# HMT Associates, LLC — Hazardous Materials Safety Interpretation

**Citation:** 09-0080  
**Type / status:** guidance / guidance  
**Agency:** Pipeline and Hazardous Materials Safety Administration  
**Effective:** Not stated  
**Published:** 2009-05-26

09-0080 response to HMT Associates, LLC concerning 178.801, 180.350.

## Document text

<<<PAGE 1>>>

U.S. Department of Transportation
Pipeline and Hazardous Materials
Safety Administration
1200 New Jersey Ave. S.E.
Washington, D.C. 20590
Mr. E.A. Altemos
HMT Associates, LLC
603 King St., Suite 300
Alexandria, VA 223 14-3 105
MAY 2 6 2009
Ref, No. 09-0080
Dear Mr. Altemos:
This responds to your April 8,2009 letter requesting clarification of the IBC design testing
requirements under the Hazardous Materials Regulations (HMR; 49 CFR Parts 17 1 - 180).
Specifically, you request confirmation that an existing IBC mounted with certain bottom
discharge equipment that is representative of the service equipment installed on the IBC
during design qualification tests is not a "different IBC design type" requiring design
qualification testing.
Your letter describes two alternative modifications of the bottom discharge outlet of an IBC
in order to conform to a new EPA requirement that each opening (other than a vent) of
portable refillable containers used for liquid pesticides must have one-way valves. The
original design qualification tests for the IBC were performed with a "Banjo" ball valve
installed at the bottom drain assembly. The alternatives are as follows:
Alternative 1 : Replace the existing "Banjo" ball valve with a new "Banjo" ball valve
fitted with an internal one-way valve. The new ball valve is identical to the existing ball
valve except for the addition of a one-way valve at the rear (inlet) of the valve that is located
completely within the IBC when installed.
Alternative 2: Retain the existing "Banjo" ball valve and add at its outlet a nozzle
with a standard external coupler connection to which a hose is attached for unloading where
the coupler contains the one-way valve.
Your understanding is correct. Based on the descriptions of the two alternatives and the
drawings provided with your letter, neither Alternative 1 nor Alternative 2 would result in the
creation of a "different IBC design type" as defined in 8 178.80 1 (c) and therefore, neither
alternative is subject to design qualification testing in accordance with !$ 178.80 1 (d).
Additionally, your understanding is correct that Alternative 1 is considered routine
maintenance because the original valve is removed and replaced (see 5 180.350(c)(l)(ii)).
Thus, this modification would be subject to verification of leaktightness and marking of the
IBC in accordance with 55 180.350(c)(l)(ii) and 180.352(e), respectively. Note that the new
"Banjo" valve described in Alternative 1 must provide an equivalent standard of integrity as
the original valve. The modification described as Alternative 2 is not considered routine

<<<PAGE 2>>>

maintenance and, thus, would not be subject to the verification of leaktightness and marking
requirements.
Sincerely,
/&
Susan Gorsky
Acting Chief, Standards Development
Office of Hazardous Materials Standards

<<<PAGE 3>>>

HMT ASSOCIATES, L.L.C.
603 KING ST
SUITE 300
ALEXANDRIA, VA 2231 4-31 05
703-549-0727
FACSIMILE: 703-549-0728
3 17 502
7esh& o f Zr&G
E.A. ALTEMOS
PATRICIA A. QUlNN
WRITER'S DIRECT DIAL NUMBER
(703) 549-0727, Ext. l l
April 8,2009
Mr. Edward T. Mazzullo
Director, Office of Hazardous
Materials Standards (PHH- 10)
Pipeline and Hazardous Materials
Safety Administration
Department of Transportation
1200 New Jersey Avenue, SE
East Building, 2nd Floor
Washington, D.C. 20590-000 1
Dear Mr. Mazzullo:
According to the definition of "D$ferent IBC design type" in fj 178.801 (c)(7) of the
Department of Transportation's Hazardous Materials Regulations ("HMR, 49 CFR Par%s 17 1 - 180),
an IBC which differs from a previously qualified IBC design type only in that it "differs in service
equipment" is g& considered a different IBC design type (see 9 178.802(c)(7)(iv)). Further,
$ 178.801(c)(l) defines an "IBC design type" to include service equipment "representative" of the
service equipment installed on the IBC for purposes of performing the required design qualification
tests. Thus, the HMR consider an IBC that differs from a previously qualified design type only in
terms of the representative service equipment installed to be of the same design type - and, therefore,
not a "different" design type requiring full design qualification testing.
The purpose of this letter is to seek your confirmation, based on the foregoing provisions,
that certain bottom discharge equipment proposed to be mounted on existing IBCs is
"representative" of the service equipment installed on the IBC when the design qualification tests
were performed, and, therefore, that the modified IBCs are of the same "IBC design type" as the
previously qualified IBCs.
Need for modified discharge arrangement.
The IBCs of interest are used in the agricultural industry for the transport of a variety of
liquid pesticides. The Il3C design qualification tests that provided the basis for the original

