# NEW YORK STATE ELECTRIC & GAS CORP — Notice of Probable Violation

**Citation:** CPF 120121004  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2012-05-21

CLOSED notice of probable violation citing 192.491(c), 192.616(f), 192.625(b), 192.706(a), 192.751(c).

## Document text

Notice of Probable Violation involving NEW YORK STATE ELECTRIC & GAS CORP. PHMSA's enforcement data identifies the cited regulations as 192.491(c),  192.616(f),  192.625(b),  192.706(a),  192.751(c). The case was opened on 2012-05-21 and is reported as closed as of 2012-11-09. Proposed civil penalty: $52,000. Assessed civil penalty: $52,000. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120121004_Final Order_10232012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_Final%20Order_10232012.pdf

120121004_Final Order_10232012_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_Final%20Order_10232012_text.pdf

120121004_NOPV_PCP_05212012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_NOPV_PCP_05212012.pdf

120121004_NOPV_PCP_05212012_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_NOPV_PCP_05212012_text.pdf

120121004_Operator Response_06182012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_Operator%20Response_06182012.pdf

120121004_Final Order_10232012_text.pdf

OCTOBER 23, 2012
Mr. Mark S. Lynch
President
New York State Electric and Gas Corporation
89 East Avenue
Rochester, NY 14649-0001
Re: CPF No. 1-2012-1004
Dear Mr. Lynch:
Enclosed please find the Final Order issued in the above-referenced case. It makes findings of
violation and assesses a civil penalty of $52,000. The penalty payment terms are set forth in the
Final Order. This enforcement action closes automatically upon receipt of payment. Service of
the Final Order by certified mail is deemed effective upon the date of mailing, or as otherwise
provided under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Jeffrey D. Wiese
Associate Administrator
for Pipeline Safety
Enclosure
cc: Mr. Byron Coy, P.E., Director, Eastern Region, OPS
Mr. Alan Mayberry, Deputy Associate Administrator for Field Operations, OPS
Mr. Kevin Speicher, New York State Department of Public Service
3 Empire State Plaza Albany, NY 12223
Mr. Michael Eastman, Vice President, Gas Operations, Rochester Gas and Electric –
89 East Ave., Rochester, NY 14649-0001
Mr. John J. Sherman, Chairman and Chief Executive Officer, Inergy Midstream, L.P. -
2 Brush Creek Blvd., Suite 200, Kansas City, MO 64112
CERTIFIED MAIL – RETURN RECEIPT REQUESTED



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
____________________________________
In the Matter of )
)
)
New York State Electric and Gas Corporation, )
)
Respondent. )
____________________________________)
) CPF No. 1-2012-1004
FINAL ORDER
From July 12 through August 23, 2010, pursuant to 49 U.S.C. § 60117, representatives of the
New York State Department of Public Service, acting as agent for the Pipeline and Hazardous
Materials Safety Administration (PHMSA), Office of Pipeline Safety (OPS), conducted an on-
site pipeline safety inspection of the facilities and records of New York State Electric and Gas
(NYSEG or Respondent) in Watkins Glen, New York. At the time of the inspection, NYSEG
operated a natural gas storage facility known as the Seneca Storage Facility and the associated
Seneca West Pipeline, which is approximately 20 miles long and connects the Seneca Storage
Facility to a transmission pipeline in Big Flats, New York.1
As a result of the inspection, the Director, Eastern Region, OPS (Director), issued to Respondent,
by letter dated May 21, 2012, a Notice of Probable Violation and Proposed Civil Penalty
(Notice), which also included a warning pursuant to 49 C.F.R. § 190.205. In accordance with
49 C.F.R. § 190.207, the Notice proposed finding that NYSEG committed various violations of
49 C.F.R. Part 192 and proposed assessing a civil penalty of $52,000 for the alleged violations.
The warning item required no further action, but warned the operator to correct the probable
violation or face possible enforcement action.
NYSEG responded to the Notice by letter dated June 18, 2012 (Response).2 The company did
not contest the allegations of violation but provided an explanation of its actions. Respondent
did not request a hearing and therefore has waived its right to one.
1 On July 13, 2011, NYSEG sold the Seneca Storage Facility and the Seneca West Pipeline to Inergy Midstream,
LP, the current operator of the facilities.
2 While the Seneca Storage Facility and the Seneca West Pipeline were operated by NYSEG at the time of the
inspection, the Notice was addressed to Rochester Gas and Electric Corporation. Both companies are subsidiaries of
Iberdrola USA. See http://www.iberdrolausa.com/OurCompanies/nyseg html (last accessed October 9, 2012).



