# SUBURBAN PROPANE — Warning Letter

**Citation:** CPF 220110003W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2011-04-06

CLOSED warning letter citing 191.11(a), 192.355(c), 192.465(a), 192.465(b), 192.465(d), 192.491(a), 192.605(a), 192.625(a), 192.723(a), 192.739(a), 192.747(a).

## Document text

Warning Letter involving SUBURBAN PROPANE. PHMSA's enforcement data identifies the cited regulations as 191.11(a),  192.355(c),  192.465(a),  192.465(b),  192.465(d),  192.491(a),  192.605(a),  192.625(a),  192.723(a),  192.739(a),  192.747(a). The case was opened on 2011-04-06 and is reported as closed as of 2011-04-06. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220110003W_warning letter_04062011.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220110003W/220110003W_warning%20letter_04062011.pdf

220110003W_warning letter_04062011_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220110003W/220110003W_warning%20letter_04062011_text.pdf

220110003W_warning letter_04062011_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
April 6, 2011
Steven Boyd
Vice President Field Operations
Suburban Propane
3161 Cameron Park Drive, No 207
Cameron Park, CA 95682
CPF 2-2011-0003W
Dear Mr. Boyd:
On January 24-26, 2011, representatives of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) inspected facilities of two Suburban Propane (Suburban) liquefied
petroleum gas (LPG) pipeline systems in Largo and Seminole, Florida, pursuant to Chapter
601 of 49 United States Code. The Suburban LPG systems inspected served more than 100
customers each in the Center City subdivision in Largo, Florida, and in the Golfwoods Estates
subdivision in Seminole, Florida. The procedures and records were evaluated in Suburban’s
office in Clearwater, Florida.
As a result of the inspection, it appears that Suburban has committed probable violations of
the Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected
and the probable violations are:
1. §191.11 Distribution system: Annual report.
(a) Except as provided in paragraph (b) of this section, each operator of a
distribution pipeline system shall submit an annual report for that system on
Department of Transportation Form RSPA F 7100.1-1. This report must be
submitted each year, not later than March 15, for the preceding calendar year.
Suburban did not submit annual reports for the calendar years 2009 and 2010.
2. §192.355 Customer meters and regulators: Protection from damage.
….(c) Pits and vaults. Each pit or vault that houses a customer meter or regulator at
a place where vehicular traffic is anticipated, must be able to support that traffic.
(See also NFPA 59, Section 7.8.1, Protection of Container Accessories)



Suburban did not protect the vaults in which the regulators are housed from vehicular
traffic. These vaults do not appear to be capable of supporting vehicular traffic. Also, the
underground LPG tanks were not secured from unauthorized operation, no locks.
3. §192.465 External corrosion control: Monitoring.
(a)Each pipeline that is under cathodic protection must be tested at least once each
calendar year, but with intervals not exceeding 15 months, to determine whether the
cathodic protection meets the requirements of §192.463.
Suburban did not test each of its pipelines under cathodic protection in calendar years
2006, 2007, 2008, 2009, and 2010. The last cathodic protection monitoring of the Center
City system was conducted in April/May 2005. The last cathodic protection monitoring
of the Golfwood Estates system was conducted in November 2002.
4. §192.465 External corrosion control: Monitoring
.... (b) Each cathodic protection rectifier or other impressed current power source
must be inspected six times each calendar year, but with intervals not exceeding 2 1/2
months, to insure that it is operating.
Suburban did not inspect each rectifier in the Center City system six times each calendar
year, but at intervals not exceeding 2 1/2 months, to insure they were operating. The
Center City system has two rectifiers, which Suburban inspected only once a year in
April/May 2005, August 2007, and in January 2008 but not at all in 2006, 2009 and 2010.
Moreover, the PHMSA field inspection of the two rectifiers on January 25, 2011, found
that both the rectifiers were not operating and showed a zero amperage output. The
federal pipeline safety regulation in §192.465(d) require operators to take prompt remedial
action to correct any deficiencies indicated by the monitoring.
5. §192.465 External corrosion control: Monitoring
.... (d) Each operator shall take prompt remedial action to correct any deficiencies
indicated by the monitoring.
Suburban did not take prompt remedial action to correct deficiencies, i.e. unsatisfactory
levels of cathodic protection indicated by low1
pipe-to-soil (p/s) readings found during
cathodic protection surveys conducted in 2005.
The pipe-to-soil monitoring conducted in April/May 2005 on the Center City LPG System
showed an unsatisfactory low level of cathodic protection at the following test stations:
8996 Easy Street: - 503 mV 11474 Easy Street: - 550 mV
9018 Fairweather Dr.: - 483 mV 9139 Fairweather Dr.: - 484 mV
9038 Fairweather Dr.: - 495 mV 9125 Fairweather Dr.: - 650 mV
9195 Fairweather Dr.: - 800 mV 11376 92nd Street N: - 504 mV
11242 92nd Street N: - 350 mV
1 The criteria for cathodic protection are contained in 49 CFR Part 192, Appendix D. The criteria being
referenced in this letter is negative (cathodic) voltage of at least 850mV with reference to a saturated copper-
copper sulfate half cell. Accordingly, a “low” p/s reading is a reading less negative than 850mV.
2



