# UGI ENERGY SERVICES — Notice of Amendment

**Citation:** CPF 12021017NOA  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2021-04-19

CLOSED notice of amendment citing 193.2503(c), 193.2509(b)(3), 193.2509(b)(4), 193.2605(b)(1), 193.2605(b)(2).

## Document text

Notice of Amendment involving UGI ENERGY SERVICES. PHMSA's enforcement data identifies the cited regulations as 193.2503(c),  193.2509(b)(3),  193.2509(b)(4),  193.2605(b)(1),  193.2605(b)(2). The case was opened on 2021-04-19 and is reported as closed as of 2022-05-03. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

12021017NOA_Closure Letter_05032022_(20-172065).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Closure%20Letter_05032022_(20-172065).pdf

12021017NOA_Closure Letter_05032022_(20-172065)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Closure%20Letter_05032022_(20-172065)_text.pdf

12021017NOA_Notice of Amendment_04192021_(20-172065).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Notice%20of%20Amendment_04192021_(20-172065).pdf

12021017NOA_Notice of Amendment_04192021_(20-172065)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Notice%20of%20Amendment_04192021_(20-172065)_text.pdf

12021017NOA_Operator Response to Notice_05192021_(20-172065).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Operator%20Response%20to%20Notice_05192021_(20-172065).pdf

12021017NOA_Order Directing Amendment_03112022_(20-172065).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Order%20Directing%20Amendment_03112022_(20-172065).pdf

12021017NOA_Order Directing Amendment_03112022_(20-172065)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Order%20Directing%20Amendment_03112022_(20-172065)_text.pdf

12021017NOA_Notice of Amendment_04192021_(20-172065)_text.pdf

NOTICE OF AMENDMENT
VIA ELECTRONIC MAIL TO: jhartz@ugies.com
April 19, 2021
Mr. Joseph Hartz
Vice President Asset Management
UGI Energy Services
1 Meridian Blvd
Wyomissing, PA 19610
CPF 1-2021-017-NOA
Dear Mr. Hartz:
From November 9, 2020 to November 18, 2020, a representative of the Pipeline and Hazardous
Materials Safety Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code
(U.S.C.) inspected UGI Energy Services’ (UGI) procedures and records for the Temple LNG Plant
in Reading, Pennsylvania.
On the basis of the inspection, PHMSA has identified the apparent inadequacies found within
UGI’s plans or procedures, as described below:
1. § 193.2503 Operating procedures.
Each operator shall follow one or more manuals of written
procedures to provide safety in normal operation and in responding to
an abnormal operation that would affect safety. The procedures must
include provisions for:
(a) …
(c) Recognizing abnormal operating conditions.
UGI’s operating procedures were inadequate. Specifically, UGI’s Temple 1- LNG Maintenance
Manual, revised 7/15/20 and LNG Liquefaction System Manual (collectively, Operating
Procedures) failed to include details for recognizing and responding to abnormal operating
conditions (AOCs).
During the inspection, the PHMSA inspector requested UGI’s procedures regarding abnormal
operating conditions, and UGI provided its Operating Procedures. However, the Operating
Procedures did not provide adequate guidance on how UGI personnel working outside of the
control room recognize and respond to AOCs, nor do they define or list AOCs that may exist at its



CPF 1-2021-017-NOA
LNG plant.
When the PHMSA inspector requested if there were additional procedures or guidance related to
recognizing AOCs, UGI stated there was no further procedures.
Therefore, UGI failed to include details in its manuals of written procedures for recognizing AOCs
in accordance with § 193.2503(c). UGI must revise its procedures to include provisions for
recognizing AOCs.
2. § 193.2509 Emergency procedures.
(a) …
(b) To adequately handle each type of emergency identified under
paragraph (a) of this section and each fire emergency, each operator
must follow one or more manuals of written procedures. The
procedures must provide for the following:
(1) Coordinating with appropriate local officials in preparation of
an emergency evacuation plan, which sets forth the steps required to
protect the public in the event of an emergency, including catastrophic
failure of an LNG storage tank.
UGI’s emergency procedures were inadequate. Specifically, UGI’s LNG Emergency Procedures
Manual and Asset Emergency Response Plan, revised 10/01/20 failed to provide details for
coordinating with appropriate local officials in preparation of an emergency evacuation plan,
which sets forth the steps required to protect the public in the event of an emergency, including
catastrophic failure of an LNG storage tank.
During the inspection, the PHMSA inspector requested UGI’s procedures regarding coordination
with local officials in preparation of an emergency evacuation plan. UGI provided its Emergency
Procedures Manual and Asset Emergency Response Plan related to emergency types/actions and
pointed to the following sections of their manuals, which failed to demonstrate compliance.
The Asset Emergency Response Plan, revised 10/01/20, Page 5, stated in part, “The purpose of this
Emergency Response Plan (ERP) is to provide consistent policies and procedures to manage an
emergency effectively. This plan will assist in protecting the lives and health of the public and
UGI Energy Services (UGIES) employees. This plan will provide guidance to protect and
minimize damage to company property in the event of an emergency and provide protective
measures to ensure minimal impact to the surrounding community during an emergency.”
The LNG Emergency Procedures Manual Section 2.4 stated in part, “UGI supervisory personnel
shall coordinate with local officials keeping them advised of the location of the plant fire control
equipment, the potential hazards at the plant, and the status of each emergency.”
These written procedures did not provide specific details for coordinating with appropriate local
officials in preparing emergency evacuation plans, nor did it discuss contents of emergency
evaluation plans to include steps required to protect the public in the event of an emergency,
including catastrophic failure of an LNG storage tank.
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 2 of 10



