# EASTERN GAS TRANSMISSION AND STORAGE, INC. — Notice of Amendment

**Citation:** CPF 12021019NOA  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2021-04-23

CLOSED notice of amendment citing 192.805(a), 192.805(b), 192.805(c), 192.805(g), 192.805(h), 192.911(d).

## Document text

Notice of Amendment involving EASTERN GAS TRANSMISSION AND STORAGE, INC.. PHMSA's enforcement data identifies the cited regulations as 192.805(a),  192.805(b),  192.805(c),  192.805(g),  192.805(h),  192.911(d). The case was opened on 2021-04-23 and is reported as closed as of 2021-08-24. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

12021019NOA_Closure Letter_08242021_(20-171889).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Closure%20Letter_08242021_(20-171889).pdf

12021019NOA_Closure Letter_08242021_(20-171889)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Closure%20Letter_08242021_(20-171889)_text.pdf

12021019NOA_Notice of Amendment_04232021_(20-171889).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Notice%20of%20Amendment_04232021_(20-171889).pdf

12021019NOA_Notice of Amendment_04232021_(20-171889)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Notice%20of%20Amendment_04232021_(20-171889)_text.pdf

12021019NOA_Operator Response to Notice_05212021_(20-171889).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Operator%20Response%20to%20Notice_05212021_(20-171889).pdf

12021019NOA_Closure Letter_08242021_(20-171889)_text.pdf

OVERNIGHT EXPRESS DELIVERY
August 24, 2021
Mr. Matt Lamb
Vice President, Eastern Pipeline Operations
Eastern Gas Transmission and Storage, Inc.
925 White Oaks Boulevard
Bridgeport, WV 26330
CPF 1-2021-019-NOA
Dear Mr. Lamb:
From February 24 - 28, 2020, representatives of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code (U.S.C.) inspected
Dominion Energy Transmission, Inc.’s procedures for Operator Qualification (OQ) at your office
located in Bridgeport, West Virginia. Subsequently, on November 1, 2020, Dominion Energy
Transmission, Inc., OPID 2714, was acquired by Berkshire Hathaway Energy, a subsidiary of
Berkshire Hathaway, Inc. Additionally, the name of OPID 2714 was changed to Eastern Gas
Transmission and Storage, Inc., referred to hereinafter as EGTSI. EGTSI is utilizing the existing
OQ procedures of Dominion Energy Transmission, Inc. As a result of the inspection, EGTSI was
issued a Notice of Amendment on April 23, 2021, which proposed amendment of your procedures.
EGTSI submitted its amended procedures on May 21, 2021. My staff reviewed the amended
procedures, and it appears that the inadequacies outlined in this Notice of Amendment have been
corrected.
This letter is to inform you no further action is necessary and this case is now closed. Thank you
for your cooperation.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration

12021019NOA_Notice of Amendment_04232021_(20-171889)_text.pdf

NOTICE OF AMENDMENT
OVERNIGHT EXPRESS DELIVERY
April 23, 2021
Mr. Matt Lamb
Vice President, Eastern Pipeline Operations
Eastern Gas Transmission and Storage, Inc.
925 White Oaks Boulevard
Bridgeport, WV 26330
CPF 1-2021-019-NOA
Dear Mr. Lamb:
From February 24 - 28, 2020, representatives of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code (U.S.C.) inspected
Dominion Energy Transmission, Inc.’s procedures for Operator Qualification (OQ) at your office
located in Bridgeport, West Virginia.
Subsequently, on November 1, 2020, Dominion Energy Transmission, Inc., OPID 2714, was
acquired by Berkshire Hathaway Energy, a subsidiary of Berkshire Hathaway, Inc. Additionally,
the name of OPID 2714 was changed to Eastern Gas Transmission and Storage, Inc., referred to
hereinafter as EGTSI. EGTSI is utilizing the existing OQ procedures of Dominion Energy
Transmission, Inc.
On the basis of the inspection, PHMSA has identified the apparent inadequacies found within
EGTSI’s plans or procedures, as described below:
1. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program shall include provisions to:
(a) Identify covered tasks; …