2
FINDINGS OF VIOLATION
The Notice alleged that Respondent violated 49 C.F.R. Part 192, as follows:
Item 1: The Notice alleged that Respondent violated 49 C.F.R. § 192.625(b), which states:
§ 192.625 Odorization of gas.
(a) A combustible gas in a distribution line must contain a natural
odorant or be odorized so that at a concentration in air of one-fifth of the
lower explosive limit, the gas is readily detectable by a person with a
normal sense of smell.
(b) After December 31, 1976, a combustible gas in a transmission line
in a Class 3 or Class 4 location must comply with the requirements of
paragraph (a) of this section unless:
(1) At least 50 percent of the length of the line downstream from that
location is in a Class 1 or Class 2 location;
(2) The line transports gas to any of the following facilities which
received gas without an odorant from that line before May 5, 1975;
(i) An underground storage field;
(ii) A gas processing plant;
(iii) A gas dehydration plant; or
(iv) An industrial plant using gas in a process where the presence of
an odorant:
(A) Makes the end product unfit for the purpose for which it is
intended;
(B) Reduces the activity of a catalyst; or
(C) Reduces the percentage completion of a chemical reaction;
(3) In the case of a lateral line which transports gas to a distribution
center, at least 50 percent of the length of that line is in a Class 1 or Class
2 location; or
(4) The combustible gas is hydrogen intended for use as a feedstock in
a manufacturing process.
The Notice alleged that Respondent violated 49 C.F.R. § 192.625(b) by failing to odorize the gas
in its transmission line. Specifically, the Notice alleged that NYSEG failed to odorize the gas in
the Seneca West Pipeline, which the company’s Operations and Maintenance (O&M) Procedure
7.650 indicated was located within a Class 3 location. In its Response, NYSEG did not contest
the allegation of violation. The company stated, however, that while its philosophy was to
conservatively design all facilities to Class 3 requirements, the entire Seneca West Pipeline was
located entirely within Class 1 and 2 locations and that therefore the exemption in
§ 192.625(b)(1) applied to this pipeline. NYSEG acknowledged that the company’s O&M
procedure did not specify that the exemption applied to this line.
Notwithstanding Respondent’s contention that the pipeline was exempt from the odorization
requirement, NYSEG did not submit any evidence demonstrating that at least 50 percent of the
length of the downstream line was in a Class 1 or Class 2 location. The company’s O&M



3
procedure stated only that the pipeline should be operated as if it were in a Class 3 location;
therefore, the gas was required to be odorized. Accordingly, after considering all of the
evidence, I find that Respondent violated 49 C.F.R. § 192.625(b) by failing to odorize the gas in
its transmission line.
Item 2: The Notice alleged that Respondent violated 49 C.F.R. § 192.491(c), which states:
§ 192.491 Corrosion control records.
(a) . . .
(c) Each operator shall maintain a record of each test, survey, or
inspection required by this subpart in sufficient detail to demonstrate
the adequacy of corrosion control measures or that a corrosive
condition does not exist. These records must be retained for at least 5
years, except that records related to §§ 192.465 (a) and (e) and
192.475(b) must be retained for as long as the pipeline remains in
service.
The Notice alleged that Respondent violated 49 C.F.R. § 192.491(c) by failing to maintain a
record of each test, survey, or inspection required by Subpart I of Part 192. Specifically, the
Notice alleged that NYSEG could not produce a record of the internal pipe-surface inspection
required by § 192.475(b)3 when meters were replaced at the Seneca Storage Facility in 2009.
Respondent did not contest this allegation of violation. Accordingly, based upon a review of all
of the evidence, I find that Respondent violated 49 C.F.R. § 192.491(c) by failing to maintain a
record of each test, survey, or inspection required by Subpart I of Part 192.
Item 3: The Notice alleged that Respondent violated 49 C.F.R. § 192.616(f), which states:
§ 192.616 Public awareness.
(a) Except for an operator of a master meter or petroleum gas system
covered under paragraph (j) of this section, each pipeline operator must
develop and implement a written continuing public education program that
follows the guidance provided in the American Petroleum Institute's (API)
Recommended Practice (RP) 1162 (incorporated by reference, see
§ 192.7) . . . .
(f) The program and the media used must be as comprehensive as
necessary to reach all areas in which the operator transports gas.
The Notice alleged that Respondent violated 49 C.F.R. § 192.616(f) by failing to ensure its
public education program was as comprehensive as necessary to reach all areas in which the
company transported gas. Specifically, the Notice alleged that NYSEG’s public education
program did not ensure that the required information would reach all the public living along the
pipeline right-of-way (ROW).
3 49 C.F.R. § 192.475(b) states, in relevant part: “Whenever any pipe is removed from a pipeline for any reason, the
internal surface must be inspected for evidence of corrosion. . . .”