Field tests at selected test stations conducted on the Center City LPG System during the
PHMSA inspection on January 25, 2011, revealed low p/s readings as follows:
11376 92nd Street N: - 265 mV 9195 Fairweather Dr.: - 700 mV
11543 Easy Street: - 550 mV
Field tests at selected test stations conducted on the Golfwoods Estates LPG System
during the PHMSA inspection on January 25, 2011, revealed low p/s readings as follows:
8256 Lark Street: - 204 mV 8319 Iris Avenue: - 410 mV
8126 Flamevine Av: - 348 mV 8518 Magnolia Dr.: - 252 mV
8641 Lantana Drive: - 327 mV 8697 Lantana Dr.: - 510 mV
Additionally, Suburban did not take prompt remedial action to repair a rectifier at 11565
92nd Way North and a rectifier located at 9050 Fairweather Dr., each of which was found
inoperative by the PHMSA inspectors on January 25, 2011.
6. §192.491 Corrosion control records.
(a) Each operator shall maintain records or maps to show the location of
cathodically protected piping, cathodic protection facilities, galvanic anodes, and
neighboring structures bonded to the cathodic protection system. Records or maps
showing a stated number of anodes, installed in a stated manner or spacing, need not
show specific distances to each buried anode.
(b) Each record or map required by paragraph (a) of this section must be retained
for as long as the pipeline remains in service.
(c) Each operator shall maintain a record of each test, survey, or inspection required
by this subpart in sufficient detail to demonstrate the adequacy of corrosion control
measures or that a corrosive condition does not exist. These records must be
retained for at least 5 years, except that records related to §§192.465(a) and (e) and
192.475(b) must be retained for as long as the pipeline remains in service.
Suburban did not have a revised and updated system map showing the location of galvanic
anodes, rectifiers and cathodically protected piping.
7. §192.605 Procedural manual for operations, maintenance, and emergencies
(a) General. Each operator shall prepare and follow for each pipeline, a manual of
written procedures for conducting operations and maintenance activities and for
emergency response. This manual must be reviewed and updated by the operator at
intervals not exceeding 15 months, but at least one each calendar year. This manual
must be prepared before operations of a pipeline system commence. Appropriate
parts of the manual must be kept at locations where operations and maintenance
activities are conducted.
Suburban did not properly prepare and follow a manual of written procedures for
conducting operations and maintenance activities and for emergency response. While the
operator had a manual dated January 3, 2011, the manual was generic and contained no
site specific operations and maintenance procedures or site specific procedures for
emergency response.
3



8. §192.625 Odorization of gas
(a) A combustible gas in a distribution line must contain a natural odorant or be
odorized so that at a concentration in air of one-fifth of the lower explosive limit, the
gas is readily detectable by a person with a normal sense of smell.
.... (f) To assure the proper concentration of odorant in accordance with this section,
each operator must conduct periodic sampling of combustible gases using an
instrument capable of determining the percentage of gas in air at which the odor
becomes readily detectable.
(See also NFPA 58, Section 4.2.3, LP-Gas Odorization)
Suburban did not conduct periodic sampling (“sniff tests”) to assure the proper
concentration of odorant using an instrument capable of determining the percentage of gas
in air at which the odor becomes readily detectable.
9. §192.723 Distribution systems: Leakage surveys.
(a) Each operator of a gas distribution system shall conduct periodic leakage surveys
in accordance with this section.
(b) The type and scope of the leakage control program must be determined by the
nature of the operations and the local conditions, but it must meet the following
minimum requirements:
(1) A leakage survey with leak detector equipment must be conducted in business
districts, including tests of the atmosphere in gas, electric, telephone, sewer, and
water system manholes, at cracks in pavement and sidewalks, and at other locations
providing an opportunity for finding gas leaks, at intervals not exceeding 15 months,
but at least once each calendar year.
Suburban did not conduct periodic leakage surveys with leak detector equipment in
business districts along its pipeline system at intervals not exceeding 15 months, but at
least once in calendar years 2009 and 2010. That is, Suburban did not provide any records
to demonstrate that it had conducted leakage surveys in business districts with leak
detector equipment in accordance with the prescribed intervals.
10. §192.723 Distribution systems: Leakage surveys.
(a) Each operator of a gas distribution system shall conduct periodic leakage surveys
in accordance with this section.
(b) The type and scope of the leakage control program must be determined by the
nature of the operations and the local conditions, but it must meet the following
minimum requirements:
.... (2) A leakage survey with leak detector equipment must be conducted outside
business districts as frequently as necessary, but at least once every 5 calendar years
at intervals not exceeding 63 months. However, for cathodically unprotected
distribution lines subject to § 192.465(e) on which electrical surveys for corrosion are
impractical, a leakage survey must be conducted at least once every 3 calendar years
at intervals not exceeding 39 months.
4



