# TRUNKLINE GAS CO — Warning Letter

**Citation:** CPF 220081008W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2008-10-16

CLOSED warning letter citing 192.13(c).

## Document text

Warning Letter involving TRUNKLINE GAS CO. PHMSA's enforcement data identifies the cited regulation as 192.13(c). The case was opened on 2008-10-16 and is reported as closed as of 2008-10-16. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220081008W_warning letter_10162008.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220081008W/220081008W_warning%20letter_10162008.pdf

220081008w_warning letter_10162008_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220081008W/220081008w_warning%20letter_10162008_text.pdf

220081008w_warning letter_10162008_text.pdf

U. S. Department
of rransponation
Pipeline and
Hazardous Materials Safety
Administration
233 Peachtree Street Ste. 600
Atlanta, GA 30303
WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT RE UESTED
October 16, 2008
Jerry Mohn
Sr, Vice President
Trunkline Gas Company
5444 Westheimer Road
Houston, TX 77056-5306
CPF 2-2008-1008W
Dear Mr. Mohn:
On August 4 thru 8 and 11 thru 14, 2008, representatives of the Pipeline and Hazardous
Materials Safety Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code
inspected your pipeline facilities in Mississippi, Tennessee, and Kentucky areas and records at
Shaw, Independence (Mississippi) and Dyersburg (Tennessee) district offices.
As a result of the inspection, it appears that you have committed a probable violation of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected and
the probable violation is:
tt 192, 13 General
(c) Each operator shall maintain, modify as appropriate, and follow the plans, and
procedures, and programs that it is required to establish under this part.
Trunkline Gas Company (TGC) did not conduct a gas leakage detection equipment
survey at its mechanically shorted casing locations at class locations I & 11 on a
semi-annual basis as per their procedure no. 1. 22, Table 4.
1. During the field check on 8/13/08 in the KY area, the casings at the following
locations are found mechanically shorted:
(a) Test Point 124+49, Hwy. 60, line 300, valve section 101: P/S: 1083mv C/S: 1081
mV (P/S:1094/1091 C/S at 5 feet distance).
(b) Test Point 250+71, Stone Corner Road, line 300, valve section 101: P/S: 1223 mV,
C/S: 1211 mV.



(c) Test Point 298+29, Abandoned Road, line 300, valve section 100: P/S: 1223 mV,
C/S: 1184 mV.
2. In Dyersburg district, the test point 146+62, Hwy. 77, AM-3, line 300, showed a
suspected shorted casing in 2006 & 2007. No electrical test was performed to verify if
it v:as an actual shorted casing.
3. During the field check on 8/I 3/08, the casings at the following locations in Dyersburg
district were found to be suspected shorted casings.
(a) Test Point: 40+88, Hwy. 21 E, line 200: P/S: 1688 mV. C/S: 1680 mV.
(b) Test Point; 442+62, Polk Road (Troy), line 200, P/S: 1304 mV, C/S: 1303 mV.
These casings v ere tested on 4/19/99 and found mechanically shorted in 2005 thru
2008. An accelerated leakage survey with gas leakage detection equipment is required
on a semi-annually basis, not to exceed 71/2 months (SOP 1. 22, effective I/I/07). The
semi-annually gas leakage detection survey by instrument is not being carried out from
the date the casings are first found mechanically shorted.
Under 49 United States Code, ) 60122, you are subject to a civil penalty not to exceed
$100, 000 for each violation for each day the violation persists up to a maximum of $1, 000, 000
for any related series of violation. We have reviewed the circumstances and supporting
documents involved in this case, and have decided not to conduct additional enforcement action
or penalty assessment proceedings at this time. We advise you to correct the item(s) identified
in this letter. Failure to do so will result in Trunkline Gas Company being subject to additional
enforcement action.
Ko reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 2-2008-1008W. Be advised that all material you submit in response to this enforcement
action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U. S. C. 552(b), along with the
complete original document you must provide a second copy of the document with the portions
you believe qualify for confidential treatment redacted and an explanation of why you believe
the redacted information qualifies for confidential treatment under 5 U, S. C. 552(b).
Sincerely,
Linda Daugherty
Director, Southern Region
Pipeline and Hazardous Materials Safety Administration

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/220081008W>
- Source ID: `phmsa-enforcement`
- SHA-256: `d5132a9b68d402bd893d981364a613b5bd70e50d6ab06da2ed632eb1362cad6a`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T05:26:56.515Z
- Document slug: `phmsa-enforcement-220081008w`

### Source metadata

```json
{
  "cpf": "220081008W",
  "operator": "TRUNKLINE GAS CO",
  "region": "Southern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.13(c)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "220081008W_warning letter_10162008.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220081008W/220081008W_warning%20letter_10162008.pdf",
      "bytes": 114207,
      "category": "agency_document"
    },
    {
      "name": "220081008w_warning letter_10162008_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220081008W/220081008w_warning%20letter_10162008_text.pdf",
      "bytes": 780791,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "TRUNKLINE GAS CO"
}
```