# Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System

**Citation:** DCA17FP003  
**Type / status:** incident / current  
**Agency:** National Transportation Safety Board  
**Effective:** 2016-11-16  
**Published:** 2021-05-18

Accident. in Canton, IL, USA. on 2016-11-16. Ameren. Leak/explosion/fire

## Document text

NTSB investigation DCA17FP003.

Event Type: Accident

Event Date: 2016-11-16

Event City: Canton

Event State Or Region: IL

Event Country: USA

Pipeline Operator: Ameren

Accident Type: Leak/explosion/fire

Completion Status: Completed

Report Number: PAB1802

Report Date: 2018-12-03

Probable cause: The National Transportation Safety Board determines that the probable cause of the natural gas release and subsequent explosion was third party damage from Sure Shot’s directional drilling to install underground fiber optic conduit. Contributing to the pipeline damage was Sure Shot’s decision not to excavate at the utility crossing to visually inspect the work, while in progress, until clear of the underground utilities, as required by Illinois law. Contributing to the severity of the accident was the failure of Sure Shot and Ameren to evacuate the area.

Tier1Name: Emergency response

Tier2Name: Evacuation

Tier1Name: Emergency response

Tier2Name: Emergency shutoff

Tier1Name: Emergency response

Tier2Name: Explosion

Tier1Name: System shutdown

Tier2Name: Fire (post-release)

Tier1Name: System operating

Tier2Name: Product leak/release

Tier1Name: System operating

Tier2Name: External/third-party damage

Finding Tier1Name: Organizational

Finding Tier2Name: Support/oversight/monitoring

Finding Tier3Name: Oversight

Finding Modifier Name: Other institution/organization

Finding Report Text: Organizational - Support/oversight/monitoring - Oversight - Other institution/organization

Finding Tier1Name: Environment/Infrastructure

Finding Tier2Name: Task environment

Finding Tier3Name: Physical workspace

Finding Modifier Name: Decision related to condition

Finding Report Text: Environment/Infrastructure - Task environment - Physical workspace - Decision related to condition

Finding Tier1Name: Pipeline

Finding Tier2Name: Pipeline handling/service

Finding Tier3Name: Maintenance/inspection

Finding Modifier Name: Inadequate inspection

Finding Report Text: Pipeline - Pipeline handling/service - Maintenance/inspection - Inadequate inspection

Finding Tier1Name: Personnel

Finding Tier2Name: Action/decision

Finding Tier3Name: Information processing/decision making

Finding Modifier Name: Equipment/vehicle operator

Finding Report Text: Personnel - Action/decision - Information processing/decision making - Equipment/vehicle operator

Finding Tier1Name: Organizational

Finding Tier2Name: Management

Finding Tier3Name: Policy/procedure

Finding Modifier Name: Other institution/organization

Finding Report Text: Organizational - Management - Policy/procedure - Other institution/organization

Official NTSB investigation data. NTSB findings determine probable cause and make safety recommendations; they do not adjudicate civil liability or regulatory violations.

What Happened
On November 16, 2016, about 5:44 p.m. central standard time, a natural gas-fueled explosion occurred at a two-level commercial building located at 45 East Side Square in Canton, Illinois. One Ameren employee was killed and 11 people were injured, including two Ameren employees.

What We Found
We determined that the probable cause of the natural gas release and subsequent explosion was third party damage from Sure Shot’s directional drilling to install underground fiber optic conduit. Contributing to the pipeline damage was Sure Shot’s decision not to excavate at the utility crossing to visually inspect the work, while in progress, until clear of the underground utilities, as required by Illinois law. Contributing to the severity of the accident was the failure of Sure Shot and Ameren to evacuate the area.

