks, such as the undetected leak that occurred at the Flower
Branch apartment complex.
15. Had methane detectors been installed at the Flower Branch apartment complex, an
alarm would have alerted residents to a gas release on either July 25, 2016, or
August 10, 2016, reducing the potential and consequences of a natural gas explosion.
16. The development of a national code that establishes methane-detection performance
criteria and requires the technology to be installed in residential and commercial
buildings with natural gas service would provide a redundant means of leak detection
to supplement the use of odorants.
17. The scope of National Fire Protection Association 54, International Fuel Gas Code,
and their widespread adoption by local authorities appear to be the most appropriate
standards for requiring methane detector alarms with local jurisdictions enforcing the
requirements and making them feasible.
4.2 Probable Cause
The National Transportation Safety Board determines that the probable cause of the
explosion in building 8701 of the Flower Branch apartment complex was the failure of an indoor
mercury service regulator with an unconnected vent line that allowed natural gas into the meter
room where it accumulated and ignited from an unknown ignition source. Contributing to the
accident was the location of the mercury service regulators where leak detection by odor was not
readily available.
41

<<<PAGE 52>>>

NTSB Pipeline Accident Report
5 Recommendations
As a result of this investigation, the National Transportation Safety Board makes the
following new safety recommendations:
To the Pipeline and Hazardous Materials Safety Administration:
Require that all new service regulators be installed outside occupied structures.
(P-19-001)
Require existing interior service regulators be relocated outside occupied structures
whenever the gas service line, meter, or regulator is replaced. In addition,
multifamily structures should be prioritized over single-family dwellings.
(P-19-002)
To the Public Service Commission of Maryland, the Commonwealth of Virginia State
Corporation Commission Division of Public Utility Regulation, and the Public Service
Commission of the District of Columbia:
Following Washington Gas’s successful completion of Safety Recommendation
P-19-009, audit and verify the performance of Washington Gas’s mercury service
regulator replacement program, including its recordkeeping. (P-19-003)
Oversee the replacement process for the mercury service regulators that
Washington Gas has in service. (P-19-004)
To the International Academies of Emergency Dispatch:
Revise Protocol-60 Gas Leak/Gas Odor (Natural and Liquified Petroleum Gases)
to direct dispatchers to notify the gas company when any odor call is received.
(P-19-005)
To the International Code Council:
In coordination with the Gas Technology Institute and the National Fire Protection
Association, incorporate provisions in the International Fuel Gas Code that
requires methane detection systems for all types of residential occupancies with gas
service. At a minimum, the provisions should cover the installation, maintenance,
placement of the detectors, and testing requirements. (P-19-006)
To the National Fire Protection Association:
In coordination with the Gas Technology Institute and the International Code
Council, revise the National Fuel Gas Code, National Fire Protection
Association 54 to require methane detection systems for all types of residential
occupancies with gas service. At a minimum, the provisions should cover the
42

<<<PAGE 53>>>

NTSB Pipeline Accident Report
installation, maintenance, placement of the detectors, and testing requirements.
(P-19-007)
To the Gas Technology Institute:
In coordination with the National Fire Protection Association and the International
Code Council, work to develop standards for methane detection systems for all
types of residential occupancies in both the International Fuel Gas Code and the
National Fuel Gas Code, National Fire Protection Association 54. At a minimum,
the provisions should cover the installation, maintenance, placement of the
detectors, and testing requirements. (P-19-008)
To Washington Gas Light Company:
Throughout the Washington Gas network, implement an audit program to verify
the data on the service forms used to determine the location and condition of
mercury service regulators to ensure the accuracy of this safety-critical data.
(P-19-009)
Revise your procedures and field forms to require technicians to verify the integrity
of vent lines following the testing of indoor service regulators throughout the
Washington Gas network. (P-19-010)
Establish a time frame with specific dates and milestones for the replacement of
mercury service regulators throughout the Washington Gas network that recognizes
the need to expedite this program and that prioritizes multifamily dwellings where
mercury service regulators are located inside the property. (P-19-011)
Install all new service regulators outside occupied structures. (P-19-012)
Relocate existing interior service regulators outside occupied structures whenever
the gas service line, meter, or regulator is replaced. In addition, multifamily
structures should be prioritized over single-family dwellings. (P-19-013)
43

<<<PAGE 54>>>

NTSB Pipeline Accident Report
BY THE NATIONAL TRANSPORTATION SAFETY BOARD
ROBERT L. SUMWALT, III EARL F. WEENER
Chairman Member
BRUCE LANDSBERG JENNIFER HOMENDY
Vice Chairman Member
Report Date: April 24, 2019
Vice Chairman Bruce Landsburg filed the following concurring statement.
44

