# AMERIGAS PROPANE LP — Warning Letter

**Citation:** CPF 220110004W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2011-04-06

CLOSED warning letter citing 192.465(b), 192.465(d), 192.467(d), 192.481(a), 192.491(c), 192.605(a).

## Document text

Warning Letter involving AMERIGAS PROPANE LP. PHMSA's enforcement data identifies the cited regulations as 192.465(b),  192.465(d),  192.467(d),  192.481(a),  192.491(c),  192.605(a). The case was opened on 2011-04-06 and is reported as closed as of 2011-04-06. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220110004W_warning letter_04062011.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220110004W/220110004W_warning%20letter_04062011.pdf

220110004W_warning letter_04062011_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220110004W/220110004W_warning%20letter_04062011_text.pdf

220110004W_warning letter_04062011_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
April 6, 2011
Mr. Eugene Bissell
President & CEO
Amerigas Propane LP
P.O.Box: 965
Valley Forge, PA 19482-0965
CPF 2-2011-0004W
Dear Mr. Bissell:
From February 28 to March 2, 2011, representatives of the Pipeline and Hazardous Materials
Safety Administration (PHMSA) inspected the procedures, records, and facilities of four
Amerigas Propane (Amerigas) liquefied petroleum gas (LPG) pipeline systems in
Jacksonville, Florida, pursuant to Chapter 601 of 49 United States Code. The Amerigas LPG
systems inspected served the Arlington 7, Arlington 610, San Jose, and San Mateo
sub-divisions.
As a result of the inspection, it appears that Amerigas has committed probable violations of
the Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected
and the probable violations are:
1. §192.465 External corrosion control: Monitoring.
(b) Each cathodic protection rectifier or other impressed current power source
must be inspected six times each calendar year, but with intervals not exceeding 2
1/2 months, to insure that it is operating.
... (d) Each operator shall take prompt remedial action to correct any deficiencies
indicated by the monitoring.
While Amerigas appears to have read its rectifiers on the Arlington 7, Arlington 610,
San Jose, and San Mateo sub-divisions systems every month in 2011, Amerigas had not
initiated any prompt remedial action to correct the deficiency found with the San Mateo
system rectifier during the monitoring in January and February in 2011.



The operator’s records show 0.001Amp current output on its San Mateo system rectifier
on January 26, 2011, and again on February 14, 2011; an indication that the rectifier was
not functioning properly. The PHMSA field inspection on March 1, 2011, found a zero
current output on the same San Mateo system rectifier, confirming that the rectifier was
not operating properly. Yet, Amerigas had not initiated a prompt remedial action to
correct the deficiency.
2. §192.465 External corrosion control: Monitoring.
(d) Each operator shall take prompt remedial action to correct any deficiencies
indicated by the monitoring.
Amerigas did not take prompt remedial action to correct deficiencies, i.e. unsatisfactory
levels of cathodic protection indicated by low1
pipe-to-soil (p/s) readings found during
cathodic protection surveys it conducted in 2008, 2009, and 2010.
The operator did not correct the following deficiencies indicated by p/s monitoring:
Arlington 610 System
2534 Lansdown Drive: - 710 mV (11/18/08); - 680 mV (11/23/09)
7335 Merrill Road: - 610 mV (11/10/08); -500 mV (11/29/10)
2472 Eastrill Drive: - 420 mV (11/23/2009)
2481 Eastrill Drive: - 540 mV (11/29/2010)
2658 Woolery Drive: - 630mV (11/23/2009); - 680 mV (11/29/2010)
In addition, p/s tests at selected test stations conducted on the Arlington 610 system
during the PHMSA inspection on March 1, 2011, revealed low p/s readings as follows:
2490 Woolery Drive: - 318 mV; Woolery creek crossing: - 710 mV
San Jose System
4462 Naranja Drive: - 480 mV (11/2010)
4332 Naranja Drive: - 690 mV (11/2010)
4015 Habana Street: - 840 mV (11/2010)
3977 Habana Street: - 460 mV (11/2009)
8137 Fresca Street: - 610 mV (11/2009)
8042 Naranja Drive: - 580 mV (11/2009)
8058 Argentine Drive: - 690 mV (10/26/2009); - 670 mV (2/2/2011)
In addition, p/s tests at selected test stations conducted on the San Jose system during
the PHMSA inspection on March 1, 2011, revealed low p/s readings as follows:
7854 Praver Drive West: - 500 mV
7808 Praver Drive West: - 500 mV
4462 Naranja Drive: - 780 mV
1 The criteria for cathodic protection are contained in 49 CFR Part 192, Appendix D. The criteria being
referenced in this letter is negative (cathodic) voltage of at least 850mV with reference to a saturated copper-
copper sulfate half cell. Accordingly, a “low” p/s reading is a reading less negative than 850mV.
2



