# DESTIN PIPELINE COMPANY, LLC — Warning Letter

**Citation:** CPF 220101003W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2010-02-09

CLOSED warning letter citing 192.459, 192.479, 192.731(c), 192.739(a).

## Document text

Warning Letter involving DESTIN PIPELINE COMPANY, LLC. PHMSA's enforcement data identifies the cited regulations as 192.459,  192.479,  192.731(c),  192.739(a). The case was opened on 2010-02-09 and is reported as closed as of 2010-02-09. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220101003W_operator response_04082010.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220101003W/220101003W_operator%20response_04082010.pdf

220101003W_warning letter_02092010.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220101003W/220101003W_warning%20letter_02092010.pdf

220101003W_warning letter_02092010_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220101003W/220101003W_warning%20letter_02092010_text.pdf

220101003W_warning letter_02092010_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
February 9, 2010
Mr. Steve Pankhurst
Business Unit Leader
Destin Pipeline Company, LLC
BP US Pipeline & Logistics
28100 Torch Parkway
Warrenville, Illinois 60555
CPF 2-2010-1003W
Dear Mr. Pankhurst:
On July 13 – 17, 2009, representatives of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code inspected your
records and procedures in Moss Point, Mississippi and pipeline facilities of Destin Pipeline
Company, LLC in Mississippi and the Gulf of Mexico.
As a result of the inspection, it appears that you have committed probable violations of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected and
the probable violation(s) are:
1. §192.491 Corrosion control records.
(c) Each operator shall maintain a record of each test, survey, or inspection
required by this subpart in sufficient detail to demonstrate the adequacy of
corrosion control measures or that a corrosive condition does not exist. These
records must be retained for at least 5 years, except that records related to
§§192.465(a) and (e) and 192.475(b) must be retained for as long as the pipeline
remains in service.
§192.459 External corrosion control: Examination of buried pipeline when
exposed.
Whenever an operator has knowledge that any portion of a buried pipeline is
exposed, the exposed portion must be examined for evidence of external corrosion
if the pipe is bare, or if the coating is deteriorated. If external corrosion requiring



remedial action under §§192.483 through 192.489 is found, the operator shall
investigate circumferentially and longitudinally beyond the exposed portion (by
visual examination, indirect method, or both) to determine whether additional
corrosion requiring remedial action exists in the vicinity of the exposed portion.
Destin Pipeline did not properly document the examination of its pipeline when
exposed.
Destin Pipeline Repair and Inspection Report Report Numbers DSN-08-I-0001 and
DSN-08-I-0002 are not filled in to document the examination of the condition of the
coating in field A14.e Coating Condition on the reports.
2. §192.709 Transmission lines: Record keeping.
Each operator shall maintain the following records for transmission lines for the
periods specified:
(c) A record of each patrol, survey, inspection, and test required by subparts L and
M of this part must be retained for at least 5 years or until the next patrol, survey,
inspection, or test is completed, whichever is longer.
§192.731 Compressor stations: Inspection and testing of relief devices.
(c) Each remote control shutdown device must be inspected and tested at intervals
not exceeding 15 months, but at least once each calendar year, to determine that it
functions properly.
Destin Pipeline did not have a record documenting the 2005 Pascagoula Compressor
Station test of the high discharge pressure shutdown and calibration of the compressor
station discharge side pressure transmitter.
Destin Pipeline was unable to provide a copy of the Work Order documenting the
calibration of the Pascagoula Compressor Station discharge side pressure transmitter
and the test of the PLC set points for the Hi Pressure Point and Hi Hi Pressure Point.
3. §192.709 Transmission lines: Record keeping.
Each operator shall maintain the following records for transmission lines for the
periods specified:
(c) A record of each patrol, survey, inspection, and test required by subparts L and
M of this part must be retained for at least 5 years or until the next patrol, survey,
inspection, or test is completed, whichever is longer.
§192.739 Pressure limiting and regulating stations: Inspection and testing.
(a) Each pressure limiting station, relief device (except rupture discs), and
pressure regulating station and its equipment must be subjected at intervals not
exceeding 15 months, but at least once each calendar year, to inspections and tests
to determine that it is–
2