<<<PAGE 55>>>

NTSB Pipeline Accident Report
Board Member Statement
Vice Chairman Bruce Landsberg filed the following concurring statement on April 25, 2019.
Chairman Robert L. Sumwalt, III and Member Earl Weener joined in this statement.
While concurring with the report, I believe there is an education opportunity for first
responders, property owners, and code enforcement personnel. This tragedy might have been
prevented had the Montgomery [County] Fire Department had access to the meter service room
on July 25th, as required by the fire code.
Because Kay Management had changed the lock in February 2016, and failed to provide a
key to the fire department, the first responders were unable to gain access, despite the report of gas
odor. They pried the top of door partially open to insert a gas detector probe but no gas was noted
and they decided not to pursue it further. Neither Washington Gas nor Kay Management was
notified.
As noted in the Board meeting, the concentration of gas mixtures, air currents, odorant
concentration, and sensitivity of various measuring devices all affect the ability to detect the
presence of gas. From the NTSB Report,“Between September 2015 and June 2016, Kay
Management received six gas odor calls from residents of 8701 Arliss Street. Members of its
maintenance staff said that when they investigated, they either did not detect gas through their
gas-detection equipment or would report that the painting of apartments was causing the smell.
During this period, MCFRS fire personnel responded to an odor call at building 8701 on July 25,
2016. According to interviews with Flower Branch residents and employees from Kay
Management, residents in the building routinely called either the management company or 9-1-1
to report gas odors.”
As a result, perhaps several opportunities to prevent the explosion were missed. While the
Board declined to make a recommendation, the various trade associations and publications should
offer a case study of this accident to code enforcement, first responder, and building management
organizations. Maintaining access to rooms having gas meters or appliances is not only required
by code, it is essential to safety. Likewise building management and maintenance personnel should
understand the seriousness of such reports, especially when repetitive and take appropriate action.
First responders must have immediate access to such places. If for any reason they are
unable, building management must be reachable 24/7 to provide immediate access - No
exceptions! Further, first responders must immediately seek to gain access with building
management, especially when inspecting closed spaces containing gas equipment within
multi-family buildings.
A placard/sign should be placed adjacent to the lockbox or entrance providing an
emergency phone number and a notice that when keys or combinations are changed, that they must
be placed in the lockbox.
First responder training should include scenarios recreating this circumstance, so crews
know how to respond when this situation is invariably repeated. It cannot be said with certainty
that had the first responders gained access to the meter room on July 25th the accident would have
45

<<<PAGE 56>>>

NTSB Pipeline Accident Report
been prevented, but it might have. Given the loss of life and property, both looking backward and
forward, this seems like a very small and easily accomplished action.
46

<<<PAGE 57>>>

NTSB Pipeline Accident Report
6 Appendix
6.1 Appendix A: The Investigation
The National Transportation Safety Board (NTSB) was notified around 2:00 a.m. on
August 11, 2016, of an explosion and fire at the Flower Branch apartment complex in
Silver Spring, Maryland. A team of seven, including an investigator-in-charge, investigators,
representatives from Transportation Disaster Assistance, and an attorney from the office of
General Counsel, launched to the scene later that morning.
Parties to the investigation included the Pipeline and Hazardous Materials Safety
Administration (PHMSA), Public Service Commission of Maryland (PSC), Montgomery County
Fire and Rescue Service (MCFRS), Montgomery County Police Department (MCPD), and
Washington Gas (WG).
6.2 Appendix B: Sample of 20 NTSB Investigations of Residential and
Commercial Building Pipeline Accidents Between 1971 and 2018
a. On October 4, 1971, in Fort Worth, Texas, a house exploded and burned when gas
ignited and exploded inside the home as a resident tried to light her gas stove. The
resident sustained major burns to over 50 percent of her body. Natural gas had migrated
from an improperly installed plastic service saddle-tapping nipple connection into the
house, which ultimately failed, and load stresses from the operation of heavy
construction equipment over the connection and heavy rainfall that caused the soil to
exert pressure on the pipe (NTSB 1972).
b. On March 24, 1972, in Annandale, Virginia, a contractor backhoe snagged a 2-inch
steel gas main. Gas company personnel arrived 40 minutes later and started searching
for the break but did not shut off the gas, check for gas in the nearby houses, or call
emergency responders. About 20 minutes later, gas had leaked from the main and into
the houses. One house exploded, and then a few minutes later two other homes
exploded and burned, killing three and injuring one. A number of residents had smelled
gas in their houses, but only one reported it to the gas company (NTSB 1972a).
c. On April 22, 1973, in El Paso, Texas, an explosion occurred at a 15-unit apartment
complex, killing seven people and injuring eight. Residents had smelled gas odor the
day before the explosion but had not alerted the fire department or the gas company.
The educational materials provided by the gas company on procedures to follow in case
of a gas leak contributed to the problem because they were only printed in English and
were sent to an area that housed a primarily Latino population. In addition, no
emergency number was provided on the materials. The gas leak had occurred from a
broken cast-iron reducer and also from two corrosion leaks from the gas main
(NTSB 1974).
47