CPF 1-2021-017-NOA
When the PHMSA inspector requested if there were additional procedures or guidance related to
coordination with local officials in preparation of emergency evacuation plans, UGI did not
provide any additional information or response.
Therefore, UGI failed to provide details for coordinating with appropriate local officials in
preparation of an emergency evacuation plan in accordance with § 193.2509(b)(3). UGI must
revise its LNG Emergency Procedures Manual and Asset Emergency Response Plan to address
this requirement.
3. § 193.2509 Emergency procedures.
(a) …
(b) To adequately handle each type of emergency identified under
paragraph (a) of this section and each fire emergency, each operator
must follow one or more manuals of written procedures. The
procedures must provide for the following:
(1) …
(4) Cooperating with appropriate local officials in evacuations and
emergencies requiring mutual assistance…
UGI’s emergency procedures were inadequate. Specifically, UGI’s LNG Emergency Procedures
Manual failed to require cooperating with appropriate local officials in evacuations and
emergencies requiring mutual assistance.
During the inspection, the PHMSA inspector requested UGI’s procedures addressing
§ 193.2509(b)(4), and UGI provided its Emergency Procedures Manual. The Emergency
Procedures Manual stated in Section 2.4, “UGI supervisory personnel shall coordinate with local
officials keeping them advised of the location of the plant fire control equipment, the potential
hazards at the plant, and the status of each emergency.”
However, the written procedure did not provide any details or guidance related to the cooperation
with local officials in evacuations and emergencies requiring mutual assistance. The Emergency
Procedures Manual also failed to define or mention any activity or requirement related to
providing mutual assistance.
When the PHMSA inspector asked UGI if there were further written procedures regarding mutual
assistance, UGI stated there were no specific requirements in their procedures on mutual assistance
events during evacuations and emergencies.
Therefore, UGI failed to have emergency procedures which require cooperating with appropriate
local officials in evacuations and emergencies requiring mutual assistance in accordance with
§ 193.2509(b)(4). UGI must revise its Emergency Procedures Manual to include details
addressing this requirement.
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 3 of 10



CPF 1-2021-017-NOA
4. § 193.2605 Maintenance procedures.
(a) …
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any
required corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under
paragraph (a) of this section and their frequency of performance;
and…
UGI’s maintenance procedures were inadequate. Specifically, UGI’s LNG Truck Transfer System
Manual, dated 7/10/19 and Temple 1-LNG Maintenance Manual, dated 7/15/20 (collectively,
Transfer Hose Procedures) failed to provide details regarding testing of transfer hoses once each
calendar year, but with intervals not exceeding 15 months, to the maximum pump pressure or relief
valve setting in accordance with § 193.2621(a).
Section 193.2621(a) states:
Hoses used in LNG or flammable refrigerant transfer systems must be:
(a) Tested once each calendar year, but with intervals not exceeding 15 months, to the
maximum pump pressure or relief valve setting;
During the inspection, the PHMSA inspector requested UGI’s procedure regarding testing and
inspection of transfer hoses. UGI provided its Transfer Hose Procedures related to Temple I, as
this is the only area with a truck transfer system. The Temple 1-LNG Maintenance Manual, dated
7/15/20, Sections 2.E. Trucking System and 2.F. Truck Rack Expansion System included a
requirement for a truck transfer hose pressure test to be performed at a 12-month frequency.
However, the Transfer Hose Procedures did not provide a procedure requiring that each transfer
hose must be tested to the maximum pump pressure or relief valve setting, or any details on how
the truck transfer hose pressure test is performed.
When the PHMSA inspector requested additional information related to testing of transfer hoses,
UGI did not provide any additional information or response.
Therefore, UGI failed to include details in its written procedures that transfer hoses must be tested
once each calendar year, but with intervals not exceeding 15 months, to the maximum pump
pressure or relief valve setting in accordance with § 193.2621(a), as required by §193.2605(b).
UGI must revise its Transfer Hose Procedures to include a detailed procedure for testing transfer
hoses in accordance with § 193.2621(a).
5. § 193.2605 Maintenance procedures.
(a) …
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any
required corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under
paragraph (a) of this section and their frequency of performance;
and…
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 4 of 10