PAB-18-02
<<<PAGE 1>>>

National Transportation Safety Board
Pipeline Accident Brief
Third-party Damage by Sure Shot Communications
to Ameren Natural Gas Distribution System
Canton, Illinois
The Accident
On November 16, 2016, about 5:44 p.m. central standard time, a natural gas-fueled
explosion occurred at a two-level commercial building located at 45 East Side Square in Canton,
Illinois. One Ameren employee was killed and 11 people were injured, including two Ameren
employees.
Prior to the accident, Sure Shot Communications LLC (Sure Shot), a contractor for
Mid Century Communications (Mid Century), a telephone and fiber optics cooperative, was
performing directional drilling adjacent to the building to install conduit for fiber optic cable.1
About 9:00 a.m., the Sure Shot crew began performing multiple drills at various locations on the
block. At 3:58 p.m., the contractor reported to the Joint Utility Locating Information for Excavators
(JULIE), the one-call message handling and delivery service for identifying underground utilities,
that a marked gas line had been damaged. The damage occurred while crews were pulling the drill
rod back to the drilling rig after a directional drilling operation under the sidewalk along North
First Street.
At 4:06 p.m., Ameren Illinois (Ameren), the owner and operator of the gas line, received a
damage report from Sure Shot and dispatched field technicians to evaluate the situation. About
7 minutes later, the first Ameren responder arrived at the scene; three other Ameren technicians
arrived shortly thereafter. The lead Ameren responder contacted his supervisor to confirm the
pipeline had been struck and to request excavation equipment to uncover the service line. A
backhoe excavator arrived at 4:41p.m. and Ameren technicians began to isolate the leak.
At 4:48 p.m., nearby customers called the Ameren Customer Contact Center to report
natural gas odors both indoors and outdoors. According to Ameren, these customers were given
safety instructions and told to leave their buildings if an odor was detected.
2 By 5:37 p.m., Ameren
technicians shut off the natural gas flow to the service line by squeezing off the pipeline. At 5:44
p.m., the Opera House Annex behind the Opera House Professional Center exploded, killing one
and injuring 11 who were impacted by debris from the blast. (See figures 1 and 2.)
1 Directional drilling is a trenchless pipe or conduit installation technique that involves drilling into the soil to
create a horizontal bore or pathway for the pipe or conduit.
2 Ameren provided verbal instructions as written in their Customer Contact Center Emergency Plan Procedures,
subsection 4.G and 4.H.
NTSB/PAB-18/02

<<<PAGE 2>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
Figure 1. A Google Earth image of the back of the Opera House Professional Center and the
two-level Opera House Annex prior to the accident.
Figure 2. Photograph of the accident site and debris from the Opera House Annex. (Courtesy of
Canton Police Department.)
2

<<<PAGE 3>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
The Pipeline System
The damaged natural gas service line was a 1-inch polyethylene line connected to a 2-inch
gas main located about 6 feet east of the west curb line (inside the roadway) of North First Street.
The service line was installed on December 6, 2012, and was 32 feet long.3 The natural gas service
was operating at 30 pounds per square inch gauge (psig) with a maximum allowable operating
pressure of 60 psig.
Sure Shot Communications LLC
Sure Shot had previously performed fiber optic conduit installation for Mid Century;
however, there was no written contract between the companies for the work performed on the day
of the accident or past work. Additionally, Sure Shot did not have either a written project plan or
an emergency response plans for the work. The company also did not have qualification and
training records for the employees performing directional drilling. The day of the accident was the
first field work day for the employee-in-charge (crew leader) of the directional drilling crew. Sure
Shot positioned directional drilling equipment at the corner of East Chestnut and North First Street.
The crew drilled southward, under the sidewalk, to a utility handhole located about 1 foot past the
service line to the extension of the Opera House Professional Center.4 Figure 3 shows the location
of the drilling rig in relation to the Opera House Professional Center and depicts the horizontal
drill path and the location where the gas service line was struck.
3 Prior to the installation of this gas main line and service in 2012, the Opera House Annex was serviced by a
branch line off the service line to the Opera House Professional Center at 45 East Side Square.
4 A handhole is an opening created on the face of an underground concrete junction box used for the routing and
termination of below grade cables/wires.
3

<<<PAGE 4>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
Figure 3. An illustration of the drill path and the location where the gas service line was struck.
The location of the natural gas service line damage was underneath the concrete sidewalk
adjacent to the destroyed structure. Sure Shot did not excavate the utility crossing location before
starting the drilling work, as required by Illinois statute.5 According to Illinois law, during
directional drilling, each location where the drill path crosses underground, utilities must be
excavated using methods such as hand or vacuum excavation. The excavator must visually inspect
the work, while in progress, until clear of the underground utilities.
Section 4(a) and (b) of 220 Illinois Compiled Statutes (ILCS) 50, Illinois Underground
Utility Facilities Damage Prevention Act, states: Every person who engages in nonemergency
excavation or demolition shall:
(a) take reasonable action to inform himself of the location of any underground
utility facilities in and near the area for which such operation is to be conducted;
(b) plan the excavation or demolition to avoid or minimize interference with
underground utility facilities within the tolerance zone by utilizing such precautions
5 The Illinois Commerce Commission’s Natural Gas Pipeline Safety section is charged with inspection and
enforcement activities applicable to intrastate natural gas transmission, distribution and gathering pipeline facilities to
assure compliance with all federal and state safety rules and regulations pertaining to the design, construction,
operation, and maintenance of those facilities (see https://www.icc.illinois.gov/pipelinesafety/ accessed October 29,
2018).
4