<<<PAGE 58>>>

NTSB Pipeline Accident Report
d. On December 2, 1973, in Charleston, West Virginia, a gas explosion occurred at a
single-family home, followed by an intense fire that killed three people and injured
two. The fire was initially extinguished by the local fire department and the gas was
shut off, but another fire rekindled from the gas-saturated soil. The NTSB determined
the probable cause of the explosion and fire was an accumulation of natural gas that
had released from two corroded holes of a gas main, which had migrated into the house
and ignited. Residents in the home had smelled a slight odor the day before the accident,
but did not report it to the gas company or fire department. The natural gas was tested
and found to have met the federal requirements for odorant level. The NTSB
contributed the odor fade to filtering of the odorant through the soil and olfactory
fatigue (NTSB 1974a).
e. On April 22, 1974, in New York City, New York, an explosion occurred at a
commercial building, injuring 70 people. The NTSB determined that the probable cause
of the accident was a rupture of an overpressure hydropneumatics tank which rocketed
upward and tore an overhead gas service line, which allowed an uncontrollable flow of
gas into the building, which ignited and exploded. Personnel who went into the
basement to check on the water smelled a gas odor, but the building exploded before
the gas could be shut off. The NTSB issued a recommendation to the US Department
of Housing and Urban Development to require gas vapor detection instruments for
installation at strategic locations in buildings (NTSB 1976).
f. On January 10, 1976, in Fremont, Nebraska, a natural gas main failed due to contraction
caused by cold weather that caused the pipe to pull out of its compression coupling and
release gas. The gas seeped into a hotel, eventually accumulating and igniting, causing
an explosion and fire that killed 20 and injured 39 people. The gas company had
received multiple odor calls an hour before the explosion occurred. The gas technicians
responded but could not identify the leak in time. An evacuation order was issued about
20 minutes before the explosion, but that was not sufficient time for everyone to leave
the building (NTSB 1976a).
g. On December 15, 1977, in Lawrence, Kansas, a natural gas main pulled out of a
compression coupling which was jointed to a steel gas main. Natural gas released and
migrated through the stone foundation walls of a three-story apartment building and an
adjacent bakery, which then accumulated and ignited. The result was an explosion and
fire that killed two residents and injured three. One of the employees of the bakery had
smelled a gas odor, but did not call the gas company (NTSB 1978).
h. On June 28, 1982, in Portales, New Mexico, a natural gas explosion killed five people
and injured one person in a single-family home. The natural gas release was caused by
a failed service line that had been damaged from earlier excavation work for the local
telephone company over a month before the accident occurred. Between the time of the
excavation work and the explosion, no one had detected gas and did not report it. The
natural gas was tested and found to have met the federal requirements for odorant level.
At that time there was high rainfall in the region. The NTSB concluded that the odorant
compounds in the gas were absorbed in the surrounding soil where the gas leaked from
the service line. Soil samples were taken and supported this conclusion (NTSB 1983).
48