4
Respondent did not contest this allegation of violation. Accordingly, based upon a review of all
of the evidence, I find that Respondent violated 49 C.F.R. § 192.616(f) by failing to ensure its
public education program was as comprehensive as necessary to reach all areas in which it
transported gas.
Item 4: The Notice alleged that Respondent violated 49 C.F.R. § 192.491(c), as quoted above,
by failing to maintain a record of each test, survey, or inspection required by Subpart I of Part
192. Specifically, the Notice alleged that NYSEG failed to maintain a record of the most recent
atmospheric corrosion inspection required by § 192.481(a).4
Respondent did not contest this allegation of violation. Accordingly, based upon a review of all
of the evidence, I find that Respondent violated 49 C.F.R. § 192.491(c) by failing to maintain a
record of each test, survey, or inspection required by Subpart I of Part 192.
Item 5: The Notice alleged that Respondent violated 49 C.F.R. § 192.706(a), which states:
§ 192.706 Transmission lines: Leakage surveys.
Leakage surveys of a transmission line must be conducted at intervals
not exceeding 15 months, but at least once each calendar year. However,
in the case of a transmission line which transports gas in conformity with
§ 192.625 without an odor or odorant, leakage surveys using leak detector
equipment must be conducted—
(a) In Class 3 locations, at intervals not exceeding 7½ months, but at
least twice each calendar year . . . .
The Notice alleged that Respondent violated 49 C.F.R. § 192.706(a) by failing to conduct
leakage surveys of its transmission line at intervals not exceeding 7½ months, but at least twice
each calendar year. Specifically, the Notice alleged that no instrumented leakage surveys had
been conducted on the transmission lines at the Seneca Storage Facility and that there was only a
record of one instrumented leak detection survey, performed in 2009, for the Seneca West
Pipeline.
Respondent did not contest this allegation of violation. Accordingly, based upon a review of all
of the evidence, I find that Respondent violated 49 C.F.R. § 192.706(a) by failing to conduct
leakage surveys of its transmission line at intervals not exceeding 7½ months, but at least twice
each calendar year.
These findings of violation will be considered prior offenses in any subsequent enforcement
action taken against Respondent.
4 49 C.F.R. § 192.481(a) requires each operator to inspect each onshore pipeline or portion of pipeline that is
exposed to the atmosphere for evidence of atmospheric corrosion at least once every three calendar years, but at
intervals not exceeding 39 months.