<<<PAGE 5>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
that include, but are not limited to, hand excavation, vacuum excavation methods,
and visually inspecting the excavation while in progress until clear of the existing
marked facility.
The crew leader told National Transportation Safety Board (NTSB) investigators that the
owner of Sure Shot instructed him not to excavate under the concrete slab to avoid replacing the
relatively new concrete sidewalk.6
The crew leader was concerned about the failure to expose the gas line; however, he
thought it would be adequate since the crew was drilling 30 inches underground or below the depth
of the natural gas line that he believed was buried 18 inches.
7 (See figure 5.)
Figure 5. Image showing the damaged yellow service line intersected by the orange fiber optic
cable conduit.
He told investigators that he believed the drill crossed the natural gas line without incident
and that the strike occurred when the drill machine operator was pulling the drill rod back to the
drill rig.8 He was certain that he would have smelled natural gas in the handhole if the drill had
6 Interview summary of Sure Shot owner located in NTSB Docket DCA17FP003.
7 The bore diameter was 6 inches.
8 The pullback of the drill rod was described as a dead pull, meaning the drill is neither rotating nor spinning on
the way back to the drill rig.
5

<<<PAGE 6>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
struck the gas line when pushing the drill rod to the vault since it was only a foot away and he had
his face in the vault.
After striking the gas line, the crew leader described hearing, smelling, and seeing the
leaking gas moving rocks and soil in the handhole. He called JULIE to report the accident and also
contacted Ameren after he spoke with a representative from Mid Century. He did not contact 911.
He told NTSB investigators that he believed JULIE would make the 911 notification.9
Ameren provided the crew leader with safety instructions to block off the street and to
evacuate nearby buildings. The Sure Shot crew shut off their equipment and blocked off the street:
the crew leader spoke to people leaving the nearby buildings. Some of these individuals told him
they smelled gas and he instructed them to leave the building. Additionally, he attempted to
evacuate the Opera House Annex by knocking on the door, but no one answered. He awaited the
arrival of Ameren response personnel.
Mid Century Communications
On the day of the accident, a Mid Century representative was at the excavation site all day;
however, he told NTSB investigators he was not responsible for overseeing work by Sure Shot
employees. His role was to answer technical questions from either Sure Shot or potential
customers. He stated that he spent most of his day sitting in his vehicle.
10
Local Emergency Response Notifications
The Sure Shot employees, the Ameren field technicians, and Ameren dispatch center
personnel called did not call 911 to report the gas leak prior to the explosion. In response to a one
call enforcement information request from the Illinois Commerce Commission, the owner of Sure
Shot stated that the company did not contact 911 since JULIE usually dispatches the fire
department when gas leaks are reported. However, he affirmed on the same form that he is aware
that Section 7 of Illinois Underground Utility Facilities Damage Prevention Act requires that “[i]n
the event of any damage to any underground utility facility that results in the escape of any
flammable, toxic, or corrosive gas or liquid, the person responsible for the excavation or
demolition shall call 911 and notify authorities of the damage.” He also affirmed that the same
section of the Act requires the person responsible to immediately notify both the affected utility
and JULIE.
Ameren employees responding to the damage report were on scene for about 1.5 hours
before the explosion. The employees recorded gas readings were taken from the outside perimeter
9 The Horizontal Directional Drilling (HDD) industry at large must follow the appropriate state one call digging
and Occupational Safety and Health Administration laws, however; in the state of Illinois, there are no training or
certification requirements for HDD contractors who work on water, telecommunications, and other utilities with HDD
equipment. Federal rules do exist for contractors performing work on gas utilities whereby HDD operators must
comply and meet the requirements under the Operator Qualification rules in the PHMSA Pipeline Safety Regulations.
10 Interview summary of Mid Century employee located in NTSB Docket DCA17FP003.
6