CPF 1-2021-019-NOA
EGTSI’s written qualification program was inadequate because it did not identify a specific
covered task. Specifically, EGTSI’s D.O.T. Operator Qualification Compliance Plan, Revision
Date: 12/11/181 (OQ Compliance Plan) did not contain a covered task that involved an individual
using digital radiography to detect internal corrosion as an integral part of its short pipe assessment
outlined in its integrity management program.
During the inspection, a PHMSA inspector reviewed EGTSI’s written process for direct
assessment that involved using digital radiography, a method of nondestructive testing, to detect
internal corrosion on a covered segment which was titled, Short Pipe Direct Examination for
Internal Corrosion, Revision Date: 02/07/2012 (Short Pipe). Pursuant to Short Pipe Subsection
5.8 Radiographic Methods, digital radiography may be used to detect internal corrosion on the
pipe segment. EGTSI (at the time Dominion) later explained via e-mail that digital radiography
can be used as a screening mechanism to inspect for internal corrosion during short pipe
assessments, and if the digital radiography detects internal corrosion then ultrasonic thickness
testing must be used to measure the depth of internal corrosion.
At prior inspections, EGTSI identified short pipe segments that were in high consequence areas
and which had internal corrosion as a threat to its pipeline integrity. Hence, EGTSI included these
short pipe segments in its integrity management program. EGTSI explained that it had an
individual use digital radiography to inspect its pipe for internal corrosion during a short pipe direct
assessment. The following records revealed an individual had performed a nondestructive test
using digital radiography inspection:
1. Direct Examination Data Collection Form, LN-30, Dated 6/26/14
Section B. Integrity Dig Site Inspection Report
(4) NDT and Inspection Results
Method of inspection: Computerized Radiography
• Non-Destructive Examination Report dated 07/01/2014
2. Direct Examination Data Collection Form, TL 469 BR2, Dated 4/13/15
Section B. Integrity Dig Site Inspection Report
(4) NDT and Inspection Results
Method of inspection: Blank
• Non-Destructive Examination Report dated 04/14/2015
The PHMSA inspector requested EGTSI to provide Operator Qualification (OQ) records for those
individuals who conducted or observed the digital radiography inspection. EGTSI stated that it did
not consider digital radiography to be a covered task and had no OQ records that included digital
radiography for those individuals. Consequently, EGTSI had not identified a covered task that
included digital radiography.
1 The document provided to PHMSA contained a revision date of 12/11/18, but EGTSI clarified during and after the
inspection that the actual revision date of the version reviewed was 12/31/19.
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 2 of 9



CPF 1-2021-019-NOA
The PHMSA inspector requested EGTSI to provide an analysis of the work activities which
included using digital radiography to detect corrosion on its pipeline during a direct assessment
under integrity management. EGTSI responded that its corrosion team determined that using
digital radiography did not meet the four-part test. Subsequently, the PHMSA inspector requested
EGTSI to provide documentation to show its corrosion control team or other individual(s) decision
to not include digital radiography as a covered task or part of a covered task in the OQ Compliance
Plan. In response, EGTSI merely stated that it does not consider digital radiography to be a covered
task. Nonetheless, EGTSI decided to utilize digital radiography as an integral part of its direct
assessment for internal corrosion.
As defined in § 192.801(b), a covered task is an activity that:
(1) is performed on a pipeline facility: based on the information provided by EGTSI, yes, an
individual performed an activity of digital radiography on a pipeline facility;
(2) is an operations or maintenance task: based on the information provided by EGTSI, yes,
an individual performed this activity during pipeline operation and maintenance task to detect
internal corrosion under integrity management;
(3) is performed as a requirement of Part 192: based on the information provided by EGTSI,
yes, this activity was conducted in accordance with requirements of Subpart O; and
(4) affects the operation or integrity of the pipeline: based on the information provided by
EGTSI, if this activity was performed inadequately it would create incorrect results which
would affect the operation or integrity of the pipeline. For instance, an inaccurate image or
misinterpretation of an image of internal corrosion would prevent further assessment to be
complete for it is used as a screening mechanism.
Thus, EGTSI’s use of digital radiography inspection is a covered task.
Therefore, EGTSI’s written qualification program was inadequate because it did not identify a
specific covered task in accordance with § 192.805(a). EGTSI must amend its OQ Compliance
Program to include digital radiography inspection.
2. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program will include provisions to:
(a) Identify covered tasks; …
EGTSI’s written qualification program was inadequate. Specifically, EGTSI’s OQ Compliance
Plan failed to include certain procedures and documents that EGTSI actively uses as part of their
OQ program.
During the inspection, EGTSI presented a form to PHMSA entitled "Operator Qualification Task:
New/Revise/Retire”, revision date January 8, 2020 (Form). EGTSI indicated that this 6-page form
is used to document new, revised, or retired covered tasks. Neither the Form nor any guidance for
its use were included in EGTSI’s OQ Compliance Plan.
Therefore, EGTSI’s OQ Compliance Plan was inadequate. EGTSI must revise its OQ Compliance
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 3 of 9