5
ASSESSMENT OF PENALTY
Under 49 U.S.C. § 60122, Respondent is subject to an administrative civil penalty not to exceed
$100,000 per violation for each day of the violation, up to a maximum of $1,000,000 for any
related series of violations. In determining the amount of a civil penalty under
49 U.S.C. § 60122 and 49 C.F.R. § 190.225, I must consider the following criteria: the nature,
circumstances, and gravity of the violation, including adverse impact on the environment; the
degree of Respondent’s culpability; the history of Respondent’s prior offenses; the Respondent’s
ability to pay the penalty and any effect that the penalty may have on its ability to continue doing
business; and the good faith of Respondent in attempting to comply with the pipeline safety
regulations. In addition, I may consider the economic benefit gained from the violation without
any reduction because of subsequent damages, and such other matters as justice may require.
The Notice proposed a total civil penalty of $52,000 for the violations cited above.
Item 1: The Notice proposed a civil penalty of $10,000 for Respondent’s violation of
49 C.F.R. § 192.625(b), for failing to odorize the gas in its transmission line. As discussed
above, NYSEG did not contest the allegation of violation but claimed that the pipeline was
exempt from the odorization requirement. Respondent failed to present any evidence supporting
its contention or any information justifying a reduction in the proposed penalty. Public safety is
jeopardized when a gas pipeline in a populated area is not odorized. The regulatory requirement
is clear and NYSEG is fully culpable for the failure to odorize the pipeline. Accordingly, having
reviewed the record and considered the assessment criteria, I assess Respondent a civil penalty of
$10,000 for violation of 49 C.F.R. § 192.625(b).
Item 2: The Notice proposed a civil penalty of $8,700 for Respondent’s violation of
49 C.F.R. § 192.491(c), for failing to maintain a record of each test, survey, or inspection
required by Subpart I of Part 192. NYSEG neither contested the allegation nor presented any
evidence or argument justifying a reduction in the proposed penalty. The failure to maintain
records of corrosion inspections on the pipeline limits the operator’s ability to analyze corrosion
threats. While NYSEG was fully culpable for the failure to maintain these records, the violation
did not pose a significant threat to pipeline integrity or public safety. I find that the nature,
circumstances, and gravity of the violation support the proposed penalty. Accordingly, having
reviewed the record and considered the assessment criteria, I assess Respondent a civil penalty of
$8,700 for violation of 49 C.F.R. § 192.491(c).
Item 3: The Notice proposed a civil penalty of $10,000 for Respondent’s violation of
49 C.F.R. § 192.616(f), for failing to ensure that its public education program was as
comprehensive as necessary to reach all areas in which it transported gas. NYSEG neither
contested the allegation nor presented any evidence or argument justifying a reduction in the
proposed penalty. While NYSEG had a public awareness program, it was not comprehensive
enough to ensure that the public living along the ROW had adequate information about the
pipeline and the potential impact of a natural gas release or ignition. While pipeline integrity
was not significantly impacted by the violation, public safety could have been adversely affected
if a pipeline incident had occurred. I find that the nature, circumstances, and gravity of the
violation support the proposed penalty. Accordingly, having reviewed the record and considered
the assessment criteria, I assess Respondent a civil penalty of $10,000 for violation of



6
49 C.F.R. § 192.616(f).
Item 4: The Notice proposed a civil penalty of $8,700 for Respondent’s violation of
49 C.F.R. § 192.491(c), for failing to maintain a record of each test, survey, or inspection
required by Subpart I of Part 192. NYSEG neither contested the allegation nor presented any
evidence or argument justifying a reduction in the proposed penalty. The failure to maintain
records of corrosion inspections on the pipeline limited the operator’s ability to analyze
corrosion threats. While NYSEG was fully culpable for the failure to maintain these records, the
violation did not pose a significant threat to pipeline integrity or public safety. I find that the
nature, circumstances, and gravity of the violation support the proposed penalty. Accordingly,
having reviewed the record and considered the assessment criteria, I assess Respondent a civil
penalty of $8,700 for violation of 49 C.F.R. § 192.491(c).
Item 5: The Notice proposed a civil penalty of $14,600 for Respondent’s violation of
49 C.F.R. § 192.706(a), for failing to conduct leakage surveys of its transmission line at intervals
not exceeding 7½ months, but at least twice each calendar year. NYSEG neither contested the
allegation nor presented any evidence or argument justifying a reduction in the proposed penalty.
While pipeline integrity was not significantly impacted by the violation, public safety and the
safety of operator personnel could have been impacted if a pipeline incident had occurred as a
result of the operator’s noncompliance. I find that the nature, circumstances, gravity, and
duration of the violation support the proposed penalty. Accordingly, having reviewed the record
and considered the assessment criteria, I assess Respondent a civil penalty of $14,600 for
violation of 49 C.F.R. § 192.706(a).
In summary, having reviewed the record and considered the assessment criteria for each of the
Items cited above, I assess Respondent a total civil penalty of $52,000.
Payment of the civil penalty must be made within 20 days of service. Federal regulations
(49 C.F.R. § 89.21(b)(3)) require such payment to be made by wire transfer through the Federal
Reserve Communications System (Fedwire), to the account of the U.S. Treasury. Detailed
instructions are contained in the enclosure. Questions concerning wire transfers should be
directed to: Financial Operations Division (AMZ-341), Federal Aviation Administration, Mike
Monroney Aeronautical Center, P.O. Box 269039, Oklahoma City, Oklahoma 73125. The
Financial Operations Division telephone number is (405) 954-8893.
Failure to pay the $52,000 civil penalty will result in accrual of interest at the current annual rate
in accordance with 31 U.S.C. § 3717, 31 C.F.R. § 901.9 and 49 C.F.R. § 89.23. Pursuant to
those same authorities, a late penalty charge of six percent (6%) per annum will be charged if
payment is not made within 110 days of service. Furthermore, failure to pay the civil penalty
may result in referral of the matter to the Attorney General for appropriate action in a district
court of the United States.



