# COLUMBIA GAS TRANSMISSION, LLC — Notice of Probable Violation

**Citation:** CPF 120121009  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2012-04-06

CLOSED notice of probable violation citing 191.5(a), 192.605.

## Document text

Notice of Probable Violation involving COLUMBIA GAS TRANSMISSION, LLC. PHMSA's enforcement data identifies the cited regulations as 191.5(a),  192.605. The case was opened on 2012-04-06 and is reported as closed as of 2012-12-27. Proposed civil penalty: $32,500. Assessed civil penalty: $0. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120121009_Final Order_12272012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_Final%20Order_12272012.pdf

120121009_Final Order_12272012_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_Final%20Order_12272012_text.pdf

120121009_NOPV_PCP_04062012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_NOPV_PCP_04062012.pdf

120121009_NOPV_PCP_04062012_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_NOPV_PCP_04062012_text.pdf

120121009_Operator Response_05042012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_Operator%20Response_05042012.pdf

120121009_Final Order_12272012_text.pdf

DECEMBER 27, 2012
Mr. Robert C. Skaggs, Jr.
President & CEO
NiSource, Inc.
801 East 86th Ave.
Merrillville, Indiana 46410
Re: CPF No. 1-2012-1009
Dear Mr. Skaggs:
Enclosed please find the Final Order issued in the above-referenced case. It withdraws one
allegation of violation and issues a warning to NiSource Gas Transmission and Storage
Company with respect to one other alleged violation. This case is now closed. Service of the
Final Order by certified mail is deemed effective upon the date of mailing, or as otherwise
provided under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Jeffrey D. Wiese
Associate Administrator
for Pipeline Safety
Enclosure
cc: Mr. Michael Hoffman, Manager – System Integrity, NiSource Gas Transmission and
Storage Company, 1700 MacCorkle Avenue, Charleston, WV, 25314
Mr. Byron E. Coy, Eastern Region Director, OPS
Mr. Alan Mayberry, Deputy Associate Administrator for Field Operations, OPS
CERTIFIED MAIL - RETURN RECEIPT REQUESTED



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
__________________________________________
In the Matter of )
NiSource Gas Transmission & Storage ) CPF No. 1-2012-1009
Company, )
)
)
)
Respondent. )
__________________________________________)
FINAL ORDER
On October 5, 2010, and June 3, 2011, pursuant to 49 U.S.C. § 60117, representatives of the
West Virginia Public Service Commission (WV PSC), acting as agent for the Pipeline and
Hazardous Materials Safety Administration (PHMSA), Office of Pipeline Safety (OPS),
conducted an on-site pipeline safety inspection of NiSource Gas Transmission & Storage
Company’s (NGTSC or Respondent) SM-80 facilities, operated by Columbia Gas Transmission,
LLC, and its records in West Virginia. NGTSC is a subsidiary of NiSource, Inc.1 The Columbia
Gas Transmission system consists of approximately 12,000 miles of pipeline, transporting an
average of three billion cubic feet of natural gas per day through 10 states.2
As a result of the inspection, the Director, Eastern Region, OPS (Director), issued to NGTSC, by
letter dated April 6, 2012, a Notice of Probable Violation and Proposed Civil Penalty (Notice),
which also included a warning pursuant to 49 C.F.R. § 190.205. In accordance with
49 C.F.R. § 190.207, the Notice proposed finding that NGTSC had violated 49 C.F.R. § 191.5,
proposed assessing a civil penalty of $32,500 for the alleged violation, and warned Respondent
to take appropriate corrective action or be subject to future enforcement action.
NGTSC responded to the Notice by letter dated May 4, 2012 (Response). NGTSC contested the
allegation, offered additional information in response to the Notice, and requested that the
proposed civil penalty be reduced or eliminated.
1 NiSource, Inc., Annual Report (Form 10K), at Exhibit 21 (February 24, 2012).
2 NiSource Gas Transmission and Storage Home Page, http://www ngts.com/en/home.aspx (last visited November
5, 2012).



2
FINDING OF VIOLATION
The Notice alleged that Respondent violated 49 C.F.R. Part 191, as follows:
Item 1: The Notice alleged that Respondent violated 49 C.F.R. § 191.5(a), which states:
§ 191.5 Telephonic notice of certain incidents.
(a) At the earliest practicable moment following discovery, each
operator shall give notice in accordance with paragraph (b) of this section
of each incident as defined in § 191.3.
The Notice alleged that Respondent violated 49 C.F.R. § 191.5(a) by failing to make a telephonic
report of an incident on pipeline SM-80 at the earliest practicable moment following discovery.
Specifically, the Notice alleged that an incident occurring on July 16, 2008, but was never
reported by NGTSC to the National Response Center (NRC). At the time of the event, 49 C.F.R.
§ 191.3 defined the term “Incident” as follows:
Incident means any of the following events:
(1) An event that involves a release of gas from a pipeline or of
liquefied natural gas or gas from an LNG facility and
(i) A death, or personal injury necessitating in-patient hospitalization;
or
(ii) Estimated property damage, including cost of gas lost, of the
operator or others, or both, of $50,000 or more; . . . .3
According to the Notice, an NGTSC crew hit a consumer tap line operating at about 693 psig, at
which point NGTSC blew down more than an estimated $50,000 worth of gas in order to stop
the resulting leak. Because the amount of the gas lost exceeded $50,000, the Notice alleged that
NGTSC was required to make a telephonic report of the incident. In response to subsequent
information requests from the WV PSC, NGTSC provided information indicating a total cost of
$106,544 for the gas lost from the damaged consumer tap line and from purging the transmission
line.
In its Response, NGTSC argued that the $50,000 reporting threshold in 49 C.F.R. § 191.3 did not
apply to gas lost due to an intentional or optional blow down.4 NGTSC contended that the
allegation in the NOPV reflected an incorrect application of the regulation because it included
the cost of gas that was evacuated from the pipeline due to an intentional blow-down for the
purpose of making a repair.
According to NGTSC, a small leak at a weld intersection had occurred as a result of certain
3 Section 191.3 was amended effective November 26, 2010, and redefined the term “Incident” to cover “[e]stimated
property damage of $50,000 or more, including loss to the operator and others, or both, but excluding cost of gas
lost.”
.
4 Response at 2.



