# SANTEE COOPER - RAINEY GENERATING STATION — Warning Letter

**Citation:** CPF 220071015W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2007-09-12

CLOSED warning letter citing 192.13, 192.481(a).

## Document text

Warning Letter involving SANTEE COOPER - RAINEY GENERATING STATION. PHMSA's enforcement data identifies the cited regulations as 192.13,  192.481(a). The case was opened on 2007-09-12 and is reported as closed as of 2007-09-12. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220071015W_warning letter_09122007.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220071015W/220071015W_warning%20letter_09122007.pdf

220071015w_warning letter_09122007_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220071015W/220071015w_warning%20letter_09122007_text.pdf

220071015w_warning letter_09122007_text.pdf

tJ 5 Department
of Transportation
Pipeline and
Hazardous Materials Safety
Administration
233 Peachtree Street Ste 600
Atlanta GA 30303
WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT RK UKSTED
September 12, 2007
Mr Joseph Thorndyke
Station Manager
Santee Cooper Rainey Generating Station
P 0 Box 70
2900 Opry House Road
lva, SC 29655 - 8580
CPF 2-2007-1015W
Dear Mr Thorndyke
On Apnl 30 thru May 2, 2007, representatives of the Pipehne and Hazardous Matenals Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code inspected your
records and pipehne facdities in Iva, South Carohna
As a result of the inspection, it appears that you have committed probable violations of the
Ptpehne Safety Regulations Title 49, Code of Federal Regulations The items inspected and the
probable violations are
1. tt192 13 General
(c) Each operator shall maintain, modify as appropriate, and follow the plans,
procedures, and programs that it is required to cstabhsh under this part.
Santee Cooper Rainey (SCR) dtd not conduct a gas leak detection survey using detector
equipment on its non odonzed gas pipehne twice a year, not exceeding 7-'/t month interval as
per its procedure, Section 30 102 SCR conducted the gas leak detection survey once each
calendar year tn accordance with 11192 706 but not according to its procedure
The gas leak surveys were conducted on 10/26/06, 10/17/05 and 12/11/04



2. I)192. 481 (a) Atmospheric corrosion control: Monitoring
Each operator must inspect each pipehne or portion of pipehne that is exposed to the
atmosphere for evidence of atmospheric corrosion at least every three years, but with
intervals not exceeding 39 months
SRC did not keep any records to show that they have monitored atmospheric corrosion as per
this section
Under 49 United States Code, I'l 60122, you are sub) ect to a civd penalty not to exceed
$100, 000 for each violation for each day the violations persists up to a maximum of $1, 000, 000
for any related senes of violations We have reviewed the circumstances and supporting
documents involved in this case, and have decided not to conduct additional enforcement action
or penalty assessment proceedings at this time We advise you to correct the item(s) identified
in this letter Be advised that failure to do so will result in Santee Cooper Rainey being sublect
to additional enforcement action
No reply to this letter is reqmred If you choose to reply, in your correspondence please refer to
CPF 2-2007-1015W Be advised that all matenal you submit in response to this enforcement
action is sub)ect to being made publicly available If you beheve that any portion of your
responsive matenal quahfies for confidential treatment under 5 U S C 552(b), along with the
complete onginal document you must provide a second copy of the document with the portions
you beheve quahfy for confidential treatment redacted and an explanation of why you believe
the redacted information quahfies for confidential treatment under 5 U S C 552(b)
Linda Daugherty
Director, Southern Region
Pipeline and Hazardous Materials Safety Administration

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/220071015W>
- Source ID: `phmsa-enforcement`
- SHA-256: `7b5b8f7ffb4fe14f9957f68b26c74facaee218a5038fea0886d3469e7f685a09`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T08:02:39.626Z
- Document slug: `phmsa-enforcement-220071015w`

### Source metadata

```json
{
  "cpf": "220071015W",
  "operator": "SANTEE COOPER - RAINEY GENERATING STATION",
  "region": "Southern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.13",
    "192.481(a)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "220071015W_warning letter_09122007.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220071015W/220071015W_warning%20letter_09122007.pdf",
      "bytes": 52941,
      "category": "agency_document"
    },
    {
      "name": "220071015w_warning letter_09122007_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220071015W/220071015w_warning%20letter_09122007_text.pdf",
      "bytes": 58028,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "SANTEE COOPER - RAINEY GENERATING STATION"
}
```