# CENTRA PIPELINE MINNESOTA INC. — Notice of Amendment

**Citation:** CPF 32025012NOA  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2025-05-05

CLOSED notice of amendment citing 192.615(b)(2), 192.615(b)(3), 192.805(c), 192.805(h), 192.935(c), 192.935(f), 192.947.

## Document text

Notice of Amendment involving CENTRA PIPELINE MINNESOTA INC.. PHMSA's enforcement data identifies the cited regulations as 192.615(b)(2),  192.615(b)(3),  192.805(c),  192.805(h),  192.935(c),  192.935(f),  192.947. The case was opened on 2025-05-05 and is reported as closed as of 2025-09-10. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

32025012NOA_Closure Letter_09102025_(24-317618).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Closure%20Letter_09102025_(24-317618).pdf

32025012NOA_Closure Letter_09102025_(24-317618)_txt.pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Closure%20Letter_09102025_(24-317618)_txt.pdf

32025012NOA_Notice of Amendment_05052025_(24-317618).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Notice%20of%20Amendment_05052025_(24-317618).pdf

32025012NOA_Notice of Amendment_05052025_(24-317618)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Notice%20of%20Amendment_05052025_(24-317618)_text.pdf

32025012NOA_Operator Response to Notice_06032025_(24-317618).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Operator%20Response%20to%20Notice_06032025_(24-317618).pdf

32025012NOA_Closure Letter_09102025_(24-317618)_txt.pdf

U.S. Department
of Transportation
Pipeline and Hazardous
Materials Safety
901 Locust Street, Suite 480
Kansas City, MO 64106
VIA ELECTRONIC MAIL TO: tkarry@efgroupllc.com; ppowers@efgroupllc.com;
jbrophy@efgroupllc.com; jonathan.wolfgram@state.mn.us
September 10, 2025
Mr. Todd Karry, President/CEO
Centra Pipeline Minnesota, Inc.
33717 Woodward Avenue, #600
Birmingham, MI 48009
RE: CPF 3-2025-012-NOA
Dear Mr. Karry:
From September 16 to September 19, 2024, representatives of the Minnesota Office of Pipeline
Safety (MNOPS), acting as interstate agents for the Pipeline and Hazardous Materials Safety
Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code (U.S.C.), inspected
the procedures for integrity management and operator qualification of Central Pipeline Minnesota,
Inc.(Centra) at the MNOPS offices in St. Paul, Minnesota. On May 5, 2025, pursuant to 49 CFR
§ 190.206, PHMSA issued a Notice of Amendment which proposed amendment of Centra’s
procedures.
Centra submitted its amended procedures on June 3, 2025 and September 10, 2025. PHMSA has
reviewed the amended procedures, and it appears that the inadequacies outlined in the Notice of
Amendment have been corrected.
This letter is to inform you that no further action is necessary, and this case is now closed. Thank
you for your cooperation.
Sincerely,
David Barrett
Acting Director, Central Region, Office of Pipeline Safety
Pipeline and Hazardous Materials Safety Administration
cc: Phillip Powers, Director Pipeline Operations, Central Pipeline Minnesota, Inc.
Joe Brophy, VP/General Manager, Central Pipeline Minnesota, Inc.
Jonathan Wolfgram, Deputy Director, MNOPS

32025012NOA_Notice of Amendment_05052025_(24-317618)_text.pdf

NOTICE OF AMENDMENT
VIA ELECTRONIC MAIL TO: tkarry@efgroupllc.com; ppowers@efgroupllc.com;
jborphy@efgroupllc.com
May 5, 2025
Mr. Todd Karry
President & CEO
Centra Pipeline Minnesota, Inc.
33717 Woodward Ave. #600
Birmingham, MI 48009
CPF 3-2025-012-NOA
Dear Mr. Karry:
From September 16 to September 19, 2024, representatives of the Minnesota Office of Pipeline
Safety (MNOPS), acting as interstate agents for the Pipeline and Hazardous Materials Safety
Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code (U.S.C.), inspected
at MNOPS’s offices in St. Paul, Minnesota, Central Pipeline Minnesota, Inc.’s (Centra)
procedures for integrity management and operator qualification.
As a result of the inspection, PHMSA has identified the apparent inadequacies found within
Centra’s plans or procedures. The items inspected and the inadequacies identified are described
below:
1. § 192.615 Emergency plans.
(a) . . . .
(b) Each operator shall:
(1) . . . .
(2) Train the appropriate operating personnel to assure that they are knowledgeable
of the emergency procedures and verify that the training is effective.
Centra’s emergency procedure EMG-PRO-001, “Management of Gas Emergencies,” did not
contain guidance to assure that personnel are knowledgeable of the emergency procedures
that they are responsible for conducting, in accordance with the requirements of
§ 192.615(b)(2). The procedures within EMG-PRO-001 were too general in nature to



