# TITAN ALASKA LNG — Warning Letter

**Citation:** CPF 520173003W  
**Type / status:** enforcement / historical  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2017-08-30

CLOSED warning letter citing 193.2637.

## Document text

Warning Letter involving TITAN ALASKA LNG. PHMSA's enforcement data identifies the cited regulation as 193.2637. The case was opened on 2017-08-30 and is reported as closed as of 2017-08-30. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

520173003W_Operator Response To Notice_10052017.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520173003W/520173003W_Operator%20Response%20To%20Notice_10052017.pdf

520173003W_Warning Letter_08302017.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520173003W/520173003W_Warning%20Letter_08302017.pdf

520173003W_Warning Letter_08302017_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520173003W/520173003W_Warning%20Letter_08302017_text.pdf

520173003W_Warning Letter_08302017_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
August 30, 2017
Mr. Daniel W. Britton
President / CEO
Titan Alaska LNG
3408 International Street
Fairbanks, AK 99701
CPF 5-2017-3003W
Dear Mr. Britton:
On March 13 through 16, 2017, a representative of the Pipeline and Hazardous Materials
Safety Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code,
inspected Titan Alaska LNG’s (Titan) records and procedures at the LNG facility near Point
MacKenzie, Alaska.
As a result of the inspection, it is alleged that you have committed a probable violation of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The items
inspected and the probable violation is:
1. §193.2637 Remedial measures.
Prompt corrective or remedial action must be taken whenever an operator learns
by inspection or otherwise that atmospheric, external, or internal corrosion is not
controlled as required by this subpart.
Coffman Engineering recommended in reports dated 2015 and 2016 that pipeline supports
and pipeline isolation be installed to prevent corrosion of the carrier pipe. The pipeline rests
on support members which are not isolated with a dielectric pad, this has caused external
corrosion at several locations on the underside of the pipeline, at the 6 o’clock



position. Coffman Engineering made note of this during their audits, but Titan, has yet to
remedy. Additionally, no record of the repair was made available at the time of the
inspection.
As of April 27, 2017, under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a
civil penalty not to exceed $209,002 per violation per day the violation persists up to a
maximum of $2,090,022 for a related series of violations. Also, for LNG facilities, an
additional penalty of not more than $76,352 for each violation may be imposed. We have
reviewed the circumstances and supporting documents involved in this case, and have decided
not to conduct additional enforcement action or penalty assessment proceedings at this time.
We advise you to correct the item identified in this letter. Failure to do so will result in Titan
Alaska LNG being subject to additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer
to CPF 5-2017-3003W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any
portion of your responsive material qualifies for confidential treatment under 5 U.S.C. 552(b),
along with the complete original document you must provide a second copy of the document
with the portions you believe qualify for confidential treatment redacted and an explanation of
why you believe the redacted information qualifies for confidential treatment under 5 U.S.C.
552(b).
Sincerely,
Kim West
Acting Director, Western Region
Pipeline and Hazardous Materials Safety Administration
cc: PHP-60 Compliance Registry
PHP-500 R. Guisinger (#155012)

## Provenance

- Official: Yes
- Source: <https://primis.phmsa.dot.gov/enforcement-data/case/520173003W>
- Source ID: `phmsa-enforcement`
- SHA-256: `ccd7f247c2d322379ee50c55664aaee324acc120c9ff7ccbec73c15a1bcd86e9`
- Retrieved: 2026-08-20T04:44:44.458Z
- Exported: 2026-08-22T20:16:39.556Z
- Document slug: `phmsa-enforcement-520173003w`

### Source metadata

```json
{
  "cpf": "520173003W",
  "operator": "TITAN ALASKA LNG",
  "region": "Western",
  "pipelineType": "INTRASTATE LNG ONSHORE",
  "caseStatus": "CLOSED",
  "citedSections": [
    "193.2637"
  ],
  "dataAsOf": "08/04/2026 12PM",
  "caseDataAsOf": "2026-08-04",
  "attachmentCount": 3,
  "attachments": [
    {
      "name": "520173003W_Operator Response To Notice_10052017.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/520173003W/520173003W_Operator%20Response%20To%20Notice_10052017.pdf",
      "bytes": 47517,
      "category": "party_submission"
    },
    {
      "name": "520173003W_Warning Letter_08302017.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/520173003W/520173003W_Warning%20Letter_08302017.pdf",
      "bytes": 63773,
      "category": "agency_document"
    },
    {
      "name": "520173003W_Warning Letter_08302017_text.pdf",
      "url": "https://primis.phmsa.dot.gov/enforcement-documents/520173003W/520173003W_Warning%20Letter_08302017_text.pdf",
      "bytes": 115092,
      "category": "agency_document"
    }
  ],
  "extractedAgencyDocumentCount": 1,
  "attachmentPolicy": "Official attachment links are retained. Agency-issued documents may also include a verified local PDF and page-level text representation.",
  "jurisdiction": "US",
  "operatorName": "TITAN ALASKA LNG"
}
```