CPF 1-2021-017-NOA
UGI’s maintenance procedures were inadequate. Specifically, UGI’s Temple 1-LNG Maintenance
Manual, dated 7/15/20 and Temple II Tank and Sendout System Operations Manual, dated
10/17/19 failed to address how it monitors for internal corrosion in accordance with the
requirements of § 193.2635(e).
Section 193.2635(e) states:
Corrosion protection provided as required by this subpart must be periodically monitored to
give early recognition of ineffective corrosion protection, including the following, as
applicable:
…
(e) If a component is protected from internal corrosion, monitoring devices designed to
detect internal corrosion, such as coupons or probes, must be located where corrosion is most
likely to occur. However, monitoring is not required for corrosion resistant materials if the
operator can demonstrate that the component will not be adversely affected by internal
corrosion during its service life. Internal corrosion control monitoring devices must be
checked at least two times each calendar year, but with intervals not exceeding 7 1/2 months.
During the inspection, the PHMSA inspector requested UGI’s procedure regarding internal
corrosion monitoring. UGI provided its Temple 1-LNG Maintenance Manual and Temple II
Tank and Sendout System Operations Manual.
The Temple 1-LNG Maintenance Manual, procedure MP-45 Corrosion Protection, stated in part,
“Per CFR Part 193.2636, WEG1 sampling and testing is to be conducted on a 6-month interval
and not to exceed 7-months” …and that the protection systems are the “Corrosion inhibitors
contained within WEG and lube oil fluid.”
The Temple 1-LNG Maintenance Manual, however, referenced a non-existent code citation from
CFR Part 193.
The Temple II Tank and Sendout System Operations Manual, procedure MP-1110 stated in part,
“The WEG should be checked on an annual basis for the following attributes
% glycol, PH, Corrosion inhibitor…”
The Temple 1-LNG Maintenance Manual, dated 7/15/20 and Temple II Tank and Sendout System
Operations Manual, dated 10/17/19 failed to mention which components are subject to internal
corrosive attack and how they are protected from internal corrosion. Additionally, the Procedures
failed to describe UGI’s internal corrosion monitoring device requirements, including details such
as where they are required or if any protected components utilizing corrosion resistant materials
are excepted from monitoring.
When the PHMSA inspector asked for additional information regarding internal corrosion
monitoring, UGI stated the CFR reference was outdated, however the WEG testing is conducted.
Therefore, UGI failed to include details in its written Procedures for Temple I and Temple II
regarding internal corrosion monitoring in accordance with § 193.2635(e), as required by
1 Water-Ethylene Glycol
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 5 of 10



CPF 1-2021-017-NOA
§ 193.2605(b). UGI must revise its procedures to address § 193.2635(e).
6. § 193.2605 Maintenance procedures.
(a) …
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any
required corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under
paragraph (a) of this section and their frequency of performance;
and…
UGI’s maintenance procedures were inadequate. Specifically, UGI’s Temple 1-LNG Maintenance
Manual, dated 7/15/20 and Temple II Tank and Sendout System Operations Manual, dated
10/17/19 failed to provide adequate guidance requiring each auxiliary power source to be tested
annually for capacity in accordance with § 193.2613.
Section 193.2613 states:
Each auxiliary power source must be tested monthly to check its operational capability and
tested annually for capacity. The capacity test must take into account the power needed to
start up and simultaneously operate equipment that would have to be served by that power
source in an emergency.
During the inspection, the PHMSA inspector requested UGI’s procedure regarding auxiliary
power sources. The Temple 1-LNG Maintenance Manual Procedure stated in part (emphasis
added):
The Temple I facility’s temporary auxiliary power source is provided by a CUMMINS 500
DFEK SPEC F, diesel fueled generator. The generator has a load capacity of 500KW for the
facility’s 480 VAC service. Load is transferred to the generator by way of an automatic transfer
switch.
Frequency: Operational Test – Monthly
Capacity Load Test – Annually
…
B. Capacity Load Test
Note: The following procedure only needs to be performed if a commercial power outage
has not occurred in the prior 12-months.
Similarly, the Temple II Tank and Sendout System Operations Manual Procedure Section 15.51
stated in part (emphasis added):
General: The Temple II facility’s standby power source is provided by Kawasaki GPS4000
natural gas turbine generator. The generator has a load capacity of 3.2MW for the facility’s
4160V service.
Frequency:
Operational Test – Monthly
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 6 of 10