adequately train the appropriate operating personnel. EMG-PRO-001 did not contain any
specificity on what particular type of training personnel must receive. Therefore, Centra
must revise EMG-PRO-001 in accordance with § 192.615.
2. § 192.615 Emergency plans.
(a) . . . .
(b) Each operator shall:
(1) . . . .
(3) Review employee activities to determine whether the procedures were effectively
followed in each emergency.
Centra's emergency procedure EMG-PRO-001, “Management of Gas Emergencies,” did not
require the review of employee activities to determine the effectiveness of a procedure following
each emergency, per the requirements of § 192.615(b)(3). Section 5 of EMG-PRO-001 did not
contain any procedures on how Centra will conduct the review to assure the effectiveness of the
emergency response procedures and how that review will be documented. Therefore, Centra
must revise EMG-PRO-001 in accordance with § 192.615(b)(3).
3. § 192.805 Qualification program.
Each operator shall have and follow a written qualification program. The program
shall include provisions to:
(a) . . . .
(c) Allow individuals that are not qualified pursuant to this subpart to perform a
covered task if directed and observed by an individual that is qualified;
Centra’s Operator Qualification (OQ) Plan, GEN-PRO-007, “Operator Qualification” (OQ Plan),
did not contain adequate procedures to ensure that personnel that are not qualified to perform a
covered task were allowed to do so if directed and observed by a qualified individual, per the
requirements of § 192.805(c). Centra’s OQ Plan was inadequate because it did not have any
“span of control” provisions which would be used to determine how many unqualified personnel
can conduct a task under the supervision of a qualified individual. Centra indicated that in
practice its “span of control” did not exceed a 1-to-1 ratio; however, the regulations do not allow
for an unqualified individual to perform covered tasks such as welding and making plastic pipe
joints.1 For these covered tasks the ratio would be 1:0; that is, “span of control” would not be
allowed. Therefore, Centra must revise its OQ Plan to define the number of individuals within a
“span of control” and when "span of control” may not be used, in accordance with § 192.805(c).
4. § 192.805 Qualification program.
Each operator shall have and follow a written qualification program. The program
shall include provisions to:
(a) . . . .
1 See 49 CFR §§ 192.229(c) and 192.285(c).



(h) After December 16, 2004, provide training, as appropriate, to ensure that
individuals performing covered tasks have the necessary knowledge and skills to
perform the tasks in a manner that ensures the safe operation of pipeline facilities;
Centra’s OQ Plan did not include procedures for providing training to ensure individuals
performing covered tasks have the necessary knowledge and skills to perform the tasks, per the
requirements of § 192.805(h). OQ Plan section 6 contained guidance to re-train and re-evaluate
personnel, but section 6 did not contain any guidance on the initial training of individuals.
Therefore, Centra must revise its OQ Plan in accordance with § 192.805(h).
5. § 192.935 What additional preventive and mitigative measures must an operator
take?
(a) . . . .
(c) Risk analysis for gas releases and protection against ruptures. If an operator
determines, based on a risk analysis, that a rupture-mitigation valve (RMV) or
alternative equivalent technology would be an efficient means of adding protection
to a high-consequence area (HCA) in the event of a gas release, an operator must
install the RMV or alternative equivalent technology. In making that
determination, an operator must, at least, evaluate the following factors—timing of
leak detection and pipe shutdown capabilities, the type of gas being transported,
operating pressure, the rate of potential release, pipeline profile, the potential for
ignition, and location of nearest response personnel. An RMV or alternative
equivalent technology installed under this paragraph must meet all of the other
applicable requirements in this part.
Centra’s procedure, INT-PRO-008, “Preventive and Mitigative Measures” (INT-PRO-008), did
not contain procedures for determining, based on a risk analysis, whether a rupture-mitigation
valve (RMV) or alternative equivalent technology would be an efficient means of adding
protection to a high-consequence area (HCA) in the event of a gas release, per the requirements
of § 192.935(c). Section 6 of INT-PRO-008 briefly mentioned the use of automatic control
valve or a remote-control valve as a mitigative measure, but it did not include any requirements
for determining whether to install or use those valves. INT-PRO-008 also did not include a
procedure to determine whether the use of an alternative equivalent technology would be an
efficient means of adding protection. Therefore, Centra must revise INT-PRO-008 in accordance
with § 192.935(c).
6. § 192.935 What additional preventive and mitigative measures must an operator
take?
(a) . . . .
(f) Periodic evaluations. Risk analyses and assessments conducted under paragraph
(c) of this section must be reviewed by the operator and certified by a senior
executive of the company, for operational matters that could affect rupture-
mitigation processes and procedures. Review and certification must occur once per
calendar year, with the period between reviews not to exceed 15 months, and must