(1) In good mechanical condition;
(2) Adequate from the standpoint of capacity and reliability of operation for the
service in which it is employed;
(3) Except as provided in paragraph (b) of this section, set to control or relieve at
the correct pressure consistent with the pressure limits of §192.201(a); and
(4) Properly installed and protected from dirt, liquids, or other conditions that
might prevent proper operation.
Destin Pipeline could not provide copies of the inspection records for the inspections of
pressure regulating control valve PV-1400 at the Pascagoula Compressor Station.
Destin Pipeline did not have inspection records for pressure regulating control valve
PV-1400 which is identified on the Pascagoula Compressor station Fuel Gas Heater /
Filter Separator Mechanical Flowsheet drawing DES-C1-A-104.
4. §192.479 Atmospheric corrosion control; General.
(a) Each operator must clean and coat each pipeline or portion of pipeline that is
exposed to the atmosphere, except pipelines under paragraph (c) of this section.
(b) Coating material must be suitable for the prevention of atmospheric corrosion.
(c) Except portions of pipelines in offshore splash zones or soil-to-air interfaces,
the operator need not protect from atmospheric corrosion any pipeline for which
the operator demonstrates by test, investigation, or experience appropriate to the
environment of the pipeline that corrosion will--
(1) Only be a light surface oxide; or
(2) Not affect the safe operation of the pipeline before the next scheduled
inspection.
The recycle line to the Unit #1 Suction Line at the Sand Hill Compressor Station is not
coated at the soil-to-air interface.
The coating of the soil-to-air interface on the bypass line at the Pascagoula Compressor
Station had deteriorated and surface rust was observed on the pipe.
During the field portion of the inspection at the Sand Hill Compressor Station, light
surface rust was observed on the recycle line of the Unit #1 Suction Line at the soil-to-
air interface. Upon further examination it was noted that the pipe was not coated.
During the field portion of the inspection at the Pascagoula Compressor Station, light
surface rust was observed on the bypass line at the soil-to-air interface. Upon further
examination it was noted that the coating on the pipe had deteriorated.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed
$100,000 for each violation for each day the violation persists up to a maximum of $1,000,000
for any related series of violations. We have reviewed the circumstances and supporting
documents involved in this case, and have decided not to conduct additional enforcement action
or penalty assessment proceedings at this time. We advise you to correct the item(s) identified
3



in this letter. Failure to do so will result in Destin Pipeline Company, LLC being subject to
additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 2-2010-1003W. Be advised that all material you submit in response to this enforcement
action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the
complete original document you must provide a second copy of the document with the portions
you believe qualify for confidential treatment redacted and an explanation of why you believe
the redacted information qualifies for confidential treatment under 5 U.S.C. 552(b).
Sincerely,
Linda Daugherty
Director, Southern Region
Pipeline and Hazardous Materials Safety Administration
4

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/220101003W>
- Source ID: `phmsa-enforcement`
- SHA-256: `5a30fb2b89997431bc6f4447ec10ba936b0891d7ea376d45de71261aed9cf387`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-23T08:54:39.486Z
- Document slug: `phmsa-enforcement-220101003w`

### Source metadata

```json
{
  "cpf": "220101003W",
  "operator": "DESTIN PIPELINE COMPANY, LLC",
  "region": "Southern",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.459",
    "192.479",
    "192.731(c)",
    "192.739(a)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 3,
  "attachments": [
    {
      "name": "220101003W_operator response_04082010.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220101003W/220101003W_operator%20response_04082010.pdf",
      "bytes": 89577,
      "category": "party_submission"
    },
    {
      "name": "220101003W_warning letter_02092010.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220101003W/220101003W_warning%20letter_02092010.pdf",
      "bytes": 236515,
      "category": "agency_document"
    },
    {
      "name": "220101003W_warning letter_02092010_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220101003W/220101003W_warning%20letter_02092010_text.pdf",
      "bytes": 26449,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "DESTIN PIPELINE COMPANY, LLC"
}
```