# NTSB Safety Recommendation P-93-008

**Citation:** P-93-008  
**Type / status:** guidance / guidance  
**Agency:** National Transportation Safety Board  
**Effective:** 1993-08-23  
**Published:** 1993-08-23

THE NTSB RECOMMENDS THAT THE CENTRAL HUDSON GAS AND ELECTRIC CORPORATION: IMPLEMENT A PROGRAM, BASED ON FACTORS SUCH AS AGE, PIPE DIAMETER, OPERATING PRESSURE, SOIL CORROSIVENESS, EXISTING GRAPHITIC DAMAGE LEAK HISTORY, BURIAL DEPTH, AND EXTERNAL LOADING, TO IDENTIFY AND REPLACE IN A PLANNED, TIMELY MANNER CAST IRON PIPING SYSTEMS THAT MAY THREATEN PUBLIC SAFETY.

## Document text

NTSB safety recommendation P-93-008.

THE NTSB RECOMMENDS THAT THE CENTRAL HUDSON GAS AND ELECTRIC CORPORATION: IMPLEMENT A PROGRAM, BASED ON FACTORS SUCH AS AGE, PIPE DIAMETER, OPERATING PRESSURE, SOIL CORROSIVENESS, EXISTING GRAPHITIC DAMAGE LEAK HISTORY, BURIAL DEPTH, AND EXTERNAL LOADING, TO IDENTIFY AND REPLACE IN A PLANNED, TIMELY MANNER CAST IRON PIPING SYSTEMS THAT MAY THREATEN PUBLIC SAFETY.

Priority: CLASS II

Overall Status: Closed - Acceptable Action

Issued Date: 1993-08-23

Adopted Date: 1993-08-09

Overall Date Closed: 1996-10-01

Synopsis: A NATURAL GAS EXPLOSION DESTROYED A HOUSE AT 26 LIBERTY STREET IN CATSKILL, NEW YORK, ON NOVEMBER 6, 1992, ABOUT 7:45 P.M. EASTERN STANDARD TIME. THE TWO-STORY WOOD-FRAME HOUSE HAD NOT HAD ACTIVE GAS SERVICE 1969. THE EXPLOSION KILLED A WOMAN IN THE HOUSE, SERIOUSLY INJURED HER DAUGHTER, AND SLIGHTLY INJURED TWO CHILDREN IN A NEIGHBORING HOUSE.

Probable Cause: None

Ntsbnumber: DCA93FP002

Report Number: None

Addressee Name: Central Hudson Gas and Electric Corporation

Addressee Status: Closed - Acceptable Action

Addressee Date Closed: 1996-10-01

Addressee Acronym: CHG&E

Addressee Organization Type: P-Private Industry

Communication Date: 1993-12-13

Communication Type: Official Correspondence

Communication Contents: RECOMMENDATION P-93-8 ASKED CENTRAL HUDSON TO IMPLEMENT A PROGRAM, BASED ON FACTORS SUCH AS AGE, PIPE DIAMETER, OPERATING PRESSURE, SOIL CORROSIVENESS, EXISTING GRAPHITIC DAMAGE, LEADK HISTORY, BURIAL DEPTH, AND EXTERNAL LOADING, TO IDENTIFY AND REPLACE IN A PLANNED, TIMELY MANNER CAST-IRON PIPING SYSTEMS THAT MAY THREATEN PUBLIC SAFETY. THE BOARD NOTES THAT BY JUNE Y, 1994, CENTRAL HUDSON WILL HAVE EXPANDED ITS PROGRAM OF EVALUATING CAST-IRON PIPELINE FACILITIES TO MONITOR SYSTEM INTEGRITY AND TO IDENTIFY POSSIBLE PROBLEMS. PENDING THE EXPANSION OF THE PROGRAM, RECOMMENDATION P-93-8 WILL BE CLASSIFIED "OPEN--ACCEPTABLE RESPONSE."