7. also occur within 3 months of an incident or safety-related condition, as those terms
are defined at §§ 191.3 and 191.23, respectively.
Centra’s INT-PRO-008 did not contain procedures for requiring that any risk analysis and
assessments conducted under § 192.935(c) be reviewed and certified by a senior executive of the
company, per the requirements of § 192.935(f). INT-PRO-008 also did not contain the
requirement to review and certify the analysis and assessments once a year not to exceed 15
months, and that it must occur within 3 months of a safety related condition. Therefore, Centra
must revise its procedures in accordance with § 192.935(f).
§ 192.947 What records must an operator keep?
An operator must maintain, for the useful life of the pipeline, records that
demonstrate compliance with the requirements of this subpart. At minimum, an
operator must maintain the following records for review during an inspection.
Centra's written procedures did not specify that records used to demonstrate compliance with the
requirements of subpart O must be maintained for the useful life of the pipeline, per the
requirements of § 192.947. Therefore, Centra must revise its procedures to meet the
requirements of §§ 192.947(a) through (i).
Response to this Notice
This Notice is provided pursuant to 49 U.S.C. § 60108(a) and 49 CFR § 190.206. Enclosed as
part of this Notice is a document entitled Response Options for Pipeline Operators in
Enforcement Proceedings.
Please refer to this document and note the response options. Be advised that all material you
submit in response to this enforcement action is subject to being made publicly available. If you
believe that any portion of your responsive material qualifies for confidential treatment under 5
U.S.C. § 552(b), along with the complete original document you must provide a second copy of
the document with the portions you believe qualify for confidential treatment redacted and an
explanation of why you believe the redacted information qualifies for confidential treatment
under 5 U.S.C. § 552(b).
Following the receipt of this Notice, you have 30 days to submit written comments, revised
procedures, or a request for a hearing under § 190.211. If you do not respond within 30 days of
receipt of this Notice, this constitutes a waiver of your right to contest the allegations in this
Notice and authorizes the Associate Administrator for Pipeline Safety to find facts as alleged in
this Notice without further notice to you and to issue an Order Directing Amendment. If your
plans or procedures are found inadequate as alleged in this Notice, you may be ordered to amend
your plans or procedures to correct the inadequacies (49 C.F.R. § 190.206). If you are not
contesting this Notice, we propose that you submit your amended procedures to my office within
90 days of receipt of this Notice. This period may be extended by written request for good
cause. Once the inadequacies identified herein have been addressed in your amended procedures,
this enforcement action will be closed.



