# SUNOCO PIPELINE L.P. — Warning Letter

**Citation:** CPF 120195014W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2019-12-12

CLOSED warning letter citing 195.432(b).

## Document text

Warning Letter involving SUNOCO PIPELINE L.P.. PHMSA's enforcement data identifies the cited regulation as 195.432(b). The case was opened on 2019-12-12 and is reported as closed as of 2019-12-12. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120195014W_Operator Response to Notice_12162019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120195014W/120195014W_Operator%20Response%20to%20Notice_12162019.pdf

120195014W_Warning Letter_12122019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120195014W/120195014W_Warning%20Letter_12122019.pdf

120195014W_Warning Letter_12122019_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120195014W/120195014W_Warning%20Letter_12122019_text.pdf

120195014W_Warning Letter_12122019_text.pdf

WARNING LETTER
OVERNIGHT EXPRESS DELIVERY
December 12, 2019
Gregory McIlwain
Senior VP, Operations
Sunoco Pipeline, L.P.
1300 Main Street
Houston, TX 77002
CPF 1-2019-5014W
Dear Mr. McIlwain:
From April 1 – August 16, 2019, a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) Office of Pipeline Safety (OPS), pursuant to Chapter 601 of 49 United
States Code (U.S.C.), inspected Sunoco Pipeline, L.P.’s (Sunoco) Sunoco Products East 1 pipeline
system in both Pennsylvania and New Jersey.
As a result of the inspection, it is alleged that you have committed a probable violation of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The item inspected and
the probable violation is:
1. § 195.432 Inspection of in-service breakout tanks.
(a)…
(b) Each operator must inspect the physical integrity of in-service
atmospheric and low-pressure steel above-ground breakout tanks
according to API Std 653 (except section 6.4.3, Alternative Internal
Inspection Interval) (incorporated by reference, see § 195.3). However,
if structural conditions prevent access to the tank bottom, its integrity
may be assessed according to a plan included in the operations and
maintenance manual under § 195.402(c)(3). The risk-based internal
inspection procedures in API Std 653, section 6.4.3 cannot be used to
determine the internal inspection interval.



Sunoco failed to inspect the physical integrity of in-service atmospheric and low-pressure steel
aboveground breakout tank according to American Petroleum Institute (API) Standard 653
(incorporated by reference into 49 C.F.R. Part 195, see § 195.3(b)(19)), as prescribed in
§ 195.432(b). Specifically, Sunoco did not conduct an external inspection for Tank 4 at its Icedale
breakout tank facility within the 5-year interval specified under API Standard 653 Section 6.3.2.1
- External Inspection (Section 6.3.2.1).
Section 6.3.2.1 states:
All tanks shall be given a visual external inspection by an authorized inspector. This
inspection shall be called the external inspection and must be conducted at least every 5
years or RCA/4N years (where RCA is the difference between the measured shell thickness
and the minimum required thickness in mils, and N is the shell corrosion rate in mils per
year) whichever is less. Tanks may be in operation during this inspection.
During the inspection, the PHMSA inspector reviewed API Standard 653 external inspection
reports for Sunoco’s Icedale breakout tank facility. The records indicated that external inspections
were conducted for its Tank 4 on June 26, 2009 and February 5, 2015. This exceeded the 5-year
maximum interval specified in Section 6.3.2.1 by approximately 7.5 months.
Therefore, Sunoco failed to inspect its Tank 4 per API Standard 653 Section 6.3.2.1 requirements
regarding inspection interval.
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$218,647 per violation per day the violation persists, up to a maximum of $2,186,465 for a related
series of violations. For violation occurring on or after November 27, 2018 and before July 31,
2019, the maximum penalty may not exceed $213,268 per violation per day, with a maximum
penalty not to exceed $2,132,679. For violation occurring on or after November 2, 2015 and before
November 27, 2018, the maximum penalty may not exceed $209,002 per violation per day, with a
maximum penalty not to exceed $2,090,022. For violations occurring prior to November 2, 2015,
the maximum penalty may not exceed $200,000 per violation per day, with a maximum penalty
not to exceed $2,000,000 for a related series of violations. We have reviewed the circumstances
and supporting documents involved in this case, and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct the
item(s) identified in this letter. Failure to do so will result in Sunoco Pipeline L.P. being subject
to additional enforcement action.
Be advised that all material you submit in response to this enforcement action is subject to being
made publicly available. If you believe that any portion of your responsive material qualifies for
confidential treatment under 5 U.S.C. 552(b), along with the complete original document you must
provide a second copy of the document with the portions you believe qualify for confidential
treatment redacted and an explanation of why you believe the redacted information qualifies for
confidential treatment under 5 U.S.C. 552(b).
No reply to this letter is required. If you choose to reply, please submit all correspondence in this
matter to Robert Burrough, Director, PHMSA Eastern Region, 840 Bear Tavern Road, Suite 300,
120195014W_Warning Letter_12122019_text Page 2 of 3



West Trenton, NJ 08628. Please refer to CPF 1-2019-5014W on each document you submit, and
whenever possible provide a signed PDF copy in electronic format. Smaller files may be emailed
to robert.burrough@dot.gov. Larger files should be sent on USB flash drive accompanied by the
original paper copy to the Eastern Region Office.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
120195014W_Warning Letter_12122019_text Page 3 of 3

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/120195014W>
- Source ID: `phmsa-enforcement`
- SHA-256: `ccaa224335365849d4142f3cecc8deae1b66c0bebac48a54f5ff61418d053ba9`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T16:48:11.999Z
- Document slug: `phmsa-enforcement-120195014w`

### Source metadata

```json
{
  "cpf": "120195014W",
  "operator": "SUNOCO PIPELINE L.P.",
  "region": "Eastern",
  "pipelineType": "INTERSTATE LIQUID ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "195.432(b)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 3,
  "attachments": [
    {
      "name": "120195014W_Operator Response to Notice_12162019.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120195014W/120195014W_Operator%20Response%20to%20Notice_12162019.pdf",
      "bytes": 369776,
      "category": "party_submission"
    },
    {
      "name": "120195014W_Warning Letter_12122019.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120195014W/120195014W_Warning%20Letter_12122019.pdf",
      "bytes": 3453073,
      "category": "agency_document"
    },
    {
      "name": "120195014W_Warning Letter_12122019_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/120195014W/120195014W_Warning%20Letter_12122019_text.pdf",
      "bytes": 125477,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "SUNOCO PIPELINE L.P."
}
```