7
WARNING ITEM
With respect to Item 6, the Notice alleged a probable violation of Part 192 but did not propose a
civil penalty or compliance order for this item. Therefore, this is considered to be a warning
item. The warning was for:
49 C.F.R. § 192.751(c) (Item 6) ─ Respondent’s alleged failure to have sufficient
warning signs to minimize the danger of accidental ignition of gas at the NYSEG
Hibbard Road and Backer Road valve set facilities.
NYSEG stated in its Response that it would communicate this issue to Inergy Midstream, LLC,
the current owner of the Seneca West Pipeline. If OPS finds a violation of this provision, the
pipeline operator may be subject to future enforcement action.
Under 49 C.F.R. § 190.215, Respondent has the right to submit a Petition for Reconsideration of
this Final Order. The petition must be sent to: Associate Administrator, Office of Pipeline
Safety, PHMSA, 1200 New Jersey Avenue, SE, East Building, 2nd Floor, Washington, DC
20590, with a copy sent to the Office of Chief Counsel, PHMSA, at the same address. PHMSA
will accept petitions received no later than 20 days after receipt of service of the Final Order by
the Respondent, provided they contain a brief statement of the issue(s) and meet all other
requirements of 49 C.F.R. § 190.215. The filing of a petition automatically stays the payment of
any civil penalty assessed but does not stay any other provisions of the Final Order, including
any required corrective actions. If Respondent submits payment of the civil penalty, the Final
Order becomes the final administrative decision and the right to petition for reconsideration is
waived.
The terms and conditions of this Final Order are effective upon service in accordance with
49 C.F.R. § 190.5.
___________________________________ __________________________
Jeffrey D. Wiese Date Issued
Associate Administrator
for Pipeline Safety

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/120121004>
- Source ID: `phmsa-enforcement`
- SHA-256: `4a01837327ba887503d3d9d0f7744e1e7ac77315d204867d9d37b3d439d7a17d`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T20:09:52.442Z
- Document slug: `phmsa-enforcement-120121004`

### Source metadata

```json
{
  "cpf": "120121004",
  "operator": "NEW YORK STATE ELECTRIC & GAS CORP",
  "region": "Eastern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.491(c)",
    "192.616(f)",
    "192.625(b)",
    "192.706(a)",
    "192.751(c)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 5,
  "attachments": [
    {
      "name": "120121004_Final Order_10232012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_Final%20Order_10232012.pdf",
      "bytes": 3693176,
      "category": "agency_document"
    },
    {
      "name": "120121004_Final Order_10232012_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_Final%20Order_10232012_text.pdf",
      "bytes": 49747,
      "category": "agency_document"
    },
    {
      "name": "120121004_NOPV_PCP_05212012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_NOPV_PCP_05212012.pdf",
      "bytes": 954837,
      "category": "case_document"
    },
    {
      "name": "120121004_NOPV_PCP_05212012_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_NOPV_PCP_05212012_text.pdf",
      "bytes": 36403,
      "category": "case_document"
    },
    {
      "name": "120121004_Operator Response_06182012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121004/120121004_Operator%20Response_06182012.pdf",
      "bytes": 158620,
      "category": "party_submission"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "NEW YORK STATE ELECTRIC & GAS CORP"
}
```