3
maintenance work done on July 16, 2008. The amount of gas escaping from the leak was
minimal and the condition did not cause a risk to public safety. The amount of gas lost was
conservatively estimated at less than 30 MCF and the value of the gas lost from the leak was
$279.41. In addition, the cost of the repair, including labor, equipment and materials, was less
than $2,000. The total property damage due to the repair plus the gas lost as a result of the
incident was less than the $50,000 incident threshold. Therefore, NiSource argued, the event
did not meet the definition of “Incident” under the regulations in effect at that time or now.
I agree. Upon review of the record, it is apparent that the estimated property damage was
determined by including the gas lost during the blow down and therefore reached the $50,000
threshold for incident reporting. However, by the agency’s own guidance (i.e., PHMSA Form F
7100.2 (1-2002)), the reporting threshold has not been interpreted as including the cost of gas
incurred as part of routine maintenance. Specifically, the general instructions for the incident
report form indicate that a release of gas “during maintenance or other routine activities need not
be reported if the only reportable criteria met is losing gas of $50,000 or more as defined in
191.3(1)(ii).”5 Under Part A – General Report Information on Form F 7100.2 (1-2002), it further
states that “[f]acility repair, replacement, or change that is not related to the incident but the
operator does for convenience is not to be included.” Therefore, I find that the blow down and
subsequent gas loss should be considered as part of the pipeline’s routine maintenance activities
to repair the leak.
Accordingly, I find that NGTSC did not violate § 191.5(a) because the leak did not meet the
definition of “incident” that would require a report. Based upon the foregoing, I hereby order
that this Item and the proposed penalty be withdrawn.
WARNING ITEM
With respect to Item 2, the Notice alleged a probable violation of Part 192 but did not propose a
civil penalty or compliance order for this item. Therefore, this is considered to be a warning
item. The warning was for:
49 C.F.R. § 192.605 (Item 2) ─ Respondent’s alleged failure to follow its
[Operation and Maintenance Procedure 200.01.02, section 3.4,] that required
identification tags on emergency valves. The NGTSC pipeline SM-80 Martha
valve setting had no identification tags on the following critical valves:
1. One main line valve;
2. Two bypass valves; and
3. Two blow down valves.
NGTSC presented information in its Response showing that it had replaced the missing tags
listed above and had instituted an initiative to identify missing identification tags on critical
5 Pipeline and Hazardous Materials Safety Administration, Pipeline Safety Community Forms,
http://phmsa.dot.gov/pipeline/library/forms (last visited November 5, 2012).



4
valves throughout its system.6 If OPS finds a violation of this provision in a subsequent
inspection, Respondent may be subject to future enforcement action.
The terms and conditions of this Final Order are effective upon service in accordance with 49
C.F.R. § 190.5.
___________________________________ __________________________
Jeffrey D. Wiese Date Issued
Associate Administrator
for Pipeline Safety
6 Response at 3.

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/120121009>
- Source ID: `phmsa-enforcement`
- SHA-256: `a0b05cce3243669b6f47df70e607839be51815205b54358f4d14515beb9d001c`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T14:03:51.183Z
- Document slug: `phmsa-enforcement-120121009`

### Source metadata

```json
{
  "cpf": "120121009",
  "operator": "COLUMBIA GAS TRANSMISSION, LLC",
  "region": "Eastern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "191.5(a)",
    "192.605"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 5,
  "attachments": [
    {
      "name": "120121009_Final Order_12272012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_Final%20Order_12272012.pdf",
      "bytes": 1805274,
      "category": "agency_document"
    },
    {
      "name": "120121009_Final Order_12272012_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_Final%20Order_12272012_text.pdf",
      "bytes": 36524,
      "category": "agency_document"
    },
    {
      "name": "120121009_NOPV_PCP_04062012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_NOPV_PCP_04062012.pdf",
      "bytes": 1252135,
      "category": "case_document"
    },
    {
      "name": "120121009_NOPV_PCP_04062012_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_NOPV_PCP_04062012_text.pdf",
      "bytes": 53370,
      "category": "case_document"
    },
    {
      "name": "120121009_Operator Response_05042012.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120121009/120121009_Operator%20Response_05042012.pdf",
      "bytes": 558499,
      "category": "party_submission"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "COLUMBIA GAS TRANSMISSION, LLC"
}
```