CPF 1-2021-019-NOA
Plan to include its Form and details on the process followed for its use.
3. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program will include provisions to:
(a) …
(b) Ensure through evaluation that individuals performing covered
tasks are qualified; …
EGTSI’s written qualification program was inadequate. Specifically, EGTSI’s OQ Compliance
Plan did not contain evaluation methods for a covered task. In addition, EGTSI’s OQ Compliance
Plan did not contain a detailed, written evaluation method process for qualifying an individual to
perform a covered task.
The following deficiencies were noted during the inspection:
1. On February 27, 2020, EGTSI presented a document titled DTI Qual and Requalification
Methods as of 11/14/2019 (OQ Methods) which listed its evaluation method(s) for qualifying
an individual to perform a covered task. This document was not referenced in its OQ
Compliance Plan. EGTSI had no other document to demonstrate it determined the evaluation
method(s) for each covered task. Consequently, EGTSI’s OQ Compliance Plan did not include
evaluation method(s) for each covered task for initial qualification and subsequent
qualification.
2. EGTSI’s OQ Compliance Plan, Section 4, Evaluation of Qualifications indicated that an
individual may be evaluated by observation during on the job performance only. However, this
is not consistent with § 192.809(e) which states that an observation of on-the-job performance
may not be used as the sole method of evaluation after December 16, 2004. EGTSI did not
produce a written process that prohibited the use of observation of on-the-job performance as
a sole evaluation method.
3. EGTSI’s OQ Compliance Plan did not have an evaluation criteria to ensure an individual
is qualified to perform a covered task. Pursuant to § 192.803, “qualified” means individuals
can (a) perform the assigned covered tasks; and (b) recognize and react to abnormal operating
conditions (AOCs). Therefore, an evaluation must ensure that an individual possesses
knowledge, skills, and abilities to perform the assigned covered task and to recognize and react
to AOCs.
For example, both EGTSI’s SOP 390/01 Valve Inspection and Maintenance / Transmission,
Storage, and Jurisdictional Gathering Pipelines, Revision Date: 08/01/2019 and OQ-071-GL
Inspecting Maintaining & Lubricating, Revision Date: 08/29/2014 (OQ-071-GL) stated that
an individual must operate a valve. However, EGTSI’s OQ Compliance Plan did not contain
the evaluation method(s) used to assess an individual's abilities to properly perform the covered
task. Based on EGTSI’s OQ Methods for covered task OQ-071-GL, initial qualification
methods would be either a class or hands-on OQ or a learning management system (LMS)2
,
and the requalification method was only LMS. Thus, EGTSI’s OQ Compliance Plan and OQ
2 LMS is a computer-based operating system used for training functions.
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 4 of 9



