# LA STORAGE, LLC — Warning Letter

**Citation:** CPF 420181009W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2018-07-19

CLOSED warning letter citing 192.465(a), 192.465(d), 192.605(b)(3), 192.736(b).

## Document text

Warning Letter involving LA STORAGE, LLC. PHMSA's enforcement data identifies the cited regulations as 192.465(a),  192.465(d),  192.605(b)(3),  192.736(b). The case was opened on 2018-07-19 and is reported as closed as of 2018-07-19. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

420181009W_Warning Letter_07192018.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420181009W/420181009W_Warning%20Letter_07192018.pdf

420181009W_Warning Letter_07192018_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420181009W/420181009W_Warning%20Letter_07192018_text.pdf

420181009W_Warning Letter_07192018_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
July 19, 2018
John Pirraglia
Vice President
LA Storage, LLC
2925 Briarpark Dr., Suite 850
Houston, TX 77042
CPF 4-2018-1009W
Dear Mr. Pirraglia:
On July 10 - 11, and September 25 - 28, 2017, representatives of the Pipeline and Hazardous
Materials Safety Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code
(U.S.C.) inspected your LA Storage, LLC (LAS) facilities in Houston, Texas and Lake Charles,
Louisiana.
As a result of the inspection, it is alleged that you have committed probable violations of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The items inspected
and the probable violations are:
1. §192.736 Compressor stations: Gas detection.
(b) Except when shutdown of the system is necessary for maintenance under
paragraph (c) of this section, each gas detection and alarm system required by this
section must
(1) Continuously monitor the compressor building for a concentration of gas
in air of not more than 25 percent of the lower explosive limit; and
(2) If that concentration of gas is detected, warn persons about to enter the
building and persons inside the building of the danger.



LAS failed to provide adequate warning to persons entering compressor building from the
southwest side. During the field inspection, PHMSA inspector observed LAS test the Ragley
Compressor Station gas detection for indication of gas at 5% LEL. The gas detection system has
three visual alarms; one strobe light outside on the northeast corner of the compressor building,
one strobe light outside on the southwest corner of the compressor building, and a strobe light
inside the compressor building. There are no audible alarms. LA Storage used calibrated gas to
test sensor S4000C 1500AA at 5% LEL. The sensor detected gas at 5% and gave indication to
the control room as well as inside the compressor station. Additionally, the northeast strobe light
outside of the compressor building illuminated as expected. However, the southwest strobe light
outside of the compressor building failed to illuminate to give indication of gas leak inside the
compressor building.
On September 28, 2017 LAS repaired light, replaced bulb and provided record FORM OM500-
02 – Compressor Station Gas Detector Calibration/Repair Report which documents the repair
actions and Work Order # #16003.
2. §192.605 Procedural manual for operations, maintenance, and emergencies
(b) Maintenance and normal operations. The manual required by paragraph (a) of
this section must include procedures for the following, if applicable, to provide safety
during maintenance and operations.
(3) Making construction records, maps, and operating history available to
appropriate operating personnel.
LAS failed to document the correct MAOP on their maps, records, and control room console. At
the time of inspection, the PHMSA inspector found the MAOP on LA Storage records, maps, and
control room console for the LAS pipeline to be inaccurate. The records, maps, and console all
listed a MAOP of 1284psi which is actually the MOP of LAS pipeline. The MAOP for LAS
pipeline is 1460psi.
On October 2, 2017 LAS fixed maps, records, and screen shot of control room console with the
correct MOP and MAOP for LAS pipeline.
3. §192.465 External corrosion control: Monitoring.
(a) Each pipeline that is under cathodic protection must be tested at least once each
calendar year, but with intervals not exceeding 15 months, to determine whether the
cathodic protection meets the requirements of §192.463. However, if tests at those
intervals are impractical for separately protected short sections of mains or
transmission lines, not in excess of 100 feet (30 meters), or separately protected service
lines, these pipelines may be surveyed on a sampling basis. At least 10 percent of these
protected structures, distributed over the entire system must be surveyed each
calendar year, with a different 10 percent checked each subsequent year, so that the
entire system is tested in each 10-year period.
2



(d) Each operator shall take prompt remedial action to correct any deficiencies
indicated by the monitoring.
LA Storage failed to take prompt remedial action to correct a deficiency with the Transco
Inter./Targa Crossing test station.
After reviewing pipe-to-soil potential survey records for July 2016 and July 2017 the PHMSA
inspector found Transco Inter./Targa Crossing test lead was missing. At the time of inspection,
September 2017, the test station was still missing and there was no work order in place to address
this deficiency.
On October 5, 2017 LAS provided an inspection report, pictures, and Work Order #15988
documents on the repair of the test lead at the Transco/Targa crossing.
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$209,002 per violation per day the violation persists, up to a maximum of $2,090,022 for a related
series of violations. For violations occurring prior to November 2, 2015, the maximum penalty
may not exceed $200,000 per violation per day, with a maximum penalty not to exceed $2,000,000
for a related series of violations. We have reviewed the circumstances and supporting documents
involved in this case, and have decided not to conduct additional enforcement action or penalty
assessment proceedings at this time. We advise you to correct the item(s) identified in this letter.
Failure to do so will result in LA Storage, LLC being subject to additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 4-2018-1009W. Be advised that all material you submit in response to this enforcement
action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the
complete original document you must provide a second copy of the document with the portions
you believe qualify for confidential treatment redacted and an explanation of why you believe the
redacted information qualifies for confidential treatment under 5 U.S.C. 552(b).
Sincerely,
Mary L. McDaniel, P.E.
Director, Southwest Region
Pipeline and Hazardous Materials Safety Administration
3

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/420181009W>
- Source ID: `phmsa-enforcement`
- SHA-256: `1e32904ab77d2945643108bd410cecdb97e305ca76eb9d61ecf401f17ee070ab`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-23T17:55:01.051Z
- Document slug: `phmsa-enforcement-420181009w`

### Source metadata

```json
{
  "cpf": "420181009W",
  "operator": "LA STORAGE, LLC",
  "region": "Southwest",
  "pipelineType": "GAS INTERSTATE ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "192.465(a)",
    "192.465(d)",
    "192.605(b)(3)",
    "192.736(b)"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 2,
  "attachments": [
    {
      "name": "420181009W_Warning Letter_07192018.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/420181009W/420181009W_Warning%20Letter_07192018.pdf",
      "bytes": 77392,
      "category": "agency_document"
    },
    {
      "name": "420181009W_Warning Letter_07192018_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/420181009W/420181009W_Warning%20Letter_07192018_text.pdf",
      "bytes": 99918,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "LA STORAGE, LLC"
}
```