San Mateo System
266 Claudia Drive - 840 mV (12/10)
261 Claudia Drive: - 750 mV (12/10)
11239 Inez Drive: - 510 mV (10/09)
255 Balsden Road: - 500 mV (10/09)
11307 Renee Drive: - 530 mV (10/09)
11536 Princess Lane: - 440 mV (10/09)
In addition, p/s tests at selected test stations conducted on the San Mateo system during
the PHMSA inspection on March 1, 2011, revealed low p/s readings as follows:
11501 Inez Drive: - 482 mV
11320 Renee Drive: - 502 mV
266 Claudia Drive: - 780 mV
Arlington 7 System
3022 Red Oak Drive: - 750 mV (11/10/2009); - 570 mV (2/11/2010)
In addition, p/s tests at selected test stations conducted on the Arlington 7 system during
the PHMSA inspection on March 1, 2011, revealed low p/s readings as follows:
3022 Red Oak Drive: - 438 mV
Test station outside the fenced tank farm: - 630 mV
3. §192.467 External corrosion control: Electrical isolation.
(a) Each buried or submerged pipeline must be electrically isolated from other
underground metallic structures, unless the pipeline and the other structures are
electrically interconnected and cathodically protected as a single unit.
... (d) Inspection and electrical tests must be made to assure that electrical
isolation is adequate.
Amerigas did not inspect or conduct electrical tests to assure that electrical isolation was
adequate for its 1¼-inch steel pipe inside a 2-inch casing at the Woolery Creek Crossing
on the Arlington 610 system. During the PHMSA field inspection on March 1, 2011, a
low pipe-to-soil potential of - 770 mV was measured on the pipe and a casing-to-soil
potential of - 710 mV was measured on the casing. Cathodic protection readings within
100 mV on a casing and carrier pipe could indicate a possible electrical short between
the two pipes. Yet, Amerigas did not provide any records to demonstrate that it had
inspected or electrically tested for adequate electrical isolation between the pipe and the
casing at this location.
4. §192.481 Atmospheric corrosion control: Monitoring.
(a) Each operator must inspect each pipeline or portion of pipeline that is exposed
to the atmosphere for evidence of atmospheric corrosion, as follows:
If the pipeline is located: Onshore.... Then the frequency of inspection is:
At least once every 3 calendar years, but with intervals not exceeding 39 months.
3



Amerigas did not inspect each pipeline or portion of pipeline that is exposed to the
atmosphere for evidence of atmospheric corrosion within the prescribed time intervals.
The atmospheric corrosion monitoring on the Arlington 610 system was conducted in
August 2002 and November 2008, which exceeds the three calendar year time limit.
5. §192.491 Corrosion control records.
(a) Each operator shall maintain records or maps to show the location of
cathodically protected piping, cathodic protection facilities, galvanic anodes, and
neighboring structures bonded to the cathodic protection system. Records or maps
showing a stated number of anodes, installed in a stated manner or spacing, need
not show specific distances to each buried anode.
(b) Each record or map required by paragraph (a) of this section must be retained
for as long as the pipeline remains in service.
(c) Each operator shall maintain a record of each test, survey, or inspection
required by this subpart in sufficient detail to demonstrate the adequacy of
corrosion control measures or that a corrosive condition does not exist. These
records must be retained for at least 5 years, except that records related to
§§192.465(a) and (e) and 192.475(b) must be retained for as long as the pipeline
remains in service.
Amerigas did not have a revised and updated system map showing the location of
galvanic anodes, rectifiers and cathodically protected piping.
6. §192.605 Procedural manual for operations, maintenance, and emergencies
(a) General. Each operator shall prepare and follow for each pipeline, a manual
of written procedures for conducting operations and maintenance activities and for
emergency response. This manual must be reviewed and updated by the operator
at intervals not exceeding 15 months, but at least one each calendar year. This
manual must be prepared before operations of a pipeline system commence.
Appropriate parts of the manual must be kept at locations where operations and
maintenance activities are conducted.
Amerigas did not properly prepare and follow a manual of written procedures for
conducting operations and maintenance activities and for emergency response. The
operator did not have written procedures to address the following:
− A time frame for prompt remedial actions in the case of unsatisfactory levels of
cathodic protection,
− Internal corrosion,
− Alternating current (A/C) interference,
− Stray currents,
− Critical bonds and interference bonds; and
− Shorted casings.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed
$100,000 for each violation for each day the violation persists up to a maximum of
4



$1,000,000 for any related series of violations. We have reviewed the circumstances and
supporting documents involved in this case, and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct
the items identified in this letter. Failure to do so will result in Amerigas Propane LP being
subject to additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer
to CPF 2-2011-0004W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any
portion of your responsive material qualifies for confidential treatment under 5 U.S.C. 552(b),
along with the complete original document you must provide a second copy of the document
with the portions you believe qualify for confidential treatment redacted and an explanation of
why you believe the redacted information qualifies for confidential treatment under 5 U.S.C.
552(b).
Sincerely,
Wayne T. Lemoi
Director, Office of Pipeline Safety
PHMSA Southern Region
cc: Michael Johnson
Manager
855 Talleyrand Ave.
Jacksonville, FL 32206
Joe Rodriguez
Area Manager
29216 Hwy. 27
Dundee, FL 33838
5

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/220110004W>
- Source ID: `phmsa-enforcement`
- SHA-256: `5df3cb82d3cc4d00f91be34e78079ab4ed1d5c0e8e116081a65b5eb26005a495`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T13:55:01.569Z
- Document slug: `phmsa-enforcement-220110004w`

### Source metadata

```json
{
  "cpf": "220110004W",
  "operator": "AMERIGAS PROPANE LP",
  "region": "Southern",
  "pipelineType": "GAS INTRASTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.465(b)",
    "192.465(d)",
    "192.467(d)",
    "192.481(a)",
    "192.491(c)",
    "192.605(a)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "220110004W_warning letter_04062011.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220110004W/220110004W_warning%20letter_04062011.pdf",
      "bytes": 249301,
      "category": "agency_document"
    },
    {
      "name": "220110004W_warning letter_04062011_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/220110004W/220110004W_warning%20letter_04062011_text.pdf",
      "bytes": 35188,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "AMERIGAS PROPANE LP"
}
```