CPF 1-2021-017-NOA
Capacity Load Test – Annually
…
C. Capacity Load Test
Note: The following procedure only needs to be performed if a commercial power outage
requiring the generator’s operation has not occurred in the prior 12-months.
The Auxiliary Power Procedures did not provide an adequate process that ensures that each
auxiliary power source is tested annually for capacity, with the capacity test taking into account
the power needed to start up and simultaneously operate equipment that would have to be served
by that power source in an emergency. A commercial power outage resulting in the generator’s
operation may not provide an adequate test of the capacity of the power source as described in
§ 193.2613.
Therefore, UGI failed to include adequate details in its written maintenance procedures that each
auxiliary power source is to be tested annually for capacity in accordance with § 193.2613, as
required by § 193.2605(b). UGI must revise its procedures to require annual capacity testing of
auxiliary power sources, and for the capacity testing to account for the specific requirements of
§ 193.2613.
7. § 193.2605 Maintenance procedures.
(a) …
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any
required corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under
paragraph (a) of this section and their frequency of performance;
and…
UGI’s maintenance procedures were inadequate. Specifically, UGI’s Temple II Tank and Sendout
System Operations Manual, dated 10/17/19 failed to provide details regarding fire protection
inspection frequencies for Temple II facilities, in accordance with § 193.2619(c)(2).
Section 193.2619(c)(2) states:
(c) Control systems in service, but not normally in operation, such as
relief valves and automatic shutdown devices, and control systems for
internal shutoff valves for bottom penetration tanks must be inspected and
tested once each calendar year, not exceeding 15 months, with the following
exceptions:
(2) Control systems that are intended for fire protection must be
inspected and tested at regular intervals not to exceed 6 months.
During the inspection, the PHMSA inspector requested UGI’s procedure regarding control systems
meeting the requirements of § 193.2619(c)(2). UGI provided its procedures regarding control
systems for Temple II facilities.
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 7 of 10



CPF 1-2021-017-NOA
The Temple II Tank and Sendout System Operations Manual, Procedure MP-1055 Fire
Detection/Fire Protection Test and Inspection, included a process for testing its Detronics fire
detection system. However, these procedures did not provide any details or guidance requiring
that control systems intended for fire protection must be inspected and tested at regular intervals
not to exceed 6 months. When the PHMSA inspector asked if this information was contained in
any UGI procedures, UGI provided Table 15.2.3 Temple II Sendout System Maintenance.
However, this document was not incorporated or referenced in any UGI Procedures, nor did it
appear to address inspection frequencies for all control systems intended for fire protection.
Therefore, UGI failed to include details in its written procedures for Temple II facilities that control
systems intended for fire protection must be inspected and tested at regular intervals not to exceed
6 months in accordance with § 193.2619(c)(2), as required by § 193.2605(b). UGI must revise its
procedures to provide details for fire protection control system inspection frequencies for its
Temple II facilities.
8. § 193.2605 Maintenance procedures.
(a) …
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any
required corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under
paragraph (a) of this section and their frequency of performance;
and…
UGI’s maintenance procedures were inadequate. Specifically, UGI’s Temple 1-LNG Maintenance
Manual, dated 7/15/20 and Temple II Tank and Sendout Systems Operations Manual, dated
10/17/19 failed to provide details on inspecting LNG storage tank Temple T-II in accordance with
§ 193.2623.
Section 193.2623 states:
Each LNG storage tank must be inspected or tested to verify that each of the following
conditions does not impair the structural integrity or safety of the tank:
(a) Foundation and tank movement during normal operation and after a major meteorological
or geophysical disturbance.
(b) Inner tank leakage.
(c) Effectiveness of insulation.
(d) Frost heave.
During the inspection, the PHMSA inspector requested UGI’s procedure regarding inspecting
LNG storage tanks. UGI provided the written Tank Procedures related to Temple I and Temple II
LNG storage tanks.
The Temple II Tank and Sendout Systems Operations Manual, Section 15.1, General stated in part,
“In addition to the normal maintenance procedure, all LNG personnel shall note and report in
writing: Any abnormal ground movements that might impair the structural integrity, or reliability
the LNG-tank or plant piping systems.
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 8 of 10