<<<PAGE 7>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
of the Opera House Professional Center building; however, they did not take any readings from
inside the building despite Ameren having received both indoor and outdoor odor complaints.
Service Line Damage
An Ameren utility crew excavated and visually examined the damaged service line at the
accident scene. The top of the 1-inch polyethylene line showed clear damage as a result of being
struck by drilling equipment. The damage to the service line from the directional drilling is shown
in figure 6.
Figure 6. Damaged service line to the exploded building from two different angles.
Probable Cause
The National Transportation Safety Board determines that the probable cause of the natural
gas release and subsequent explosion was third party damage from Sure Shot’s directional drilling
to install underground fiber optic conduit. Contributing to the pipeline damage was Sure Shot’s
decision not to excavate at the utility crossing to visually inspect the work, while in progress, until
clear of the underground utilities, as required by Illinois law. Contributing to the severity of the
accident was the failure of Sure Shot and Ameren to evacuate the area.
For more details about this accident, visit www.ntsb.gov/investigations/dms.html and search for
NTSB accident ID DCA17FP003.
Issued: December 3, 2018
7

<<<PAGE 8>>>

Third-party Damage by Sure Shot Communications to Ameren Natural Gas Distribution System
The NTSB has authority to investigate and establish the facts, circumstances, and cause or probable
cause of a pipeline accident in which there is a fatality, substantial property damage, or significant
injury to the environment. (49 US Code § 1131 - General authority)
The NTSB does not assign fault or blame for an accident or incident; rather, as specified by NTSB
regulation, “accident/incident investigations are fact-finding proceedings with no formal issues and no
adverse parties . . . and are not conducted for the purpose of determining the rights or liabilities of any
person.” Title 49 Code of Federal Regulations, Section 831.4. Assignment of fault or legal liability is
not relevant to the NTSB’s statutory mission to improve transportation safety by investigating
accidents and incidents and issuing safety recommendations. In addition, statutory language prohibits
the admission into evidence or use of any part of an NTSB report related to an accident in a civil action
for damages resulting from a matter mentioned in the report. 49 USC 1154(b).
8

## Provenance

- Official: Yes
- Source: <https://www.ntsb.gov/investigations/Pages/DCA17FP003.aspx>
- Source ID: `ntsb-pipeline`
- SHA-256: `2ef8393715491f763d8af5ef2b939b14aefd61b7853729af81db991535bd2be8`
- Retrieved: 2026-08-20T04:57:25.499Z
- Exported: 2026-08-24T03:31:03.404Z
- Document slug: `ntsb-case-dca17fp003`