Addressee Acronym: CHG&E

Addressee Organization Type: P-Private Industry

Communication Date: 1996-10-01

Communication Type: Official Correspondence

Communication Contents: THE BOARD IS PLEASED TO LEARN THAT CENTRAL HUDSON HAS DEVELOPED & IMPLEMENTED AN EXPANDED PROGRAM TO MONITOR, TEST, & EVALUATE CAST IRON & UNPROTECTED STEEL PIPELINE FACILITIES BASED ON THE FACTORS DESCRIBED IN THE RECOMMENDATION. THE BOARD ALSO NOTES THAT CENTRAL HUDSON HAS INVESTED IN A PROGRAM TO REPLACE CAST IRON & BARE STEEL PIPELINES SINCE RECEIVING P-93-8. BASED ON THIS INFO, P-93-8 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

Addressee Acronym: CHG&E

Addressee Organization Type: P-Private Industry

Communication Date: 1993-10-22

Communication Type: Official Correspondence

Communication Contents: CENTRAL HUDSON IS DEVELOPING AN EXPANDED PROGRAM OF MONITORING, TESTING, AND EVALUATING CAST IRON PIPELINE FACILITIES TO MONITOR SYSTEM INTEGRITY AND TO IDENTIFY POSSIBLE PROBLEM AREAS. ON OR BEFORE JUNE 1 1994, CENTRAL HUDSON WILL COMPLETE THE DEVELOPMENT OF THIS EXPANDED PROGRAM FOR SUBSEQUENT INPLEMENTATION.

Addressee Acronym: CHG&E

Addressee Organization Type: P-Private Industry

Communication Date: 1996-07-10

Communication Type: Official Correspondence

Communication Contents: IN RESPONSE TO RECOMMENDATION P-93-08, CENTRAL HUDSON HAS DEVELOPED & IMPLEMENTED AN EXPANDED PROGRAM OF MONITORING TESTING & EVALUATING CAST IRON & UNPROTECTED STEEL PIPELINE FACILITIES TO MONITOR SYSTEM INTEGRITY & TO IDENTIFY POSSIBLE PROBLEM AREAS. FACTORS SUCH AS AGE, PIPE DIAMETER, OPERATING PRESSURE, SOIL CORROSIVENESS, EXISTING GRAPHITIC DAMAGE, LEAK HISTORY, BURIAL DEPTH, & EXTERNAL LOADING ARE INCLUDED IN OUR PROGRAM. CENTRAL HUDSON HAS SPENT 3 MILLION DOLLARS TO REPLACE CAST IRON BARE STEEL PIPING FACILITIES THUS FAR.

## Provenance

- Official: Yes
- Source: <https://data.ntsb.gov/carol-main-public/sr-details/P-93-008>
- Source ID: `ntsb-pipeline`
- SHA-256: `133290add8d835dbdf3a0f22aaecf378fa6fd31deb4e44b52838494a642f9d34`
- Retrieved: 2026-08-20T04:57:24.741Z
- Exported: 2026-08-23T02:09:57.951Z
- Document slug: `ntsb-recommendation-p-93-008`

