# RICHMOND, CITY OF — Warning Letter

**Citation:** CPF 12026041WL  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2026-03-17

CLOSED warning letter citing 192.605(a).

## Document text

Warning Letter involving RICHMOND, CITY OF. PHMSA's enforcement data identifies the cited regulation as 192.605(a). The case was opened on 2026-03-17 and is reported as closed as of 2026-03-17. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

12026041WL_Warning Letter_03172026_(25-360133).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12026041WL/12026041WL_Warning%20Letter_03172026_(25-360133).pdf

12026041WL_Warning Letter_03172026_(25-360133)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12026041WL/12026041WL_Warning%20Letter_03172026_(25-360133)_text.pdf

12026041WL_Warning Letter_03172026_(25-360133)_text.pdf

U.S. Department
of Transportation
Pipeline and
Hazardous Materials
Safety Administration
840 Bear Tavern Road, Suite 300
West Trenton, NJ 08628
609.771.7800
WARNING LETTER
VIA EMAIL TO: daniel.rifenburgh@rva.gov
March 17, 2026
Daniel Rifenburgh
Director
City of Richmond
400 Richmond Highway
Richmond, Virginia 23224
CPF 1-2026-041-WL
Dear Mr. Rifenburgh:
On March 27, 2025, an inspector from the Virginia State Corporation Commission, Division of
Pipeline Safety (VA SCC), acting as an agent for the Pipeline and Hazardous Materials Safety
Administration (PHMSA), Office of Pipeline Safety (OPS), Eastern Region, pursuant to Chapter
601 of Title 49 United States Code (U.S.C.), inspected the City of Richmond’s (the City or
Respondent) pipeline near 4614 Leonard Parkway in Richmond, Virginia.
As a result of the inspection, Eastern Region alleges that the City violated the Pipeline Safety
Regulations, Title 49, Code of Federal Regulations (CFR) Part 192. Eastern Region identifies one
warning item. The probable violation is:
1. § 192.605 Procedural manual for operations, maintenance, and emergencies.
(a) General. Each operator shall prepare and follow for each
pipeline, a manual of written procedures for conducting operations and
maintenance activities and for emergency response. For transmission
lines, the manual must also include procedures for handling abnormal
operations. This manual must be reviewed and updated by the operator
at intervals not exceeding 15 months, but at least once each calendar
year. This manual must be prepared before operations of a pipeline
system commence. Appropriate parts of the manual must be kept at
locations where operations and maintenance activities are conducted.



CPF 1-2026-041-WL
The City failed to follow for each pipeline, a manual of written procedures for conducting
operations and maintenance activities and for emergency response, as required by section
192.605(a). Specifically, the City failed to follow its Utility: Natural Gas Volume II Procedures
Manual, Chapter 2, Section II (11/27/2013) (NGPM) by excavating with mechanized equipment
within two feet of an exposed gas service line.
The NGPM required all work in close proximity to underground utility lines to be performed by
hand digging. However, a VA SCC inspector observed a City contractor crew using mechanized
equipment within two feet of an exposed gas service line.
Therefore, the City failed to follow for each pipeline, a manual of written procedures for
conducting operations and maintenance activities and for emergency response, as required by
section 192.605(a).
Response to this Notice
This Notice is issued in accordance with 49 CFR § 190.205. No reply to this Notice is required.
Warning Item
Eastern Region has reviewed the facts and evidence and has decided not to propose a civil penalty
or compliance order at this time. Eastern Region advises the Respondent to promptly correct this
item, if it has not already done so. Failure to do so may result in additional enforcement action.
All material submitted in response to this enforcement action may be made publicly available. If
the Respondent believes that any portion of the responsive material qualifies for confidential
treatment under 5 U.S.C. § 552(b), along with the complete original document, it must provide a
second copy of the document with the portions that may qualify for confidential treatment redacted
and an explanation of why the redacted information may qualify for confidential treatment under
5 U.S.C. § 552(b).
In correspondence on this matter, please refer to CPF 1-2026-041-WL.
Sincerely,
Robert Burrough
Director, Eastern Region, Office of Pipeline Safety
Pipeline and Hazardous Materials Safety Administration
cc: Eddie Childers, Operations Manager, City of Richmond, eddie.childers@rva.gov
Page 2 of 2

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/12026041WL>
- Source ID: `phmsa-enforcement`
- SHA-256: `df78ec1899ec8711c79fba749a1d3cc11e38ce202daf0b125aaf5891fe058285`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T16:40:37.005Z
- Document slug: `phmsa-enforcement-12026041wl`

### Source metadata

```json
{
  "cpf": "12026041WL",
  "operator": "RICHMOND, CITY OF",
  "region": "Eastern",
  "pipelineType": "DISTRIBUTION MUNICIPAL",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.605(a)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "12026041WL_Warning Letter_03172026_(25-360133).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12026041WL/12026041WL_Warning%20Letter_03172026_(25-360133).pdf",
      "bytes": 197177,
      "category": "agency_document"
    },
    {
      "name": "12026041WL_Warning Letter_03172026_(25-360133)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/12026041WL/12026041WL_Warning%20Letter_03172026_(25-360133)_text.pdf",
      "bytes": 221828,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "RICHMOND, CITY OF"
}
```