The operator did not conduct a residential gas leak survey with leak detector equipment at
intervals not exceeding 63 months but at least once every 5 calendar years. Moreover,
Suburban did not provide any records to demonstrate that it had conducted leakage
surveys outside of business districts with leak detector equipment in accordance with the
prescribed intervals.
11. §192.739 Pressure limiting and regulating stations: Inspection and testing.
(a) Each pressure limiting station, relief device (except rupture discs), and Pressure
regulating station and its equipment must be subjected at intervals not exceeding 15
months, but at least once each calendar year, to inspections and tests to determine
that it is–
(1) In good mechanical condition;
(2) Adequate from the standpoint of capacity and reliability of operation for the
service in which it is employed;
(3) Except as provided in paragraph (b) of this section, set to control or relieve at the
correct pressure consistent with the pressure limits of §192.201(a);; and
(4) Properly installed and protected from dirt, liquids, or other conditions that
might prevent proper operation.
Suburban had Fisher 64SR regulators installed on 500-gallon and 1000-gallon
underground LPG tanks. These regulators are ¾-inch in size with a ¼-inch orifice and
have pressure ratings of 250 psig at the inlet and 5-35 psig at the outlet. Suburban did not
inspect and test these regulators in calendar years 2009 and 2010. The regulator stability
test was last done in November 2002.
Suburban did not provide any records to demonstrate that the regulators are set to control
or relieve at the correct pressure consistent with the pressure limits of §192.201(a). That
is, there were no set points recorded for these regulators and the capacity at the inlet
pressure and the capacity at the outlet pressure were not calculated.
12. §192.747 Valve maintenance: Distribution systems.
(a) Each valve, the use of which may be necessary for the safe operation of a
distribution system, must be checked and serviced at intervals not exceeding 15
months, but at least once each calendar year.
Suburban did not check and service each valve in its distribution system that may be
necessary for the safe operation of its distribution system in calendar years 2009 and 2010.
The last valve inspection was conducted in November 2002.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed
$100,000 for each violation for each day the violation persists up to a maximum of
$1,000,000 for any related series of violations. We have reviewed the circumstances and
supporting documents involved in this case, and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct
the items identified in this letter. Failure to do so will result in Suburban Propane being
subject to additional enforcement action.
5



No reply to this letter is required. If you choose to reply, in your correspondence please refer
to CPF 2-2011-0003W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any
portion of your responsive material qualifies for confidential treatment under 5 U.S.C. 552(b),
along with the complete original document you must provide a second copy of the document
with the portions you believe qualify for confidential treatment redacted and an explanation of
why you believe the redacted information qualifies for confidential treatment under 5 U.S.C.
552(b).
Sincerely,
Wayne T. Lemoi
Director, Office of Pipeline Safety
PHMSA Southern Region
cc: Henry W. Howell
Customer Service Center Manager
Suburban Propane
775 Belleair Road
Clearwater, Florida 33756
Thomas Ross
General Manager
Suburban Propane
6991-15th Street East
Sarasota, Florida 34243
6

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/220110003W>
- Source ID: `phmsa-enforcement`
- SHA-256: `8acc914a2ad46722f4ff509a4fc1fdea9b7d0b568e19396da7ab44176b19aede`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T02:53:49.343Z
- Document slug: `phmsa-enforcement-220110003w`

### Source metadata

```json
{
  "cpf": "220110003W",
  "operator": "SUBURBAN PROPANE",
  "region": "Southern",
  "pipelineType": "GAS INTRASTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "191.11(a)",
    "192.355(c)",
    "192.465(a)",
    "192.465(b)",
    "192.465(d)",
    "192.491(a)",
    "192.605(a)",
    "192.625(a)",
    "192.723(a)",
    "192.739(a)",
    "192.747(a)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "220110003W_warning letter_04062011.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220110003W/220110003W_warning%20letter_04062011.pdf",
      "bytes": 339200,
      "category": "agency_document"
    },
    {
      "name": "220110003W_warning letter_04062011_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220110003W/220110003W_warning%20letter_04062011_text.pdf",
      "bytes": 39416,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "SUBURBAN PROPANE"
}
```