# NTSB Safety Recommendation P-76-069

**Citation:** P-76-069  
**Type / status:** guidance / guidance  
**Agency:** National Transportation Safety Board  
**Effective:** 1976-10-02  
**Published:** 1976-10-02

ASSURE THAT WHEN A CAST IRON CAULKED BELL AND SPIGOT JOINT IS EXPOSED, A LEAK CLAMP IS INSTALLED AS REQUIRED BY 49 CFR 192.753(B). (URGENT)

## Document text

NTSB safety recommendation P-76-069.

ASSURE THAT WHEN A CAST IRON CAULKED BELL AND SPIGOT JOINT IS EXPOSED, A LEAK CLAMP IS INSTALLED AS REQUIRED BY 49 CFR 192.753(B). (URGENT)

Priority: CLASS I

Overall Status: Closed - Acceptable Action

Issued Date: 1976-10-02

Adopted Date: 1976-09-08

Overall Date Closed: 1979-02-02

Synopsis: ON MARCH 27, 1976, A TWO-STORY BUILDING THAT HOUSED PHENIX CUTTING AND SEWING, INC., IN PHENIX CITY, ALABAMA, EXPLODED AND BURNED. THE EXPLOSION AND FIRE KILLED THE SIX PERSONS IN THE BUILDING.

Ntsbnumber: DCA76FP019

Report Number: None

Addressee Name: State of Alabama, City of Phenix City, Utilities Board

Addressee Status: Closed--No Longer Applicable

Addressee Date Closed: 1979-02-02

Addressee Organization Type: L-Local Government

Communication Date: 1976-09-29

Communication Type: Official Correspondence

Communication Contents: LTR. FROM UTILITIES BOARD OF THE CITY OF PHENIX CITY: AS OF THIS DATE THE GAS CREWS WILL INSURE THAT A CAST IRON CAULKED BELL AND SPIGOT JOINT WHEN EXPOSED, HAS A LEAK CLAMP INSTALLED AS REQUIRED BY 49 CFR 192.753(B).

## Provenance

- Official: Yes
- Source: <https://data.ntsb.gov/carol-main-public/sr-details/P-76-069>
- Source ID: `ntsb-pipeline`
- SHA-256: `161159710b068c97df1b6d35fdfadc4dae78fbbb7f6e77868fbf087a2851adbe`
- Retrieved: 2026-08-20T04:57:24.741Z
- Exported: 2026-08-23T05:24:15.141Z
- Document slug: `ntsb-recommendation-p-76-069`

### Source metadata

```json
{
  "recordKind": "ntsb_safety_recommendation",
  "safetyRecommendationNumber": "P-76-069",
  "recommendationMode": "Pipeline",
  "topicMode": "Pipeline",
  "ntsbNumber": "DCA76FP019",
  "priority": "CLASS I",
  "overallStatus": "Closed - Acceptable Action",
  "overallStatusAcronym": "CAA",
  "overallDateClosed": "1979-02-02",
  "lastModifiedDate": "2017-09-06",
  "reportNumber": "None",
  "reportUrl": null,
  "transmittalLetterUrl": "http://www.ntsb.gov/safety/safety-recs/recletters/P76_67_72.pdf",
  "addressees": [
    {
      "addresseeName": "State of Alabama, City of Phenix City, Utilities Board",
      "addresseeStatusAcronym": "CNLA",
      "addresseeStatus": "Closed--No Longer Applicable",
      "addresseeDateClosed": "1979-02-02",
      "addresseeDetails": [
        {
          "addresseeAcronym": null,
          "addresseeOrganizationType": "L-Local Government",
          "isFromNtsb": false,
          "communicationDate": "1976-09-29",
          "communicationType": "Official Correspondence",
          "communicationContents": "LTR. FROM UTILITIES BOARD OF THE CITY OF PHENIX CITY: AS OF THIS DATE THE GAS CREWS WILL INSURE THAT A CAST IRON CAULKED BELL AND SPIGOT JOINT WHEN EXPOSED, HAS A LEAK CLAMP INSTALLED AS REQUIRED BY 49 CFR 192.753(B)."
        }
      ]
    }
  ],
  "jurisdiction": "US"
}
```