It is requested (not mandated) that Centra Pipeline Minnesota Inc maintain documentation of the
safety improvement costs associated with fulfilling this Notice of Amendment (preparation/
revision of plans, procedures) and submit the total to Gregory A. Ochs, Director, Central Region,
Pipeline and Hazardous Materials Safety Administration. In correspondence concerning this
matter, please refer to CPF 3-2025-012-NOPV and, for each document you submit, please
provide a copy in electronic format whenever possible.
Sincerely,
Gregory A. Ochs
Director, Central Region, Office of Pipeline Safety
Pipeline and Hazardous Materials Safety Administration
cc: Phillip Powers, Director Pipeline Operations, ppowers@efgroupllc.com
Joe Brophy, VP/General Manager, jborphy@efgroupllc.com
Enclosure: Response Options for Pipeline Operators in Enforcement Proceedings

32025012NOA_Closure Letter_09102025_(24-317618).pdf

U.S. Department
of Transportation
Pipeline and Hazardous
Materials Safety
901 Locust Street, Suite 480
Kansas City, MO 64106
VIA ELECTRONIC MAIL TO: tkarry@efgroupllc.com; ppowers@efgroupllc.com;
jbrophy@efgroupllc.com; jonathan.wolfgram@state.mn.us
September 10, 2025
Mr. Todd Karry, President/CEO
Centra Pipeline Minnesota, Inc.
33717 Woodward Avenue, #600
Birmingham, MI 48009
RE: CPF 3-2025-012-NOA
Dear Mr. Karry:
From September 16 to September 19, 2024, representatives of the Minnesota Office of Pipeline
Safety (MNOPS), acting as interstate agents for the Pipeline and Hazardous Materials Safety
Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code (U.S.C.), inspected
the procedures for integrity management and operator qualification of Central Pipeline Minnesota,
Inc.(Centra) at the MNOPS offices in St. Paul, Minnesota. On May 5, 2025, pursuant to 49 CFR
§ 190.206, PHMSA issued a Notice of Amendment which proposed amendment of Centra’s
procedures.
Centra submitted its amended procedures on June 3, 2025 and September 10, 2025. PHMSA has
reviewed the amended procedures, and it appears that the inadequacies outlined in the Notice of
Amendment have been corrected.
This letter is to inform you that no further action is necessary, and this case is now closed. Thank
you for your cooperation.
Sincerely,
David Barrett
Acting Director, Central Region, Office of Pipeline Safety
Pipeline and Hazardous Materials Safety Administration
cc: Phillip Powers, Director Pipeline Operations, Central Pipeline Minnesota, Inc.
Joe Brophy, VP/General Manager, Central Pipeline Minnesota, Inc.
Jonathan Wolfgram, Deputy Director, MNOPS

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/32025012NOA>
- Source ID: `phmsa-enforcement`
- SHA-256: `30154a639efc3fff0ffaa81134284651c01d089a6ae4a8f68e2cb61e99da4b8f`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T22:18:34.436Z
- Document slug: `phmsa-enforcement-32025012noa`

### Source metadata

```json
{
  "cpf": "32025012NOA",
  "operator": "CENTRA PIPELINE MINNESOTA INC.",
  "region": "Central",
  "pipelineType": "INTERSTATE GAS TRANSMISSION",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.615(b)(2)",
    "192.615(b)(3)",
    "192.805(c)",
    "192.805(h)",
    "192.935(c)",
    "192.935(f)",
    "192.947"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 5,
  "attachments": [
    {
      "name": "32025012NOA_Closure Letter_09102025_(24-317618).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Closure%20Letter_09102025_(24-317618).pdf",
      "bytes": 227038,
      "category": "agency_document"
    },
    {
      "name": "32025012NOA_Closure Letter_09102025_(24-317618)_txt.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Closure%20Letter_09102025_(24-317618)_txt.pdf",
      "bytes": 158593,
      "category": "agency_document"
    },
    {
      "name": "32025012NOA_Notice of Amendment_05052025_(24-317618).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Notice%20of%20Amendment_05052025_(24-317618).pdf",
      "bytes": 304888,
      "category": "agency_document"
    },
    {
      "name": "32025012NOA_Notice of Amendment_05052025_(24-317618)_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Notice%20of%20Amendment_05052025_(24-317618)_text.pdf",
      "bytes": 195391,
      "category": "agency_document"
    },
    {
      "name": "32025012NOA_Operator Response to Notice_06032025_(24-317618).pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/32025012NOA/32025012NOA_Operator%20Response%20to%20Notice_06032025_(24-317618).pdf",
      "bytes": 107558,
      "category": "party_submission"
    }
  ],
  "extractedAgencyDocumentCount": 3,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "CENTRA PIPELINE MINNESOTA INC."
}
```