CPF 1-2021-019-NOA
Methods allows an individual to take an initial on-line test in LMS and a subsequent on-line
test only. The LMS and on-line test would not be able to ascertain an individual’s ability to
operate a manual valve. Consequently, as written, an individual would not be assessed for
their physical ability to perform that covered task.
In addition, EGTSI’s on-line test for covered task OQ-071-GL did not contain an evaluation
to determine whether an individual can recognize and react to specific AOCs that may occur
when performing that covered task. EGTSI’s on-line test did not cover AOCs for inspecting,
maintaining, and lubricating valve. Consequently, an individual will not be evaluated for task
specific AOCs if an on-line test is taken.
4. EGTSI stated that an individual can take the online test anywhere and anytime on their
company's laptop. However, EGTSI did not have a written process to ensure no one other than
the individual to be qualified is taking the test or no other individual provides the answers to
the individual to be qualified while taking the test.
Therefore, EGTSI’s OQ Compliance Plan failed to include provisions that ensure through
evaluation that individuals performing covered tasks are qualified as prescribed in § 192.805(b).
As such, EGTSI must amend its OQ Compliance Plan to include evaluation method(s) for each
covered task for initial qualification and subsequent qualification. Also, EGTSI’s OQ Compliance
Plan must ensure no individual can be evaluated solely by “observation during performance on the
job.” In addition, EGTSI’s OQ Compliance Plan must have an evaluation criteria to ensure an
individual performing a covered task is qualified. Furthermore, EGTSI’s OQ Compliance Plan
must ensure each covered task evaluation method includes an evaluation on task specific AOCs,
and have a process to ensure individuals will be the only one taking the on-line test.
4. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program will include provisions to:
(a) …
(b) Ensure through evaluation that individuals performing covered
tasks are qualified; …
EGTSI’s written qualification program was inadequate. Specifically, EGTSI’s OQ Compliance
Plan failed to include certain procedures and documents that EGTSI actively uses as part of their
OQ program.
During the inspection, PHMSA reviewed and noted several individual’s OQ qualification records
indicating “equivalent” under the recorded “Qualification Method”. EGTSI’s OQ Compliance
Plan did not include a process for using “equivalent’ courses for granting OQ credit. EGTSI
provided a spreadsheet reflecting which OQ courses are granted as equivalent credit for other OQ
courses, but it is unclear how this is used as it is not included in their OQ Compliance Plan.
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 5 of 9



CPF 1-2021-019-NOA
Therefore, EGTSI’s OQ Compliance Plan were inadequate. EGTSI must revise its OQ Compliance
Plan to include the list of “equivalent courses” and details of its process of granting qualifications
using equivalent OQ credit.
5. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program will include provisions to:
(a) …
(c) Allow individuals that are not qualified pursuant to this subpart
to perform a covered task if directed and observed by an individual
that is qualified; …
EGTSI’s written qualification program was inadequate because it failed to include provisions to
allow individuals that are not qualified pursuant to this subpart to perform a covered task if directed
and observed by an individual that is qualified. Specifically, EGTSI’s OQ Compliance Plan did
not define under what condition(s) a qualified person would direct and observe one or more
unqualified persons.
EGTSI’s OQ Compliance Plan, Section 5. Non-Qualified Individuals Performing Covered Tasks,
referenced a document titled OQ and IMP Tasks by Category. The OQ and IMP Tasks by Category
as of 1/8/2020 listed a span of control ratio for each covered task. The PHMSA inspector requested
EGTSI to produce its criteria in determining the number of qualified individual(s) to non-qualified
individual(s) who can safely perform a covered task under their direction and observation (known
as span of control). EGTSI stated that it did not establish criteria to determine the span of control.
Thus, the written process for allowing unqualified individuals to perform covered tasks while
being directed and observed by a qualified individual was inadequate.
Therefore, EGTSI’s OQ Compliance Plan was inadequate for it failed to include adequate
provisions for allowing individuals that are not qualified pursuant to this subpart to perform a
covered task if directed and observed by an individual that is qualified in accordance with §
192.805(c). EGTSI must amend its OQ Compliance Plan to include more details on determining
span of control.
6. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program will include provisions to:
(a) …
(g) Identify those covered tasks and the intervals at which
evaluation of the individual's qualifications is needed; …
EGTSI’s written qualification program was inadequate because it failed to include a provision to
identify those covered tasks and the intervals at which evaluation of an individual's qualifications
is needed.
EGTSI’s OQ Compliance Plan, Section 9, Qualification Evaluation and Intervals did not describe
the number of times an individual can be re-evaluated before their qualification is revoked or a
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 6 of 9