<<<PAGE 59>>>

NTSB Pipeline Accident Report
i. On September 25, 1984, in Phoenix, Arizona, an intense natural gas-fed fire destroyed
two apartments in an apartment building, killing five residents and injuring seven. The
probable cause of the accident was the weakening of a plastic main that failed and
released natural gas that migrated through the soil and under two apartments, where it
accumulated and ignited by a gas pilot light of a furnace. Prior to the accident, residents
smelled gas, but failed to report it to the gas company (NTSB 1985).
j. On December 6, 1985, in Derby, Connecticut, a natural gas explosion and fire
destroyed a restaurant, killing 6 people and injuring 12 inside. Also, one passerby and
one firefighter were also injured. Gas had released into the restaurant from a broken
gas main that migrated into the basement of the restaurant and ignited and exploded.
Restaurant personnel and patrons detected the gas odor, but did not report it to the gas
company of the fire department prior to the accident (NTSB 1986).
k. On June 9, 1994, in Allentown, Pennsylvania, a natural gas explosion occurred at a
retirement home. Excavation work was being performed outside the home when a
natural gas service line was hit. The fugitive gas flowed underground, passed through
an opening in the building foundation, and migrated to other floors. Eventually the gas
accumulated and ignited, causing an explosion, killing 1, and injuring 66. Workers and
residents inside the home smelled gas and reported it to the gas company, but did not
complete the evacuation before the explosion occurred. The NTSB recommended to
the US Department of Housing and Urban Development to evaluate the safety benefits
of using gas detectors and to require an approved device in buildings similar to the
retirement home (NTSB 1996).
l. On October 17, 1994, in Waterloo, Iowa, an explosion and fire occurred at a
neighborhood tavern, killing six, severely injuring one, and causing several minor
injuries. The NTSB determined that the service pipeline had failed due to stress
intensification that was primarily caused by shifting soil settlement at a connection to
a steel main. The service pipeline had poor resistance to brittle cracking. Odorant levels
were tested and found in compliance with federal requirements (NTSB 1998).
m. On July 7, 1998, in South Riding, Virginia, a house exploded, killing one and injuring
three others. The accident was caused by the failure of a gas service line to the home
that had been located too close to an electrical service line that overheated and arced.
The uncontrolled release of gas accumulated into the basement and ignited. The owner
of the house did not smell gas before going to bed, which was about 2 hours before the
explosion occurred. A resident located 150 feet away smelled gas 30 minutes before
the explosion, investigated, and called the gas company when he could not locate the
source. Minutes later, the explosion occurred (NTSB 2001).
n. On December 13, 2005, in Bergenfield, New Jersey, an apartment building exploded
after natural gas migrated into the building from a damaged distribution service
pipeline due to nearby excavation work that was being performed the same day. The
building exploded while contractors and gas company service technicians were
working to shut off the gas. Three residents were killed and five were injured. Although
49

<<<PAGE 60>>>

NTSB Pipeline Accident Report
some residents smelled gas, people remained in the building because there was no
evacuation order (NTSB 2007).
o. On March 5, 2008, in Plum Borough, Pennsylvania, an explosion and fire occurred at
a single-family home, killing one person and severely injuring a child. The NTSB
determined that the gas distribution pipeline had been damaged from excavation work
from years before which created corrosive conditions, causing the pipe to fail. No one
smelled gas 30 minutes prior to the explosion, and the gas was thought to have migrated
through a porous backfill of a new sewer line and accumulated rapidly in the house
with little warning to residents. Odorant levels were tested and found in compliance
with both federal and state requirements (NTSB 2008).
p. On December 24, 2008, in Rancho Cordova, California, an explosion and fire occurred
at a house, killing one person and injuring five others, including a utility employee and
one firefighter who were hospitalized. The NTSB determined that the main pipeline
had inadequate wall thinning that allowed gas to leak from a mechanical coupling that
was installed 2 years before the accident. Residents had smelled gas prior to the
accident and called the gas company. Although the gas company personnel were in the
process of locating the leak, they did not promptly evacuate the residents and the public.
The delayed response contributed to the accident (NTSB 2010).
q. On December 17, 2013, in Birmingham, Alabama, a two-story duplex at a public
housing project exploded when natural gas in an apartment ignited, killing one resident
and injuring three others. Residents said they had smelled gas outside the surrounding
apartments earlier in the night but reported that it was only a faint smell and they did
not notify the fire department. The NTSB determined that the probable cause was the
accumulation of natural gas released from a corroded main that cracked from tree root
growth. The NTSB report noted that when odorized natural gas passes through the soil,
it can absorb and deplete the odorant from the gas (NTSB 2016).
r. On March 12, 2014, two adjacent multi-occupancy, five-story buildings in Manhattan,
New York City, were destroyed by a natural gas-fueled explosion and fire, killing 8,
injuring more than 50 people, and displacing over 100 families from their home. The
NTSB found that a defective fusion joint at the service tee allowed natural gas to leak
from the gas main and migrated into the building where it ignited. During postaccident
interviews, residents reported smelling gas the evening prior, but did not report it to the
gas company (NTSB 2015).
s. On August 2, 2017, the NTSB investigated a school building in Minneapolis,
Minnesota, that was destroyed by a natural gas explosion, killing two individuals and
injuring nine. At the time of the explosion, two workers were installing new piping to
support the relocation of gas meters from the basement of the building to the outside.
As gas company employees were removing the existing piping, a natural gas line
pressure opened, releasing gas into the basement. A school maintenance worker
smelled the natural gas and went to the basement meter room where the gas company
employees had been working. He exited the basement, announcing over his handheld
radio there was gas in the building and that everyone should evacuate immediately.
50

