# PORTLAND NATURAL GAS TRANSMISSION SYSTEM — Notice of Amendment

**Citation:** CPF 120071007M  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2007-08-01

CLOSED notice of amendment citing 192.463(a), 192.465(d), 192.473(a), 192.481(c).

## Document text

Notice of Amendment involving PORTLAND NATURAL GAS TRANSMISSION SYSTEM. PHMSA's enforcement data identifies the cited regulations as 192.463(a),  192.465(d),  192.473(a),  192.481(c). The case was opened on 2007-08-01 and is reported as closed as of 2009-12-14. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120071007M_Notice of Amendment_080107.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120071007M/120071007M_Notice%20of%20Amendment_080107.pdf

120071007m_notice of amendment_080107_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120071007M/120071007m_notice%20of%20amendment_080107_text.pdf

120071007M_operator response to notice_09282007.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120071007M/120071007M_operator%20response%20to%20notice_09282007.pdf

120071007m_notice of amendment_080107_text.pdf

U 5 Department
of Transportation
Pipeline and
Hazardous Materials Safety
Administration
409 3rd Street SW Sorts 300
Washington, DC 20024
NOTICE OF AMENDMENT
CERTIFIED MAIL - RETURN RECEIPT RE UESTED
August l, 2007
Mr Robert Pirt
President
Portland Natural Gas Transmission System, LLC
One Harbour Place, S-375
Portsmouth, NH 03081
CPF 1-2007-1007M
Dear Mr Pirt
Dunng the week of Apnl 23, 2007, a representative of the Pipehne and Hazardous Matenals
Safety Administration (PHMSA) pursuant to Chapter 601 of 49 Umted States Code inspected
Portland Natural Gas Transmission System's (PNGTS) corrosion procedures in Wtndham,
Maine
On the basis of the inspection, PHMSA has identified the apparent inadequacies found within
PNGTS's plans or procedures, as descnbed below



I tt192. 463 External corrosion control: Cathodic protection
(a) Each cathodic protection system required by this subpart must provide a level
of cathodic protection that comphes with one or more of the apphcable criteria
contained m Appendix D of this part. If none of these criteria is apphcable, the
cathodic protection system must provide a level of cathodic protection at least equal
to that provided by compliance with one or more of these criteria.
PNGTS's procedures 453 and EDMS 004258833 do uot state explicitly that the measured pipe to
soil voltage measurements must be a negative voltage of at least 0 85 volts to indicate an
adequate level of cathodic protection The procedures do uot state that the voltage measurement
must consider the effect of voltage (IR) drops in the voltage measurement
2. tt 192. 465 External corrosion control Monitoring.
(d) Each operator shall take prompt remedial action to correct any deficiencies
indicated by the monitoring.
PNGTS's procedures 453 and EDMS 004258833 do not specify a time frame for correcting any
deficiencies indicated by external corrosion morutonng
3 It 192. 473 External corrosion control: Interference currents
(a) Each operator whose pipelme system is subiected to stray currents shall have m
effect a continuing program to mmtmixe the detrimental effects of such currents
Apparently there is no PNGTS wntteu plan or procedure that addresses this code requirement
4. g 192 481 Atmospheric corrosion control Monitoring
(c) If atmosphenc corrosion is found durmg an mspection, the operator must
provide protection against the corrosion as required by $192. 479.
PNGTS's EDMS 004266539 does not specify a time frame for evaluating data and determining a
course of remedial action to correct deficiencies indicated by atmosphenc corrosion control
moiutoriug



Res onse to this Notice
Tlus Notice is provided pursuant to 49 U S C $ 60108(a) and 49 C F R II 190 237 Enclosed as
part of this Notice is a document entitled Response Options for Pipehne Operators in
Comphance Proceedings Please refer to this document and note the response options Be
advised that all material you submit in response to this enforcement action is sublect to being
made pubhcly available If you beheve that any portion of your responsive material quahfies for
confidential treatment under 5 U S C 552(b), along with the complete original document you
must provide a second copy of the document with the portions you believe qualify for
confidential treatment redacted and an explanation of why you believe the redacted information
quahfies for confidential treatment under 5 U S C 552(b) If you do not respond within 30 days
of receipt of this Notice, this constitutes a waiver of your right to contest the allegations in this
Notice and authorizes the Associate Administrator for Pipeline Safety to find facts as alleged in
this Notice without further notice to you and to issue a Final Order
If, after opportunity for a hearing, your plans or procedures are found inadequate as alleged in
this Notice, you may be ordered to amend your plans or procedures to correct the inadequacies
(49 C F R $ 190 237) If you are not contesting this Notice, we propose that you submit your
amended procedures to my office within 60 days of receipt of this Notice This period may be
extended by written request for good cause Once the inadequacies identified herein have been
addressed in your amended procedures, this enforcement action will be closed
In correspondence concerning this matter, please refer to CPF 1-2007-1007M and, for each
document you submit, please provide a copy in electronic format whenever possible
By on Coy, PE
Director, Eastern Region
Pipeline and Hazardous Matenals Safety Administration
Enclosure Response Options for Pipeline Operators in Compliance Proceedings

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/120071007M>
- Source ID: `phmsa-enforcement`
- SHA-256: `407a9835b2e3f75c3bf0ac56346bf9c66e9657186e08077d493eea0600de655f`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T20:23:27.480Z
- Document slug: `phmsa-enforcement-120071007m`

### Source metadata

```json
{
  "cpf": "120071007M",
  "operator": "PORTLAND NATURAL GAS TRANSMISSION SYSTEM",
  "region": "Eastern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.463(a)",
    "192.465(d)",
    "192.473(a)",
    "192.481(c)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 3,
  "attachments": [
    {
      "name": "120071007M_Notice of Amendment_080107.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120071007M/120071007M_Notice%20of%20Amendment_080107.pdf",
      "bytes": 77297,
      "category": "agency_document"
    },
    {
      "name": "120071007m_notice of amendment_080107_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120071007M/120071007m_notice%20of%20amendment_080107_text.pdf",
      "bytes": 83896,
      "category": "agency_document"
    },
    {
      "name": "120071007M_operator response to notice_09282007.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120071007M/120071007M_operator%20response%20to%20notice_09282007.pdf",
      "bytes": 489472,
      "category": "party_submission"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "PORTLAND NATURAL GAS TRANSMISSION SYSTEM"
}
```