### Source metadata

```json
{
  "recordKind": "ntsb_safety_recommendation",
  "safetyRecommendationNumber": "P-93-008",
  "recommendationMode": "Pipeline",
  "topicMode": "Pipeline",
  "ntsbNumber": "DCA93FP002",
  "priority": "CLASS II",
  "overallStatus": "Closed - Acceptable Action",
  "overallStatusAcronym": "CAA",
  "overallDateClosed": "1996-10-01",
  "lastModifiedDate": "2016-11-15",
  "reportNumber": "None",
  "reportUrl": null,
  "transmittalLetterUrl": "http://www.ntsb.gov/safety/safety-recs/recletters/P93_7_8.pdf",
  "addressees": [
    {
      "addresseeName": "Central Hudson Gas and Electric Corporation",
      "addresseeStatusAcronym": "CAA",
      "addresseeStatus": "Closed - Acceptable Action",
      "addresseeDateClosed": "1996-10-01",
      "addresseeDetails": [
        {
          "addresseeAcronym": "CHG&E",
          "addresseeOrganizationType": "P-Private Industry",
          "isFromNtsb": true,
          "communicationDate": "1993-12-13",
          "communicationType": "Official Correspondence",
          "communicationContents": "RECOMMENDATION P-93-8 ASKED CENTRAL HUDSON TO IMPLEMENT A PROGRAM, BASED ON FACTORS SUCH AS AGE, PIPE DIAMETER, OPERATING PRESSURE, SOIL CORROSIVENESS, EXISTING GRAPHITIC DAMAGE, LEADK HISTORY, BURIAL DEPTH, AND EXTERNAL LOADING, TO IDENTIFY AND REPLACE IN A PLANNED, TIMELY MANNER CAST-IRON PIPING SYSTEMS THAT MAY THREATEN PUBLIC SAFETY.  THE BOARD NOTES THAT BY JUNE Y, 1994, CENTRAL HUDSON WILL HAVE EXPANDED ITS PROGRAM OF EVALUATING CAST-IRON PIPELINE FACILITIES TO MONITOR SYSTEM INTEGRITY AND TO IDENTIFY POSSIBLE PROBLEMS. PENDING THE EXPANSION OF THE PROGRAM, RECOMMENDATION P-93-8 WILL BE CLASSIFIED \"OPEN--ACCEPTABLE RESPONSE.\""
        },
        {
          "addresseeAcronym": "CHG&E",
          "addresseeOrganizationType": "P-Private Industry",
          "isFromNtsb": true,
          "communicationDate": "1996-10-01",
          "communicationType": "Official Correspondence",
          "communicationContents": "THE BOARD IS PLEASED TO LEARN THAT CENTRAL HUDSON HAS DEVELOPED & IMPLEMENTED AN EXPANDED PROGRAM TO MONITOR, TEST, & EVALUATE CAST IRON & UNPROTECTED STEEL PIPELINE FACILITIES BASED ON THE FACTORS DESCRIBED IN THE RECOMMENDATION.  THE BOARD ALSO NOTES THAT CENTRAL HUDSON HAS INVESTED IN A PROGRAM TO REPLACE CAST IRON & BARE STEEL PIPELINES SINCE RECEIVING P-93-8.  BASED ON THIS INFO, P-93-8 HAS BEEN CLASSIFIED \"CLOSED--ACCEPTABLE ACTION.\""
        },
        {
          "addresseeAcronym": "CHG&E",
          "addresseeOrganizationType": "P-Private Industry",
          "isFromNtsb": false,
          "communicationDate": "1993-10-22",
          "communicationType": "Official Correspondence",
          "communicationContents": "CENTRAL HUDSON IS DEVELOPING AN EXPANDED PROGRAM OF MONITORING, TESTING, AND EVALUATING CAST IRON PIPELINE FACILITIES TO MONITOR SYSTEM INTEGRITY AND TO IDENTIFY POSSIBLE PROBLEM AREAS.  ON OR BEFORE JUNE 1 1994, CENTRAL HUDSON WILL COMPLETE THE DEVELOPMENT OF THIS EXPANDED PROGRAM FOR SUBSEQUENT INPLEMENTATION."
        },
        {
          "addresseeAcronym": "CHG&E",
          "addresseeOrganizationType": "P-Private Industry",
          "isFromNtsb": false,
          "communicationDate": "1996-07-10",
          "communicationType": "Official Correspondence",
          "communicationContents": "IN RESPONSE TO RECOMMENDATION P-93-08, CENTRAL HUDSON HAS DEVELOPED & IMPLEMENTED AN EXPANDED PROGRAM OF MONITORING TESTING & EVALUATING CAST IRON & UNPROTECTED STEEL PIPELINE FACILITIES TO MONITOR SYSTEM INTEGRITY & TO IDENTIFY POSSIBLE PROBLEM AREAS.  FACTORS SUCH AS AGE, PIPE DIAMETER, OPERATING  PRESSURE, SOIL CORROSIVENESS, EXISTING GRAPHITIC DAMAGE, LEAK HISTORY, BURIAL DEPTH, & EXTERNAL LOADING ARE INCLUDED IN OUR PROGRAM.  CENTRAL HUDSON HAS SPENT 3 MILLION DOLLARS TO REPLACE CAST IRON BARE STEEL PIPING FACILITIES THUS FAR."
        }
      ]
    }
  ],
  "jurisdiction": "US"
}
```