<<<PAGE 61>>>

NTSB Pipeline Accident Report
However, less than 1 minute later, the building exploded. At the time of this report, this
investigation is still open (NTSB 2017).
t. On February 21, 2018, in Dallas, Texas, a natural gas-fueled explosion occurred at a
single-family home, killing a 12-year old juvenile and injuring four other family
members. The family reported they had not smelled any natural gas prior to the
explosion. At the time of this report, this investigation is still open (NTSB 2018).
51

<<<PAGE 62>>>

NTSB Pipeline Accident Report
References
ASME (The American Society of Mechanical Engineers). Welded and Seamless Wrought Steel
Pipe. ASME B36.10M-2018. (New York: ASME).
Bull, David, 1998. [Title] 49 CFR § 192.625: Odorization: A Matter of Protection. White paper.
April 1998. (Washington, DC: US Department of Transportation, Transportation Safety
Institute).
BSI (British Standards Institution). 2009. Electrical apparatus for the detection of combustible
gases in domestic premises. Part 1. “Test methods and performance requirements.”
(London: BSI).
----. 2016. Electrical apparatus for the detection of combustible gases in domestic premises. Guide
on the selection, installation, use and maintenance. EN50244. (London: BSI).
EPA (US Environmental Protection Agency). 2011. Before You Tear it Down, Get the Mercury
Out.(https://www.epa.gov/sites/production/files/2015-
10/documents/before_you_tear_it_down.pdf.), accessed September 5, 2018.
FR (Federal Register). 1970. Vol. 35, no. 161 (August 19).
GAO (US Government Accountability Office). 2018. Gas Pipeline Safety: Stakeholders and
Officials’ Views of Federal Odorizing Requirements. GAO-18-409. (Washington, DC:
GAO).
GTI (Gas Technology Institute). 2017. Residential Methane Detector Program, Phase II. Prepared
for Operations Technology Development. (Des Plaines, Illinois: GTI).
IAED (International Academies of Emergency Dispatch). 2014. Protocol-60 Gas Leak/Gas Odor
(Natural and Liquified Petroleum Gases). (Salt Lake City, Utah: IAED).
ICC (International Code Council). 2015. International Fuel Gas Code. (Washington, DC: ICC).
MCFRC (Montgomery County Fire and Rescue Commission). 1996. Policy and Procedure,
“Natural Gas Incident Response.” No. 25-07. (Rockville, Maryland: MCFRC).
Moses, Alfred J., 1978. Practicing Scientist’s Handbook. (New York: Van Nostrand Reinhold
Company).
NCSL (National Conference of State Legislatures). 2018. “Carbon Monoxide Detector
Requirements, Laws and Regulations.” (http://www.ncsl.org/research/environment-and-
natural-resources/carbon-monoxide-detectors-state-statutes.aspx), accessed November 5,
2018.
NFPA (National Fire Protection Association). 2017. Guide for Fire and Explosion Investigations.
Section 10.2.1, “Natural Gas.” NFPA 921. (Quincy, Massachusetts: NFPA).
52

<<<PAGE 63>>>

NTSB Pipeline Accident Report
----. 2018. National Fuel Gas Code. NFPA 54. (Quincy, Massachusetts: NFPA).
NTSB (National Transportation Safety Board). 1972. Lone Star Gas Company, Fort Worth, Texas,
October 4, 1971. PAR-72/05. (Washington, DC: NTSB).
----. 1972a. Washington Gas Light Company, Natural Gas Explosion, Annandale, Virginia,
March 24, 1972. PAR-72/04. (Washington, DC: NTSB).
----. 1974. Southern Union Gas Company, El Paso, Texas, April 22, 1973. PAR-74/02.
(Washington, DC: NTSB).
----. 1974a. Columbia Gas of West Virginia, Inc., Charleston, West Virginia, December 2, 1973.
PAR-74/04. (Washington, DC: NTSB).
----. 1976. Consolidated Edison Company Explosion, New York, New York, April 22, 1974.
PAR-76/02. (Washington, DC: NTSB).
----. 1976a. Nebraska Natural Gas Company, Pathfinder Hotel Explosion and Fire, Fremont,
Nebraska, January 10, 1976. PAR-76/06. (Washington, DC: NTSB).
----. 1978. Kansas Public Service Company, Inc. Explosion and Fire, Lawrence, Kansas,
December 15, 1977. PAR-78/04. (Washington, DC: NTSB).
----. 1983. The Gas Company of New Mexico Natural Gas Explosion and Fire, Portales,
New Mexico, June 28, 1982. PAR-83/01. (Washington, DC: NTSB).
----. 1985. Arizona Public Service Company Natural Gas Explosion and Fire, Phoenix, Arizona,
September 25, 1984. PAR-85/01. (Washington, DC: NTSB).
----. 1986. Northeast Utilities Service Company Explosion and Fire, Derby, Connecticut,
December 6, 1985. PAR-86/02. (Washington, DC: NTSB).
----. 1996. UGI Utilities, Inc., Natural Gas Distribution Pipeline Explosion and Fire, Allentown,
Pennsylvania, June 9, 1994. PAR-96/01. (Washington, DC: NTSB).
----. 1998. Fire and Explosion, Midwest Gas Company, Waterloo, Iowa, October 17, 1994.
PAB-98/02. (Washington, DC: NTSB).
----. 2001. Natural Gas Explosion and Fire, South Riding, Virginia, July 7, 1998. PAR-01/01.
(Washington, DC: NTSB).
----. 2007. Natural Gas Service Line Break and Subsequent Explosion and Fire, Bergenfield,
New Jersey, December 13, 2005. PAB-17/01. (Washington, DC: NTSB).
----. 2008. Natural Gas Distribution Line Break and Subsequent Explosion and Fire,
Plum Borough, Pennsylvania, March 5, 2008. PAB-08/01. (Washington, DC: NTSB).
----. 2010. Explosion, Release, and Ignition of Natural Gas, Rancho Cordova, California,
December 24, 2008. PAB-10/01. (Washington, DC: NTSB).
53

