# COLUMBIA GAS TRANSMISSION, LLC — Notice of Probable Violation

**Citation:** CPF 120111006  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2011-05-09

CLOSED notice of probable violation citing 192.736(b)(1).

## Document text

Notice of Probable Violation involving COLUMBIA GAS TRANSMISSION, LLC. PHMSA's enforcement data identifies the cited regulation as 192.736(b)(1). The case was opened on 2011-05-09 and is reported as closed as of 2012-04-23. Proposed civil penalty: $67,800. Assessed civil penalty: $67,800. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120111006_Final Order_04232012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_Final%20Order_04232012.pdf

120111006_Final Order_04232012_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_Final%20Order_04232012_text.pdf

120111006_NOPV PCP_05092011.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_NOPV%20PCP_05092011.pdf

120111006_NOPV PCP_05092011_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_NOPV%20PCP_05092011_text.pdf

120111006_Operator Response_06082011.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_Operator%20Response_06082011.pdf

120111006_Final Order_04232012_text.pdf

APR 23 2012
Mr. Jimmy D. Staton
Executive Vice President & CEO
NiSource Gas Transmission & Storage
801 E. 86th Ave
Merrillville, IN 46410
Re: CPF No. 1-2011-1006
Dear Mr. Staton:
Enclosed please find the Final Order issued in the above-referenced case. It makes a finding
of violation and assesses a civil penalty of $67,800. This is to acknowledge receipt of
payment of the full penalty amount, by wire transfer, dated June 6, 2011. This enforcement
action is now closed. Service of the Final Order by certified mail is deemed effective upon
the date of mailing, or as otherwise provided under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Jeffrey D. Wiese
Associate Administrator
for Pipeline Safety
Enclosure
cc: Mr. Byron Coy, Director, Eastern Region, OPS
Mr. Alan Mayberry, Deputy Associate Administrator for Field Operations, OPS
Mr. Joe Shields, Chief Operating Officer, NiSource Gas Transmission & Storage, 5151
San Felipe, Suite 2500, Houston, Texas 77056
CERTIFIED MAIL - RETURN RECEIPT REQUESTED



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
___________________________________
)
In the Matter of )
)
Columbia Gas Transmission Company, ) CPF No. 1-2011-1006
LLC, )
)
Respondent. )
___________________________________ )
FINAL ORDER
On May 18 to 22, 2009, pursuant to 49 U.S.C. § 60117, a representative of the Pipeline and
Hazardous Materials Safety Administration (PHMSA), Office of Pipeline Safety (OPS),
conducted an on-site pipeline safety inspection of the facilities and records of Columbia Gas
Transmission Company, LLC (Columbia GTC or Respondent). Columbia GTC is the operator
of a 12,000-mile gas pipeline system that includes more than three dozen storage fields in four
states.
1 The particular focus of the May 2009 OPS inspection was the Donegal Gas Storage
Field, an interstate natural gas storage field located in Washington County, Pennsylvania.2
As a result of the inspection, the Director, Eastern Region, OPS (Director), issued to Respondent,
by letter dated May 9, 2011, a Notice of Probable Violation and Proposed Civil Penalty (Notice).
In accordance with 49 C.F.R. § 190.207, the Notice proposed finding that Columbia GTC had
violated 49 C.F.R. § 192.736(b)(1) and proposed assessing a civil penalty of $67,800 for the
alleged violation.
Columbia GTC responded to the Notice by letter dated June 8, 2011 (Response). The company
did not contest the allegation of violation and paid the proposed civil penalty of $67,800, as
provided in 49 C.F.R. § 190.227. Payment of the penalty serves to close the case with prejudice
to Respondent.
FINDING OF VIOLATION
In its Response, Columbia GTC did not contest the allegation in the Notice that it violated
49 C.F.R. Part 192, as follows:
1 http://www.ngts.com/en/about-us/our-companies.aspx (last accessed Jan. 9, 2012).
2 http://www.ferc.gov/industries/gas.asp (last accessed Jan. 9, 2012) (providing list of interstate natural gas storage
fields by owner and location).



2
Item 1: The Notice alleged that Respondent violated 49 C.F.R. § 192.736(b)(1), which states:
§ 192.736 Compressor stations: Gas detection.
(a) Not later than September 16, 1996, each compressor building in a
compressor station must have a fixed gas detection and alarm system . . . .
(b) Except when shutdown of the system is necessary for maintenance
under paragraph (c) of this section, each gas detection and alarm system
required by this section must—
(1) Continuously monitor the compressor building for a concentration
of gas in air of not more than 25 percent of the lower explosive limit;. . . .
The Notice alleged that Respondent violated 49 C.F.R. § 192.736(b)(1) by failing to
continuously monitor the company’s Claysville Compressor Station for a concentration of gas in
air of not more than 25 % of the lower explosive limit (LEL). Specifically, the Notice alleged
that in November 2006, Columbia GTC had updated its written procedures to require that gas
detectors be set at 25% LEL monitoring level, but that a review of its records showed that from
January 9, 2007, to October 3, 2008, the gas detectors at the Claysville Compressor Station had
been set at 50% LEL level.
Respondent did not contest this allegation of violation. Accordingly, based upon a review of all
of the evidence, I find that Respondent violated 49 C.F.R. § 192.736(b)(1) by failing to
continuously monitor the Claysville Compressor Station for a concentration of gas in air of not
more than 25 % of the LEL.
This finding of violation will be considered a prior offense in any subsequent enforcement action
taken against Respondent.
The terms and conditions of this Final Order are effective upon service in accordance with
49 C.F.R. § 190.5.
___________________________________ __________________________
Jeffrey D. Wiese Date Issued
Associate Administrator
for Pipeline Safety

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/120111006>
- Source ID: `phmsa-enforcement`
- SHA-256: `f2c5182f84c913cc9930ce86c959f49adb84c5c32fb571863379ca0b8d41aa17`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-24T21:01:59.546Z
- Document slug: `phmsa-enforcement-120111006`

### Source metadata

```json
{
  "cpf": "120111006",
  "operator": "COLUMBIA GAS TRANSMISSION, LLC",
  "region": "Eastern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.736(b)(1)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 5,
  "attachments": [
    {
      "name": "120111006_Final Order_04232012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_Final%20Order_04232012.pdf",
      "bytes": 56223,
      "category": "agency_document"
    },
    {
      "name": "120111006_Final Order_04232012_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_Final%20Order_04232012_text.pdf",
      "bytes": 20720,
      "category": "agency_document"
    },
    {
      "name": "120111006_NOPV PCP_05092011.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_NOPV%20PCP_05092011.pdf",
      "bytes": 633053,
      "category": "case_document"
    },
    {
      "name": "120111006_NOPV PCP_05092011_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_NOPV%20PCP_05092011_text.pdf",
      "bytes": 26792,
      "category": "case_document"
    },
    {
      "name": "120111006_Operator Response_06082011.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120111006/120111006_Operator%20Response_06082011.pdf",
      "bytes": 200592,
      "category": "party_submission"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "COLUMBIA GAS TRANSMISSION, LLC"
}
```