### Source metadata

```json
{
  "recordKind": "ntsb_pipeline_investigation",
  "mkey": 94389,
  "ntsbNumber": "DCA17FP003",
  "completionStatus": "Completed",
  "caseClosed": true,
  "hasSafetyRecommendation": false,
  "eventType": "Accident",
  "accidentType": "Leak/explosion/fire",
  "operator": "Ameren",
  "pipelineType": null,
  "location": {
    "city": "Canton",
    "state": "IL",
    "country": "USA",
    "latitude": null,
    "longitude": null
  },
  "reportNumber": "PAB1802",
  "probableCause": "The National Transportation Safety Board determines that the probable cause of the natural gas release and subsequent explosion was third party damage from Sure Shot’s directional drilling to install underground fiber optic conduit. Contributing to the pipeline damage was Sure Shot’s decision not to excavate at the utility crossing to visually inspect the work, while in progress, until clear of the underground utilities, as required by Illinois law. Contributing to the severity of the accident was the failure of Sure Shot and Ameren to evacuate the area.",
  "events": [
    {
      "eventNumber": 2,
      "sequenceNumber": 3,
      "eventCode": "600460",
      "tier1Number": "600",
      "tier1Name": "Emergency response",
      "tier2Number": "460",
      "tier2Name": "Evacuation",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 3,
      "sequenceNumber": 4,
      "eventCode": "600060",
      "tier1Number": "600",
      "tier1Name": "Emergency response",
      "tier2Number": "060",
      "tier2Name": "Emergency shutoff",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 5,
      "sequenceNumber": 5,
      "eventCode": "600170",
      "tier1Number": "600",
      "tier1Name": "Emergency response",
      "tier2Number": "170",
      "tier2Name": "Explosion",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 6,
      "sequenceNumber": 6,
      "eventCode": "550160",
      "tier1Number": "550",
      "tier1Name": "System shutdown",
      "tier2Number": "160",
      "tier2Name": "Fire (post-release)",
      "isDefiningEvent": false
    },
    {
      "eventNumber": 4,
      "sequenceNumber": 2,
      "eventCode": "400450",
      "tier1Number": "400",
      "tier1Name": "System operating",
      "tier2Number": "450",
      "tier2Name": "Product leak/release",
      "isDefiningEvent": true
    },
    {
      "eventNumber": 1,
      "sequenceNumber": 1,
      "eventCode": "400240",
      "tier1Number": "400",
      "tier1Name": "System operating",
      "tier2Number": "240",
      "tier2Name": "External/third-party damage",
      "isDefiningEvent": false
    }
  ],
  "findings": [
    {
      "findingNumber": 3,
      "sequenceNumber": 3,
      "findingCode": "04032073",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Support/oversight/monitoring",
      "findingTier3Name": "Oversight",
      "findingTier4Name": null,
      "findingModifierName": "Other institution/organization",
      "findingReportText": "Organizational  - Support/oversight/monitoring - Oversight - Other institution/organization",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 4,
      "sequenceNumber": 4,
      "findingCode": "03041084",
      "findingTier1Name": "Environment/Infrastructure",
      "findingTier2Name": "Task environment",
      "findingTier3Name": "Physical workspace",
      "findingTier4Name": null,
      "findingModifierName": "Decision related to condition",
      "findingReportText": "Environment/Infrastructure - Task environment - Physical workspace - Decision related to condition",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 5,
      "sequenceNumber": 5,
      "findingCode": "01010515",
      "findingTier1Name": "Pipeline",
      "findingTier2Name": "Pipeline handling/service",
      "findingTier3Name": "Maintenance/inspection",
      "findingTier4Name": null,
      "findingModifierName": "Inadequate inspection",
      "findingReportText": "Pipeline - Pipeline handling/service - Maintenance/inspection - Inadequate inspection",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 2,
      "sequenceNumber": 2,
      "findingCode": "02041536",
      "findingTier1Name": "Personnel",
      "findingTier2Name": "Action/decision",
      "findingTier3Name": "Information processing/decision making",
      "findingTier4Name": null,
      "findingModifierName": "Equipment/vehicle operator",
      "findingReportText": "Personnel - Action/decision - Information processing/decision making - Equipment/vehicle operator",
      "findingText": null,
      "inProbableCause": true
    },
    {
      "findingNumber": 1,
      "sequenceNumber": 1,
      "findingCode": "04021073",
      "findingTier1Name": "Organizational ",
      "findingTier2Name": "Management",
      "findingTier3Name": "Policy/procedure",
      "findingTier4Name": null,
      "findingModifierName": "Other institution/organization",
      "findingReportText": "Organizational  - Management - Policy/procedure - Other institution/organization",
      "findingText": null,
      "inProbableCause": true
    }
  ],
  "caveat": "Official NTSB investigation data. NTSB findings determine probable cause and make safety recommendations; they do not adjudicate civil liability or regulatory violations.",
  "investigationPageAvailable": true,
  "investigationPageUrl": "https://www.ntsb.gov/investigations/Pages/DCA17FP003.aspx",
  "docketUrl": "https://data.ntsb.gov/Docket/?NTSBNumber=DCA17FP003",
  "reportArtifacts": [
    {
      "id": "ntsb-report-pab1802",
      "title": "PAB-18-02",
      "url": "https://www.ntsb.gov/investigations/AccidentReports/Reports/PAB1802.pdf",
      "pageCount": 8,
      "pdfArtifactPath": "data/sources/ntsb-reports/artifacts/reports/ntsb-report-pab1802.pdf",
      "pdfArtifactSha256": "cd9a38284bdb108485040fb57cd4a10174c870bfefa004b1a2c3f53870701356",
      "extractedTextPath": "data/sources/ntsb-reports/artifacts/reports/ntsb-report-pab1802.txt",
      "extractedTextSha256": "693c13fe10ae1e776fcc92b9a6d5f294b3f2a6a2c4a7faeac4509aa36eafdb95",
      "extractionVersion": 2
    }
  ],
  "jurisdiction": "US",
  "operatorName": "Ameren",
  "region": "IL"
}
```