<<<PAGE 64>>>

NTSB Pipeline Accident Report
----. 2015. Natural Gas-Fueled Building Explosion and Resulting Fire, New York, New York,
March 12, 2014. PAR-15/01. (Washington, DC: NTSB).
----. 2016. Pipeline Accident Brief: Birmingham Public Housing Gas Explosion, Birmingham,
Alabama, December 17, 2013. PAB-16/01. (Washington, DC: NTSB).
----. 2017. Preliminary Report: Pipeline: Gas Explosion Destroyed Minnehaha Academy,
Minneapolis, Minnesota, August 2, 2017. DCA17MP007. (Washington, DC: NTSB).
----. 2018. Preliminary Report: Natural Gas-Fueled Explosion of Residence, Dallas, Texas,
February 23, 2018. PLD18FR002. (Washington, DC: NTSB).
----. 2018a. Materials Laboratory Study Report. 18-039S. (Washington, DC: NTSB).
OSHA (Occupational Safety and Health Administration). 2018. “OSHA’s Nationally Recognized
Testing Laboratory (NRTL) Program.” (https://www.osha.gov/dts/otpca/nrtl/index.html),
accessed November 5, 2018.
OTD (Operations Technology Development). 2018. “Strengthening North America’s Energy
Infrastructure.” (https://www.otd-co.org/about/Pages/default.aspx), accessed November 5,
2018.
RSPA (Research and Special Programs Administration). 1975. Study of the Properties of the
Numerous Odorants and Assessment of their Effectiveness in Various Environmental
Conditions to Alert People to the Presence of Natural Gas. (Washington, DC: US
Department of Transportation, RSPA).
UL (Underwriter’s Laboratories). 2016. Standard for Residential Gas Detectors. (Northbrook,
Illinois: UL).
Usher, M.J., 1999. Odor Fade – Possible Causes and Remedies. White paper. (Philadelphia,
Pennsylvania: Elf Atochem North America, Inc. and London: CGA Gas Measurement
School).
WG (Washington Gas). 2016. Operations and Maintenance Manual. Revision 27. (Washington,
DC: WG).
Wiley, K. 2016. “Methane Detection Projects.” Presentation to the Pipeline and Hazardous
Materials Safety Administration Research and Development Forum, November 16, 2016,
Cleveland, Ohio.
WSSC (Washington Suburban Sanitary Commission). 2015. Plumbing and Fuel Gas Code.
(Laurel, Maryland: WSSC).
54

## Provenance

- Official: Yes
- Source: <https://www.ntsb.gov/investigations/Pages/DCA16FP003.aspx>
- Source ID: `ntsb-pipeline`
- SHA-256: `d1f8a5b2b327d05b739cada0065ef236049cb0d592e7086632c81d78da3e690d`
- Retrieved: 2026-08-20T04:57:25.499Z
- Exported: 2026-08-23T21:26:32.518Z
- Document slug: `ntsb-case-dca16fp003`