CPF 1-2021-019-NOA
minimum timeframe for re-evaluation once an individual did not pass or complete an evaluation
for a covered task. In addition, EGTSI’s OQ Compliance Plan, Section 9 Qualification Evaluation
and Intervals did not define when a qualification has expired. It mentioned that each of its covered
tasks has a requalification interval and a grace period of three months, but it is unclear when the
qualification has become invalid and re-evaluation of the individual’s qualification is needed.
Therefore, EGTSI’s OQ Compliance Plan was inadequate because it failed to include a provision
to identify those covered tasks and its intervals at which evaluation of the individual's
qualifications are is needed in accordance with § 192.805(g). EGTSI must amend its OQ
Compliance Plan to include more details on the its qualification process.
7. § 192.805 Qualification program.
Each operator shall have and follow a written qualification
program. The program will include provisions to:
(a) …
(h) After December 16, 2004, provide training, as appropriate, to
ensure that individuals performing covered tasks have the necessary
knowledge and skills to perform the tasks in a manner that ensures the
safe operation of pipeline facilities; and …
EGTSI’s written qualification program was inadequate because it failed to fully address training
requirements, as appropriate, to ensure that individual performing covered tasks have the necessary
knowledge and skills to perform the tasks in a manner that ensures the safe operation of pipeline
facilities.
EGTSI’s OQ Compliance Plan vaguely mentioned training for individuals whose performance of
a covered task was determined to have contributed to an incident or accident. The OQ Compliance
Plan, Section 6, Performance of a Covered Task Contributing to an Incident or Accident, indicated
that an evaluation would be done to determine whether an individual should receive training, but
there was no additional information on method, content, or time frame. Thus, the written process
to determine when training is “appropriate” was inadequate.
During this inspection, EGTSI stated that there were PowerPoint slides before the on-line test for
covered tasks which provided training to individuals. This information was not included in
EGTSI’s OQ Compliance Plan. DETI Qual and Requalification Methods, as of 11/14/2019
described that an individual can be evaluated using other methods beside on-line evaluation, in
which case an individual would not be trained if he or she did not take an on-line evaluation. In
addition, EGTSI’s OQ Compliance Program had no instructions on minimum passing grade or
completion for training. Furthermore, EGTSI’s OQ Compliance Plan did not define the
requirements for initial training and new hires. Thus, the written process for providing training per
§ 192.805(h) lacked sufficient detail.
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 7 of 9



CPF 1-2021-019-NOA
Therefore, EGTSI’s OQ Program was inadequate for it failed to ensure that individual performing
covered tasks have the necessary knowledge and skills to perform the tasks in a manner that
ensures the safe operation of pipeline facilities in accordance with § 192.805(h). EGTSI must
amend its OQ Compliance Plan to include more details on training requirements.
8. § 192.911 What are the elements of an integrity management program?
An operator's initial integrity management program begins with a
framework (see §192.907) and evolves into a more detailed and
comprehensive integrity management program, as information is
gained and incorporated into the program. An operator must make
continual improvements to its program. The initial program
framework and subsequent program must, at minimum, contain the
following elements. (When indicated, refer to ASME/ANSI B31.8S
(incorporated by reference, see §192.7) for more detailed information
on the listed element.)
(a) …
(d) A direct assessment plan, if applicable, meeting the
requirements of §192.923, and depending on the threat assessed, of
§§192.925, 192.927, or 192.929.
EGTSI’s integrity management program was inadequate because it did not contain a detailed direct
assessment plan in accordance with § 192.927. Specifically, EGTSI’s Integrity Management
Program Gas Transmission Pipeline, Revision Date: 09/01/2014 (IMP) did not contain a detailed
direct assessment plan addressing how digital radiography is employed when used to detect
internal corrosion.
During the inspection, a PHMSA inspector reviewed EGTSI’s written process for direct
assessment that involved using digital radiography to detect internal corrosion, which was titled
Short Pipe Direct Examination for Internal Corrosion, Revision Date: 02/07/2012 (Short Pipe).
Pursuant to Short Pipe Subsection 5.8 Radiographic Methods, digital radiography detects
corrosion, but may not be used without other techniques. EGTSI later explained via e-mail that
digital radiography can be used as a screening mechanism to inspect for internal corrosion during
short pipe assessments, and if the digital radiography detects internal corrosion then ultrasonic
thickness testing must be used to measure the depth of internal corrosion. However, there was no
reference to ultrasonic thickness testing as a required next action when corrosion was detected by
digital radiography inspection in the written process. Subsection 5.8, Radiographic Methods, also
did not delineate the methodology to conduct a digital radiography inspection. For example, there
was neither information on an industry standard to apply and interpret digital radiography images
nor was there criteria to determine when to use an ultrasonic thickness testing.
Therefore, EGTSI’s IMP did not contain a detailed direct assessment plan in accordance with
§ 192.927. EGTSI’s must amend its IMP to reflect and include more details on the actual direct
assessment process of applying digital radiography during its short pipe direct examination for
internal corrosion.
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 8 of 9