CPF 1-2021-017-NOA
-Any malfunction that exposes process piping or vessels or the LNG-tank to an
overpressure condition (beyond maximum operating pressure plus allowable build-up).
-Any leak of gas or LNG from piping or vessels.
-Any condition such as inner-tank leakage, ineffective insulation, or frost heave that
impairs the structural integrity of the LNG tank.”
However, the Procedures did not provide any details or guidance on how UGI inspects or tests
Temple Tank T-II for inner tank leakage, effectiveness of insulation and frost heave.
When the PHMSA inspector asked UGI about the related Procedure, UGI stated that there are no
processes or procedures for these inspections or tests because it is a concrete walled tank.
However, Section 193.2623 does not provide exception for concrete walled tanks.
Therefore, UGI failed to include details in its written procedures on inspecting or testing LNG
storage tank Temple T-II, as required by § 193.2605(b). UGI must revise its procedures to include
a process for inspecting or testing Temple T-II in accordance with § 193.2623.
9. § 193.2605 Maintenance procedures.
(a) …
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any
required corrosion control. The procedure must include:
(1) …
(2) A description of other actions necessary to maintain the LNG
plant according to the requirements of this subpart.
UGI’s maintenance procedures were inadequate. Specifically, UGI’s Temple 1-LNG Maintenance
Manual, dated 7/15/20 failed to include details that the LNG plant grounds must be free from
rubbish, debris, and other material which present a fire hazard in accordance with § 193.2607(b).
Section 193.2607(b) states:
LNG plant grounds must be free from rubbish, debris, and other material which present a
fire hazard. Grass areas on the LNG plant grounds must be maintained in a manner that does
not present a fire hazard.
During the inspection, the PHMSA inspector requested UGI’s procedures regarding their process
to maintain the facility to be free from the presence of foreign material and debris. UGI provided
its Temple 1-LNG Maintenance Manual, dated 7/15/20, which failed to indicate any such
requirement.
When the PHMSA inspector requested if there were additional procedures or guidance related to
maintaining the facility free from the presence of foreign material and debris, UGI did not provide
any additional information or response.
Therefore, UGI failed to include details in its written procedures that the LNG plant grounds must
be free from rubbish, debris, and other material which present a fire hazard in accordance with
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 9 of 10



CPF 1-2021-017-NOA
§ 193.2607(b), as required by §193.2605(b). UGI must revise its procedures to address this
requirement.
Response to this Notice
This Notice is provided pursuant to 49 U.S.C. § 60108(a) and 49 C.F.R. § 190.206. Enclosed as
part of this Notice is a document entitled Response Options for Pipeline Operators in Enforcement
Proceedings.
Please refer to this document and note the response options. Be advised that all material you submit
in response to this enforcement action is subject to being made publicly available. If you believe
that any portion of your responsive material qualifies for confidential treatment under 5 U.S.C.
552(b), along with the complete original document you must provide a second copy of the
document with the portions you believe qualify for confidential treatment redacted and an
explanation of why you believe the redacted information qualifies for confidential treatment under
5 U.S.C. 552(b).
Following the receipt of this Notice, you have 30 days to submit written comments, revised
procedures, or a request for a hearing under §190.211. If you do not respond within 30 days of
receipt of this Notice, this constitutes a waiver of your right to contest the allegations in this Notice
and authorizes the Associate Administrator for Pipeline Safety to find facts as alleged in this Notice
without further notice to you and to issue an Order Directing Amendment. If your plans or
procedures are found inadequate as alleged in this Notice, you may be ordered to amend your plans
or procedures to correct the inadequacies (49 C.F.R. § 190.206). If you are not contesting this
Notice, we propose that you submit your amended procedures to my office within 30 days of
receipt of this Notice. This period may be extended by written request for good cause. Once the
inadequacies identified herein have been addressed in your amended procedures, this enforcement
action will be closed.
It is requested (not mandated) that UGI Energy Services maintain documentation of the safety
improvement costs associated with fulfilling this Notice of Amendment (preparation/revision of
plans, procedures) and submit the total to Robert Burrough, Director, PHMSA Eastern Region,
840 Bear Tavern Road, Suite 300, West Trenton, NJ 08628. In correspondence concerning this
matter, please refer to CPF 1-2021-017-NOA and, for each document you submit, please provide
a copy in electronic format whenever possible. Smaller files may be emailed to
robert.burrough@dot.gov. Larger files should be sent on USB flash drive accompanied by the
original paper copy to the Eastern Region Office.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
Enclosure: Response Options for Pipeline Operators in Enforcement Proceedings
12021017NOA_Notice of Amendment_04192021_(20-172065)_text Page 10 of 10

12021017NOA_Closure Letter_05032022_(20-172065)_text.pdf

OVERNIGHT EXPRESS DELIVERY
May 3, 2022
Mr. Dante D’ Alessandro
Vice President – Engineering and Operations
UGI Energy Services
1 Meridian Boulevard
Wyomissing, PA 19610
CPF 1-2021-017-NOA
Dear Mr. D’Alessandro:
From November 9, 2020 to November 18, 2020, a representative of the Pipeline and Hazardous
Materials Safety Administration (PHMSA), Office of Pipeline Safety (OPS), pursuant to Chapter
601 of 49 United States Code (U.S.C.) inspected UGI Energy Services’ (UGI) procedures for the
Temple LNG Plant in Reading, Pennsylvania. As a result of the inspection, UGI was issued a
Notice of Amendment (NOA) on April 19, 2021, which proposed amendment of your procedures.
On August 6, 2021 UGI submitted its amended procedures for items 2 – 9, only. On March 11,
2022, PHMSA issued an Ordering Directing Amendment (Order) to UGI requiring UGI to amend
certain portions of its procedures. On April 18, 2022 UGI provided its response to the Order. My
staff reviewed the amended procedures, and it appears that the inadequacies outlined in this Order
have been corrected.
This letter is to inform you no further action is necessary and this case is now closed. Thank you
for your cooperation.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration

12021017NOA_Order Directing Amendment_03112022_(20-172065)_text.pdf

March 11, 2022
VIA ELECTRONIC MAIL TO: ddalessandro@ugies.com
Mr. Dante D’Alessandro
Vice President – Engineering and Operations
UGI Energy Services
1 Meridian Boulevard
Wyomissing, Pennsylvania 19610
Re: CPF No. 1-2021-017-NOA
Dear Mr. D’Alessandro:
Enclosed please find the Order Directing Amendment issued in the above-referenced case to
UGI Energy Services, LLC (UGIES). It makes findings of inadequate procedures, finds that
certain amended procedures provided by UGIES are adequate, and requires UGIES to amend
certain portions of its procedures for the Temple LNG Plant in Reading, Pennsylvania. When
the amendment of procedures has been completed, as determined by the Director, Eastern
Region, this enforcement action will be closed. Service of the Order by email is complete upon
transmission and acknowledgement of receipt, as provided under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Alan K. Mayberry
Associate Administrator
for Pipeline Safety
Enclosure
cc: Mr. Robert Burrough, Director, Eastern Region, Office of Pipeline Safety, PHMSA
Mr. Jeremy Kuhn, Manager, Pipeline Engineering & Compliance, UGIES,
jkuhn@ugies.com
CONFIRMATION OF RECEIPT REQUESTED



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
____________________________________
In the Matter of )
UGI Energy Services, LLC, ) CPF No. 1-2021-017-NOA
)
)
)
Respondent. )
____________________________________)
ORDER DIRECTING AMENDMENT
From November 9, 2020 to November 18, 2020, a representative of the Pipeline and Hazardous
Materials Safety Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code
(U.S.C.) inspected UGI Energy Services, LLC’s (UGIES or Respondent) procedures and records
for the Temple LNG Plant in Reading, Pennsylvania.
As a result of the inspection, the Director, Eastern Region, OPS, issued to Respondent, by letter
dated April 19, 2021, a Notice of Amendment (Notice). In accordance with 49 C.F.R. § 190.206,
the Notice proposed finding that certain of UGIES’s plans and procedures were inadequate to
assure safe operation and proposed that Respondent amend its procedures for operations,
maintenance, and emergencies.
UGIES responded to the Notice by letter dated May 19, 2021 (Response). In its Response,
UGIES contested Item 1 of the Notice, but did not contest the remaining eight items. On August
6, 2021, UGIES provided amended procedures in response to Item 2 through 9 of the Notice for
review and approval by the Director, Eastern Region. The company did not request a hearing
and therefore waived its right to one.
FINDING OF INADEQUATE PROCEDURES
Item 1: The Notice alleged that Respondent’s procedures were inadequate with regard to
49 C.F.R. § 193.2503(c), which states:
§ 193.2503 Operating procedures.
Each operator shall follow one or more manuals of written procedures
to provide safety in normal operation and in responding to an abnormal
operation that would affect safety. The procedures must include provisions
for:
(a) . . . .
(c) Recognizing abnormal operating conditions.



CPF No. 1-2021-017-NOA
Page 2
The Notice alleged that UGIES’s operating procedures were inadequate for recognizing and
responding to abnormal operating conditions (AOCs) with regard to § 193.2503(c). Specifically,
the Notice alleged the company’s procedures failed to provide adequate guidance on how UGIES
personnel working outside of the control room were to recognize and respond to AOCs.
In its Response, UGIES contested this allegation of inadequacy. Specifically, UGIES stated that
its written alarm monitoring and response procedures discuss possible AOC scenarios for various
associated systems as well as resolutions to the AOCs identified. Further, UGIES points to
subsections in its alarm monitoring procedures that discuss how to handle AOCs when personnel
are outside of the control room. Based on those references, UGIES argued that its procedures are
adequate for safety and satisfy the applicable regulatory requirements.
Having reviewed UGIES procedure titled “Remote Alarm Monitoring” (Procedure), I find that it
lacks sufficient detail to assure safe operation with regard to § 193.2503(c). While the Procedure
did include references to how personnel are to respond to certain alarms, it lacked adequate detail
to clarify how operator personnel are to recognize and respond to all AOCs that would affect
safety. Specifically, the Procedure failed to establish the specific types of alarms received by the
remote alarm monitoring system (for example, does the remote alarm monitoring system receive
all the alarms the control center receives or only certain ones), how the Gas Operations
Supervisor (GSOS) conducting the monitoring should contact appropriate personnel if they are
unable to contact the LNG Technician on-call, and how the remote alarm incidents are
documented. Further, the Procedure did not specify under what alarm scenarios the LNG
Technician should instruct the GSOS to conduct emergency shutdown (ESD). Additionally, the
procedures fail to specify whether other measures must be in place to respond to the AOC when
initiating ESD is not appropriate.
Accordingly, based upon a review of all the evidence, I find that Respondent’s Procedure was
inadequate, as alleged in the Notice, and revisions are required to include the additional
information and clarifications referenced above in order to assure safety with regard to
§ 193.2503(c).
Item 2: The Notice alleged that Respondent’s procedures were inadequate with regard to
49 C.F.R. § 193.2509(b)(3), which states:
§ 193.2509 Emergency procedures.
(a) . . . .
(b) To adequately handle each type of emergency identified under
paragraph (a) of this section and each fire emergency, each operator must
follow one or more manuals of written procedures. The procedures must
provide for the following:
(3) Coordinating with appropriate local officials in preparation of an
emergency evacuation plan, which sets forth the steps required to protect
the public in the event of an emergency, including catastrophic failure of an
LNG storage tank.
The Notice alleged that UGIES’s emergency procedures were inadequate with regard to



