08-0255 response to Tyco Safety Products concerning 173.309.

## Document text

<<<PAGE 1>>>

U.S. Department of Transportation
Pipeline and Hazardous Materials
Safety Administration
1200 New Jersey Ave. S.E.
Washington, D.C. 20590
Mr. Richard Seaburg
Quality Assurance Manager
Tyco Safety Products
One Stanton Street
Marinette, WI 54143-2542
Ref. No. 08-0255
Dear Mr. Seaburg:
This responds to your October 6,2008 letter requesting clarification of the fire extinguisher
requirements in 5 173.309 of the Hazardous Materials Regulations (HMR; 49 CFR Parts 171-
180). You state your company manufactures cylinders under the exception in 5 173.309 for
fire extinguishers and provided data sheets and drawings. The cylinders are filled with a
pressurized wet chemical extinguishing agent (potassium carbonate solution). You ask if the
cylinders meet the requirements in 6 173.309 for fire extinguishers.
The answer is no. The requirements in !j 173.309 are applicable to cylinders used as portable
fire extinguishers. According to the data sheets and drawings you submitted, your non-DOT
specification cylinders are fitted with fusible links, have no nozzles, and are designed for use
as fixed fire suppression systems. When transported, each cylinder must be described with
the name of its compressed gas contents followed by the qualifying word "mixture" or
"solution" as appropriate. See 172.101(b)(l). The potassium carbonate extinguishing
agent is not a regulated material and, therefore, not subject to the HMR. The outside package
must be properly marked and labeled in accordance with Part 172. Your company may be
interested in applying for a special permit under the procedures in 49 CFR 107.105.
We apologize for the earlier misinformation regarding the transportation of these cylinders.
Please contact us if you require additional assistance.
Sincerely, d
Hattie L. Mitchell
Chief, Regulatory Review and Reinvention
Office of Hazardous Materials Standards

<<<PAGE 2>>>

Fire Suppression
& Building Products
Ansul Inc.
1 Stanton St.
Marineffe, WI 54 143
Tele: 715-735-741 1
Fax: 7 15- 732-34 72
Interoffice Memorandum
This correspondence may contain confidential information intended for the use of Lhe ind~idual or entity to whom it is addressed. If me reader is not me
intended recbient or the em~lovee or aaentres~onsible tu deliver m me inrendedreciDienc you are hereby nofifiedmat w y dissemination for co~yine is
. - . ~. .- -
str/ctly prohibited.
Date Oct. 6, 2008
To Edward Mauullo
Office of Hazardous Materials Standards, Pipeline and Hazardous Material Safety
Administration, Attn: PH-10, U.S. Dept. Washington, DC 20590-0001
From
Copy Subject Richard Seaberg
Brad Goldapske, Lyne Demers, Eric Bretl
Interpretation of 49 CFR 173.309
Edward
Your name was given to us when we called DOT for information on 173.309. We
would like to have an interpretation on the subject par 173.309(a) of 49 CFR.
We manufacture a couple cylinders under this exception for Fire Extinguishers and
are getting confiding reviews.
We contacted Don Hilts with DOT in May of 2005 and his statement was as long as
the cylinder meets the requirements of 173.309(a) we were in compliance with the
exception.
We have since contracted with a consultant ,that is stating we are not in compliance
with the standard. I have attached the data sheet and drawings for your review as we
would like clarification.
Please let me know if you need any additional information.
Thank you, /
Richard Seaberg
Quality Assurance Manager

## Provenance

- Official: Yes
- Source: <https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2008/080255.pdf>
- Source ID: `phmsa`
- SHA-256: `d2820ab7216045ddf2dba48089529e660b8b552ce5d4557582d2c19cfdb9204f`
- Retrieved: 2026-08-20T00:59:31.977Z
- Exported: 2026-08-22T14:55:53.990Z
- Document slug: `phmsa-interpretation-08-0255`

### Source metadata

```json
{
  "materialSubtype": "interpretation",
  "interpretationArea": "hazardous_materials",
  "representation": "full_text_from_official_pdf",
  "companies": [
    "Tyco Safety Products"
  ],
  "individuals": [
    "Mr. Richard Seaburg"
  ],
  "refIds": [
    "08-0255"
  ],
  "catalogDates": [
    "2009-05-20"
  ],
  "catalogParts": [
    173
  ],
  "catalogRowCount": 1,
  "sourceRecordUrls": [
    "https://www.phmsa.dot.gov/node/45821"
  ],
  "linkedAttachmentUrls": [],
  "unavailableResponseUrls": [],
  "duplicateRepresentationUrls": [],
  "citedSections": [
    "173.309",
    "172.101(b)(l)",
    "107.105"
  ],
  "catalogPageUrls": [
    "https://www.phmsa.dot.gov/regulations/title49/section/173309"
  ],
  "pdfUrls": [
    "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2008/080255.pdf"
  ],
  "representations": [
    {
      "viewUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2008/080255.pdf",
      "detailUrl": null,
      "detailHtmlPath": null,
      "pdfUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2008/080255.pdf",
      "pdfArtifactPath": "data/sources/phmsa-interpretations/08-0255-174bf3827a.pdf",
      "pdfArtifactSha256": "01daee537ea38166211234d569d84b22d9bc974691808f1795f96a16247eed23",
      "extractedTextPath": "data/sources/phmsa-interpretations/08-0255-174bf3827a.v2.txt",
      "extractedTextSha256": "a12746a92d62c80c5c40faf2e988c6f440d7df0eb9e2c2db3e96dc3dc198318d",
      "pageCount": 2,
      "extractionVersion": 2
    }
  ],
  "caveat": "Interpretations apply regulations to the facts presented and do not create independently enforceable requirements.",
  "jurisdiction": "US"
}
```