CPF 1-2021-019-NOA
Response to this Notice
This Notice is provided pursuant to 49 U.S.C. § 60108(a) and 49 C.F.R. § 190.206. Enclosed as
part of this Notice is a document entitled Response Options for Pipeline Operators in Enforcement
Proceedings. Please refer to this document and note the response options. Be advised that all
material you submit in response to this enforcement action is subject to being made publicly
available. If you believe that any portion of your responsive material qualifies for confidential
treatment under 5 U.S.C. 552(b), along with the complete original document you must provide a
second copy of the document with the portions you believe qualify for confidential treatment
redacted and an explanation of why you believe the redacted information qualifies for confidential
treatment under 5 U.S.C. 552(b).
Following the receipt of this Notice, you have 30 days to submit written comments, revised
procedures, or a request for a hearing under §190.211. If you do not respond within 30 days of
receipt of this Notice, this constitutes a waiver of your right to contest the allegations in this Notice
and authorizes the Associate Administrator for Pipeline Safety to find facts as alleged in this Notice
without further notice to you and to issue an Order Directing Amendment. If your plans or
procedures are found inadequate as alleged in this Notice, you may be ordered to amend your plans
or procedures to correct the inadequacies (49 C.F.R. § 190.206). If you are not contesting this
Notice, we propose that you submit your amended procedures to my office within 30 days of
receipt of this Notice. This period may be extended by written request for good cause. Once the
inadequacies identified herein have been addressed in your amended procedures, this enforcement
action will be closed.
It is requested (not mandated) that Eastern Gas Transmission and Storage, Inc maintain
documentation of the safety improvement costs associated with fulfilling this Notice of
Amendment (preparation/revision of plans, procedures) and submit the total to Robert Burrough,
Director, PHMSA Eastern Region, 840 Bear Tavern Road, Suite 300, West Trenton, NJ 08628.
Please refer to CPF 1-2021-019-NOA on each document you submit, and whenever possible
provide a signed PDF copy in electronic format. Smaller files may be emailed to
robert.burrough@dot.gov. Larger files should be sent on USB flash drive accompanied by the
original paper copy to the Eastern Region Office.
Additionally, if you choose to respond to this (or any other case), please ensure that any response
letter pertains solely to one CPF case number.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
Enclosure: Response Options for Pipeline Operators in Enforcement Proceedings
12021019NOA_Notice of Amendment_04232021_(20-171889)_text Page 9 of 9

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/12021019NOA>
- Source ID: `phmsa-enforcement`
- SHA-256: `26830e528af46bcf15d478e0b483037a284a2b63bb79c3923ed5ca097365f533`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-23T18:08:37.215Z
- Document slug: `phmsa-enforcement-12021019noa`

### Source metadata

```json
{
  "cpf": "12021019NOA",
  "operator": "EASTERN GAS TRANSMISSION AND STORAGE, INC.",
  "region": "Eastern",
  "pipelineType": "INTERSTATE GAS TRANSMISSION, JURISDICTIONAL GAS GATHERING",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.805(a)",
    "192.805(b)",
    "192.805(c)",
    "192.805(g)",
    "192.805(h)",
    "192.911(d)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 5,
  "attachments": [
    {
      "name": "12021019NOA_Closure Letter_08242021_(20-171889).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Closure%20Letter_08242021_(20-171889).pdf",
      "bytes": 449094,
      "category": "agency_document"
    },
    {
      "name": "12021019NOA_Closure Letter_08242021_(20-171889)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Closure%20Letter_08242021_(20-171889)_text.pdf",
      "bytes": 81691,
      "category": "agency_document"
    },
    {
      "name": "12021019NOA_Notice of Amendment_04232021_(20-171889).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Notice%20of%20Amendment_04232021_(20-171889).pdf",
      "bytes": 1639140,
      "category": "agency_document"
    },
    {
      "name": "12021019NOA_Notice of Amendment_04232021_(20-171889)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Notice%20of%20Amendment_04232021_(20-171889)_text.pdf",
      "bytes": 209226,
      "category": "agency_document"
    },
    {
      "name": "12021019NOA_Operator Response to Notice_05212021_(20-171889).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12021019NOA/12021019NOA_Operator%20Response%20to%20Notice_05212021_(20-171889).pdf",
      "bytes": 1585476,
      "category": "party_submission"
    }
  ],
  "extractedAgencyDocumentCount": 2,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "EASTERN GAS TRANSMISSION AND STORAGE, INC."
}
```