CPF No. 1-2021-017-NOA
Page 3
§ 193.2509(b)(3).1 In its Response, UGIES provided its amendments. The Director, Eastern
Region, reviewed the amended procedure and concluded that the inadequacies had been corrected.
Accordingly, based upon a review of all the evidence, I find that Respondent’s procedures were
inadequate, as alleged in the Notice, but have subsequently been adequately modified. Therefore,
no further action is necessary with regard to this Item.
Item 3: The Notice alleged that Respondent’s operations and maintenance procedures were
inadequate with regard to 49 C.F.R. § 193.2509(b)(4), which states:
§ 193.2509 Emergency procedures.
(a) . . . .
(b) To adequately handle each type of emergency identified under
paragraph (a) of this section and each fire emergency, each operator must
follow one or more manuals of written procedures. The procedures must
provide for the following:
(1) . . . .
(4) Cooperating with appropriate local officials in evacuations and
emergencies requiring mutual assistance and keeping those officials advised
of:
The Notice alleged that UGIES’s emergency procedures were inadequate with regard to
§ 193.2509(b)(4). In its Response, UGIES provided its amendments. The Director, Eastern
Region, reviewed the amended procedure and concluded that the inadequacies had been corrected.
Accordingly, based upon a review of all the evidence, I find that Respondent’s procedures were
inadequate, as alleged in the Notice, but have subsequently been adequately modified. Therefore,
no further action is necessary with regard to this Item.
Items 4 through 7: The Notice alleged that Respondent’s operations and maintenance
procedures were inadequate with regard to 49 C.F.R. § 193.2605(b)(1), which states:
§ 193.2605 Maintenance procedures.
(a) . . . .
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any required
corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under paragraph
(a) of this section and their frequency of performance; and
The Notice alleged that UGIES’s emergency procedures were inadequate with regard to
§ 193.2605(b)(1). In its Response, UGIES provided its amendments. The Director, Eastern
Region, reviewed the amended procedure and concluded that the inadequacies had been corrected.
1 It appears the Notice contained a typographical error and cited this regulation as § 193.2509(b)(1).



CPF No. 1-2021-017-NOA
Page 4
Accordingly, based upon a review of all the evidence, I find that Respondent’s procedures were
inadequate, as alleged in the Notice, but have subsequently been adequately modified. Therefore,
no further action is necessary with regard to these Items.
Item 8: The Notice alleged that Respondent’s operations and maintenance procedures were
inadequate with regard to 49 C.F.R. § 193.2605(b)(1), which states:
§ 193.2605 Maintenance procedures.
(a) . . . .
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any required
corrosion control. The procedure must include:
(1) The details of the inspections or tests determined under paragraph
(a) of this section and their frequency of performance; and
The Notice alleged that UGIES’s emergency procedures were inadequate with regard to
§ 193.2605(b)(1). In its Response, UGIES did not contest the allegation and provided its
amendments. The Director, Eastern Region, reviewed the amended procedures and found certain
inadequacies still remain. Although the amendments clarified the temperature monitoring
system and added a visual inspection of the outer tank if an alarm sounds, they did not contain
adequate detail regarding the visual inspection requirement. In particular, the amended
procedures state that a visual inspection shall be performed if an alarm is received, but do not
describe the process for conducting and documenting these inspections. The amended
procedures also do not include a requirement that a visual inspection of the outer tank be
conducted within a specified interval of time if an alarm is not received. The procedures did not
include a process for responding to issues discovered during a visual inspection. In addition, the
procedures did not include requirements that temperature transmitter calibration and testing be
conducted at a specified frequency and documented.
Accordingly, based upon a review of all the evidence, I find that Respondent’s emergency
procedures were inadequate, as alleged in the Notice, and revisions are required to include the
additional information and clarifications referenced above in order to assure safety with regard to
§ 193.2605(b)(1).
Item 9: The Notice alleged that Respondent’s operations and maintenance procedures were
inadequate with regard to 49 C.F.R. § 193.2605(b)(2), which states:
§ 193.2605 Maintenance procedures.
(a) . . . .
(b) Each operator shall follow one or more manuals of written
procedures for the maintenance of each component, including any required
corrosion control. The procedure must include:
(2) A description of other actions necessary to maintain the LNG plant
according to the requirements of this subpart.
The Notice alleged that UGIES’s emergency procedures were inadequate with regard to