### Source metadata

```json
{
  "recordKind": "ntsb_pipeline_investigation",
  "mkey": 93845,
  "ntsbNumber": "DCA16FP003",
  "completionStatus": "Completed",
  "caseClosed": true,
  "hasSafetyRecommendation": true,
  "eventType": "Accident",
  "accidentType": "Leak/explosion/fire",
  "operator": "Washington Gas Light Company",
  "pipelineType": "Distribution",
  "location": {
    "city": "Silver Spring",
    "state": "MD",
    "country": "USA",
    "latitude": null,
    "longitude": null
  },
  "reportNumber": "PAR1901",
  "probableCause": "The National Transportation Safety Board determines that the probable cause of the explosion in building 8701 of the Flower Branch apartment complex was the failure of an indoor mercury service regulator with an unconnected vent line that allowed natural gas into the meter room where it accumulated and ignited from an unknown ignition source. Contributing to the accident was the location of the mercury service regulators where leak detection by odor was not readily available.",
  "events": [
    {
      "eventNumber": 7,
      "sequenceNumber": 4,
      "eventCode": "400170",
      "tier1Number": "400",
      "tier1Name": "System operating",
      "tier2Number": "170",
      "tier2Name": "Explosion",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 11,
      "sequenceNumber": 5,
      "eventCode": "700180",
      "tier1Number": "700",
      "tier1Name": "Post-release",
      "tier2Number": "180",
      "tier2Name": "Fire/explosion (post-release)",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 12,
      "sequenceNumber": 6,
      "eventCode": "600060",
      "tier1Number": "600",
      "tier1Name": "Emergency response",
      "tier2Number": "060",
      "tier2Name": "Emergency shutoff",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 8,
      "sequenceNumber": 3,
      "eventCode": "400450",
      "tier1Number": "400",
      "tier1Name": "System operating",
      "tier2Number": "450",
      "tier2Name": "Product leak/release",
      "isDefiningEvent": true
    },
    {
      "eventNumber": 3,
      "sequenceNumber": 2,
      "eventCode": "400330",
      "tier1Number": "400",
      "tier1Name": "System operating",
      "tier2Number": "330",
      "tier2Name": "System/equipment malf/failure",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 10,
      "sequenceNumber": 1,
      "eventCode": "600050",
      "tier1Number": "600",
      "tier1Name": "Emergency response",
      "tier2Number": "050",
      "tier2Name": "Inspection event",
      "isDefiningEvent": false
    }
  ],
  "findings": [
    {
      "findingNumber": 41,
      "sequenceNumber": 16,
      "findingCode": "04021069",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Management",
      "findingTier3Name": "Policy/procedure",
      "findingTier4Name": null,
      "findingModifierName": "Pipeline operator",
      "findingReportText": "Organizational  - Management - Policy/procedure - Pipeline operator",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 40,
      "sequenceNumber": 15,
      "findingCode": "04033069",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Support/oversight/monitoring",
      "findingTier3Name": "Documentation/record keeping",
      "findingTier4Name": null,
      "findingModifierName": "Pipeline operator",
      "findingReportText": "Organizational  - Support/oversight/monitoring - Documentation/record keeping - Pipeline operator",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 27,
      "sequenceNumber": 3,
      "findingCode": "04034070",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Support/oversight/monitoring",
      "findingTier3Name": "Enforcement",
      "findingTier4Name": null,
      "findingModifierName": "Federal agency",
      "findingReportText": "Organizational  - Support/oversight/monitoring - Enforcement - Federal agency",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 20,
      "sequenceNumber": 4,
      "findingCode": "04033099",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Support/oversight/monitoring",
      "findingTier3Name": "Documentation/record keeping",
      "findingTier4Name": null,
      "findingModifierName": "Not specified",
      "findingReportText": "Organizational  - Support/oversight/monitoring - Documentation/record keeping - Not specified",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 29,
      "sequenceNumber": 11,
      "findingCode": "04034071",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Support/oversight/monitoring",
      "findingTier3Name": "Enforcement",
      "findingTier4Name": null,
      "findingModifierName": "State/Local agency",
      "findingReportText": "Organizational  - Support/oversight/monitoring - Enforcement - State/Local agency",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 30,
      "sequenceNumber": 12,
      "findingCode": "04033071",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Support/oversight/monitoring",
      "findingTier3Name": "Documentation/record keeping",
      "findingTier4Name": null,
      "findingModifierName": "State/Local agency",
      "findingReportText": "Organizational  - Support/oversight/monitoring - Documentation/record keeping - State/Local agency",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 39,
      "sequenceNumber": 14,
      "findingCode": "04011068",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Development",
