# TOTAL PEAKING SERVICES — Warning Letter

**Citation:** CPF 120195004W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2019-04-02

CLOSED warning letter citing 193.2619(c)(2), 193.2717(b).

## Document text

Warning Letter involving TOTAL PEAKING SERVICES. PHMSA's enforcement data identifies the cited regulations as 193.2619(c)(2),  193.2717(b). The case was opened on 2019-04-02 and is reported as closed as of 2019-04-02. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120195004W_Warning Letter_04022019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120195004W/120195004W_Warning%20Letter_04022019.pdf

120195004W_Warning Letter_04022019_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120195004W/120195004W_Warning%20Letter_04022019_text.pdf

120195004W_Warning Letter_04022019_text.pdf

WARNING LETTER
OVERNIGHT EXPRESS DELIVERY
April 2, 2019
Anthony Marone
Senior Vice President, Gas Operations
AVANGRID Networks
Total Peaking Services
180 Marsh Hill Rd.
Orange, CT 06477
CPF 1-2019-5004W
Dear Mr. Marone:
On April 24 to April 30, 2018, an inspector from the Connecticut Department of Energy and
Environmental Protection (CT DEEP), acting as Agent for Pipeline and Hazardous Materials
Safety Administration (PHMSA), Office of Pipeline Safety (OPS), pursuant to Chapter 601 of
Title 49 of the United States Code inspected Total Peaking Services’ (TPS) records and procedures
at its LNG plant located in Bridgeport, Connecticut.
As a result of the inspection, it is alleged that you have committed probable violations of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The items inspected
and the probable violations are:
1. § 193.2619 Control Systems
…
(c) Control systems in service, but not normally in operation, such as relief
valves and automatic shutdown devices, and control systems for internal shutoff
valves for bottom penetration tanks must be inspected and tested once each
calendar year, not exceeding 15 months, with the following exceptions:
…
(2) Control systems that are intended for fire protection must be inspected and
tested at regular intervals not to exceed 6 months.
TPS failed to inspect and test at regular intervals not to exceed 6 months, control systems that are
intended for fire protection. Specifically, TPS failed to inspect and test UV detection at intervals
not to exceed 6 months.



CPF 1-2019-5004W
During the inspection, the CT DEEP inspector reviewed TPS’s Preventive Maintenance Work
Orders from April 2016 to September 2017. Records provided showed UV detection inspections
and tests were performed on 7/14/2016 and 9/18/2017. The interval between inspections and
tests exceeded 6 months.
Therefore, TPS failed to inspect and test a control system that is intended for fire protection, UV
detection, at regular intervals not to exceed 6 months.
2. § 193.2717 Training, fire protection.
…
(b) A written plan of continuing instruction, including plant fire drills, must be
conducted at intervals of not more than 2 years to keep personnel current on the
knowledge and skills they gained in the instruction under paragraph (a) of this
section.
TPS failed to conduct plant fire drills at intervals of not more than 2 years to keep personnel
current on the knowledge and skills they gained in the instruction under § 193.2717(a).
During the inspection, the CT DEEP inspector reviewed records of TPS’s plant fire drills. The
records demonstrated that TPS performed plant fire drills on November 12, 2014 and November
29, 2016. This exceeds the maximum interval of 2 years by 17 days. Upon being informed of
this issue, TPS stated they will change the recurrence on this work order to 21 months to provide
adequate time to complete future plant fire drills within the required interval.
Please be advised that all material you submit in response to this enforcement action is subject to
being made publicly available. If you believe that any portion of your responsive material qualifies
for confidential treatment under 5 U.S.C. 552(b), along with the complete original document you
must provide a second copy of the document with the portions you believe qualify for confidential
treatment redacted and an explanation of why you believe the redacted information qualifies for
confidential treatment under 5 U.S.C. 552(b).
No reply to this letter is required. If you choose to reply, please submit all correspondence in this
matter to Robert Burrough, Director, PHMSA Eastern Region, 840 Bear Tavern Road, Suite 300,
West Trenton, NJ 08628. Please refer to CPF 1-2019-5004W on each document you submit, and
whenever possible provide a signed PDF copy in electronic format. Smaller files may be emailed
to robert.burrough@dot.gov. Larger files should be sent on a USB flash drive accompanied by the
original paper copy to the Eastern Region Office.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
120195004W_Warning Letter_04022019_text Page 2 of 2

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/120195004W>
- Source ID: `phmsa-enforcement`
- SHA-256: `c6b8b1f0da1413ab294f45a58776d7e70d9aeaa2fea291bcf8c14213aab85886`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-25T08:16:15.479Z
- Document slug: `phmsa-enforcement-120195004w`

### Source metadata

```json
{
  "cpf": "120195004W",
  "operator": "TOTAL PEAKING SERVICES",
  "region": "Eastern",
  "pipelineType": "INTERSTATE LIQUID ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "193.2619(c)(2)",
    "193.2717(b)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "120195004W_Warning Letter_04022019.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120195004W/120195004W_Warning%20Letter_04022019.pdf",
      "bytes": 1447007,
      "category": "agency_document"
    },
    {
      "name": "120195004W_Warning Letter_04022019_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120195004W/120195004W_Warning%20Letter_04022019_text.pdf",
      "bytes": 109316,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "TOTAL PEAKING SERVICES"
}
```