CPF No. 1-2021-017-NOA
Page 5
§ 193.2605(b)(2). In its Response, UGIES provided its amendments. The Director, Eastern
Region, reviewed the amended procedure and concluded that the inadequacies had been corrected.
Accordingly, based upon a review of all the evidence, I find that Respondent’s procedures were
inadequate, as alleged in the Notice, but have subsequently been adequately modified. Therefore,
no further action is necessary with regard to this Item.
Pursuant to 49 U.S.C. § 60108(a) and 49 C.F.R. § 190.206, UGIES is ordered to revise its
procedures as specified in Items 1 and 8 above. Respondent must submit the amended
procedures to the Director, Eastern Region, within 30 days following receipt of this Order.
The Director may grant an extension of time to comply with any of the required items upon a
written request timely submitted by the Respondent and demonstrating good cause for an
extension. Failure to comply with this Order may result in the administrative assessment of civil
penalties not to exceed $200,000, as adjusted for inflation (49 C.F.R. § 190.223), for each
violation for each day the violation continues or in referral to the Attorney General for
appropriate relief in a district court of the United States.
Under 49 C.F.R. § 190.243, Respondent may submit a Petition for Reconsideration of this Order
Directing Amendment to the Associate Administrator, Office of Pipeline Safety, PHMSA, 1200
New Jersey Avenue, SE, East Building, 2nd Floor, Washington, DC 20590, with a copy sent to
the Office of Chief Counsel, PHMSA, at the same address, no later than 20 days after receipt of
this Order Directing Amendment by Respondent. Any petition submitted must contain a
statement of the issue(s) and meet all other requirements of 49 C.F.R. § 190.243. The terms of
the order, including required amendment to procedures, remain in effect unless the Associate
Administrator, upon request, grants a stay.
The terms and conditions of this Order Directing Amendment are effective upon service in
accordance with 49 C.F.R. § 190.5.
March 11, 2022
___________________________________ __________________________
Alan K. Mayberry Date Issued
Associate Administrator
for Pipeline Safety

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/12021017NOA>
- Source ID: `phmsa-enforcement`
- SHA-256: `e471bead069f1fc079906a0c772eda08e0fcd9b081cada96aeb6dd16432d8942`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-23T16:21:22.598Z
- Document slug: `phmsa-enforcement-12021017noa`

### Source metadata

```json
{
  "cpf": "12021017NOA",
  "operator": "UGI ENERGY SERVICES",
  "region": "Eastern",
  "pipelineType": "INTERSTATE LNG",
  "caseStatus": "CLOSED",
  "citedSections": [
    "193.2503(c)",
    "193.2509(b)(3)",
    "193.2509(b)(4)",
    "193.2605(b)(1)",
    "193.2605(b)(2)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 7,
  "attachments": [
    {
      "name": "12021017NOA_Closure Letter_05032022_(20-172065).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Closure%20Letter_05032022_(20-172065).pdf",
      "bytes": 396075,
      "category": "agency_document"
    },
    {
      "name": "12021017NOA_Closure Letter_05032022_(20-172065)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Closure%20Letter_05032022_(20-172065)_text.pdf",
      "bytes": 79732,
      "category": "agency_document"
    },
    {
      "name": "12021017NOA_Notice of Amendment_04192021_(20-172065).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Notice%20of%20Amendment_04192021_(20-172065).pdf",
      "bytes": 287159,
      "category": "agency_document"
    },
    {
      "name": "12021017NOA_Notice of Amendment_04192021_(20-172065)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Notice%20of%20Amendment_04192021_(20-172065)_text.pdf",
      "bytes": 186326,
      "category": "agency_document"
    },
    {
      "name": "12021017NOA_Operator Response to Notice_05192021_(20-172065).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Operator%20Response%20to%20Notice_05192021_(20-172065).pdf",
      "bytes": 884022,
      "category": "party_submission"
    },
    {
      "name": "12021017NOA_Order Directing Amendment_03112022_(20-172065).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Order%20Directing%20Amendment_03112022_(20-172065).pdf",
      "bytes": 295814,
      "category": "agency_document"
    },
    {
      "name": "12021017NOA_Order Directing Amendment_03112022_(20-172065)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021017NOA/12021017NOA_Order%20Directing%20Amendment_03112022_(20-172065)_text.pdf",
      "bytes": 124983,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 3,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "UGI ENERGY SERVICES"
}
```