      "findingTier3Name": "Design",
      "findingTier4Name": null,
      "findingModifierName": "Inspection organization",
      "findingReportText": "Organizational  - Development - Design - Inspection organization",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 11,
      "sequenceNumber": 6,
      "findingCode": "01024401",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipline systems/equipment",
      "findingTier3Name": "Regulator",
      "findingTier4Name": null,
      "findingModifierName": "Failure",
      "findingReportText": "Pipeline - Pipline systems/equipment - Regulator - Failure",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 14,
      "sequenceNumber": 7,
      "findingCode": "01024302",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipline systems/equipment",
      "findingTier3Name": "Venting",
      "findingTier4Name": null,
      "findingModifierName": "Malfunction",
      "findingReportText": "Pipeline - Pipline systems/equipment - Venting - Malfunction",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 24,
      "sequenceNumber": 8,
      "findingCode": "01035007",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipeline structure",
      "findingTier3Name": "Pipe",
      "findingTier4Name": null,
      "findingModifierName": "Design",
      "findingReportText": "Pipeline - Pipeline structure - Pipe - Design",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 25,
      "sequenceNumber": 9,
      "findingCode": "03011087",
      "findingTier1Name": "Environment/Infrastructure",
      "findingTier2Name": "Operating environment/control system",
      "findingTier3Name": "Sensor/detector coverage/availability",
      "findingTier4Name": null,
      "findingModifierName": "Awareness of condition",
      "findingReportText": "Environment/Infrastructure - Operating environment/control system - Sensor/detector coverage/availability - Awareness of condition",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 9,
      "sequenceNumber": 1,
      "findingCode": "01010116",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipeline handling/service",
      "findingTier3Name": "Operating information",
      "findingTier4Name": null,
      "findingModifierName": "Not inspected",
      "findingReportText": "Pipeline - Pipeline handling/service - Operating information - Not inspected",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 22,
      "sequenceNumber": 2,
      "findingCode": "02041541",
      "findingTier1Name": "Personnel",
      "findingTier2Name": "Action/decision",
      "findingTier3Name": "Information processing/decision making",
      "findingTier4Name": null,
      "findingModifierName": "Pipeline maintenance personnel",
      "findingReportText": "Personnel - Action/decision - Information processing/decision making - Pipeline maintenance personnel",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 23,
      "sequenceNumber": 5,
      "findingCode": "02041547",
      "findingTier1Name": "Personnel",
      "findingTier2Name": "Action/decision",
      "findingTier3Name": "Information processing/decision making",
      "findingTier4Name": null,
      "findingModifierName": "Emergency services personnel",
      "findingReportText": "Personnel - Action/decision - Information processing/decision making - Emergency services personnel",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 28,
      "sequenceNumber": 10,
      "findingCode": "01024407",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipline systems/equipment",
      "findingTier3Name": "Regulator",
      "findingTier4Name": null,
      "findingModifierName": "Design",
      "findingReportText": "Pipeline - Pipline systems/equipment - Regulator - Design",
      "findingText": null,
      "inProbableCause": false
    },
    {
      "findingNumber": 31,
      "sequenceNumber": 13,
      "findingCode": "01024402",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipline systems/equipment",
      "findingTier3Name": "Regulator",
      "findingTier4Name": null,
      "findingModifierName": "Malfunction",
      "findingReportText": "Pipeline - Pipline systems/equipment - Regulator - Malfunction",
      "findingText": null,
      "inProbableCause": false
    }
  ],
  "caveat": "Official NTSB investigation data. NTSB findings determine probable cause and make safety recommendations; they do not adjudicate civil liability or regulatory violations.",
  "investigationPageAvailable": true,
  "investigationPageUrl": "https://www.ntsb.gov/investigations/Pages/DCA16FP003.aspx",
  "docketUrl": "https://data.ntsb.gov/Docket/?NTSBNumber=DCA16FP003",
  "reportArtifacts": [
    {
      "id": "ntsb-report-par1901",
      "title": "PAR-19-01",
      "url": "https://www.ntsb.gov/investigations/AccidentReports/Reports/PAR1901.pdf",
      "pageCount": 64,
      "pdfArtifactPath": "data/sources/ntsb-reports/artifacts/reports/ntsb-report-par1901.pdf",
      "pdfArtifactSha256": "ae49cba564b8edcacb6c1fdd0e1395da15e1048fdc96f318071b49e9d3724e29",
      "extractedTextPath": "data/sources/ntsb-reports/artifacts/reports/ntsb-report-par1901.txt",
      "extractedTextSha256": "a52e29dfb03ec99fd7179bc90050dcac426c033940c470241d44cb6763c585c9",
      "extractionVersion": 2
    }
  ],
  "jurisdiction": "US",
  "operatorName": "Washington Gas Light Company",
  "region": "MD"
}
```