<<<PAGE 4>>>

HMT ASSOCIATES, L.L.C.
Mr. Edward T. Mazzullo
April 8,2009
Page 2
manufacturers' markings applied to the IBCs in order to certify conformance to the applicable
requirements of the HMR were performed with a standard "Banjo" ball valve installed at the outlet
of the bottom drain assembly. The design of this valve - which is very commonly used on IBCs of
a variety of different design types - does not have an inherent feature to prevent reverse flow into the
LBC through the bottom discharge outlet.
The US Environmental Protection Agency (EPA) recently adopted new requirements
applicable to packagings used for pesticides. One ofthese requirements, which appears as paragraph
(e) of 40 CFR 165.45 ("Refillable container standards"), states (in pertinent part):
"(e) What standards for openings do my refillable containers have to meet? If
your refillable container is a portable pesticide container that is designed to hold
liquid pesticide formulations and is not a cylinder that complies with the DOT
Hazardous Materials Regulations, each opening of the container other than a vent
must have a one-way valve, a tamper-evident device or both."
Compliance with this new provision is required on and after August 16, 201 1, and
"grandfathering" of existing packagings is provided. For purposes of this requirement, EPA has
defined a "one-way valve" as a valve that is "designed and constructed to allow virtually unrestricted
flow in one direction and no flow in the opposite direction". Moreover, it is noted that use of a
tamper-evident device as the sole means to satisfy this requirement is allowed only for containers
that are cleaned of all residue prior to refilling. However, in practice IBCs used by the agricultural
industry for the transport of pesticides are normally refilled with the same or a similar pesticide
without first being cleaned. Thus, in effect, on and after August 16,20 1 1, all existing IBCs used for
liquid pesticides will have to be retro-fitted with a "one-way" valve in order to comply with this
requirement, or no longer used in pesticides service.
It is estimated that several hundred thousand IBCs used in the agricultural industry are
affected by this new requirement. The cost of removing these IBCs from this service and replacing
them (within the authorized time-frame) with new IBCs equipped with discharge valves that meet
this requirement is prohibitive. Thus, the only practicable option is to retro-fit these existing IBCs
with discharge valves complying with the new EPA requirement. However, at the same time, in
order to ensure that the applicable requirements of the HMR are satisfied, it is imperative that any
alteration of the bottom outlets on these IBCs does not result in the IBC being considered to be of
a "different design type". Were h s to result, the continued use of the IBCs on the basis of the
previously conducted design qualification tests (under which the UN markings certifying compliance
with the applicable requirements of the HMR were applied) would be precluded - thereby causing
significant harm and serious financial loss to an agricultural industry that relies heavily on these
IBCs for the transport of pesticides.

<<<PAGE 5>>>

HMT ASSOCIATES, L.L.C.
Mr. Edward T. Mazzullo
April 8, 2009
Page 3
Proposed alternatives.
Against that background, and based on the provisions of the HMR outlined above, your
confirmation is requested that certain bottom discharge equipment proposed to be mounted on these
existing IBCs may be considered to be "representative" of the service equipment installed on the IBC
when the design qualification tests were performed, or otherwise authorized, such that the modified
IBCs may be considered to be of the same "IBC design type" as the previously qualified IBCs. Two
alternative bottom discharge arrangements, as described below, are proposed in order to ensure these
existing IBCs conform to the new EPA requirements. Your consideration of each of these
alternatives in light of the "representative service equipment" provisions will be appreciated.
Alternative 1. Alternative 1 is to replace of the existing Banjo ball valve at the IBC bottom
outlet with a new Banjo ball valve fitted with an internal one-way valve. The original ball valve is
shown in attached drawing identified as "1" in the upper left hand corner, and the new ball valve is
shown in the drawing identified as "2".
• The drawing identified as "5" is a sectioned isometric view
of the IBC body and base illustrating the drain assembly with the original valve installed.' The new
ball valve is identical to the existing ball valve except for the addition of the one-way valve at the
rear (inlet) of the valve which, when the valve is installed, is located completely within the IBC.
Thus, viewed from outside of the IBC, the valve installed in the drain assembly would appear the
same as does the original valve, as illustrated in the drawing identified as "1". It is understood that
the replacement of the original valve by a new valve would constitute "routine maintenance" as
defined in § 180.350(c), which is subject to verification of the leaktightness, and marking of the IBC
as provided in §§ 180.350(c)(ii) and 180.352(e), respectively.
Your confirmation is requested that the replacement described above will not result in the
creation of a "different IBC design type" on the basis that the original Banjo ball valve (with which
the IBCs subjected to the design qualification tests were equipped) is "representative" of the new
Banjo ball valve (with integral one-way valve).
Alternative 2. Alternative 2 is to retain the existing Banjo ball valve and to add at its outlet
a nozzle (with the standard external "coupler" connection to which a hose is attached for unloading).
This added "coupler" would contain the internal one-way valve necessary to satisfy the new EPA
requirement. This alternative arrangement is illustrated in the attached drawings identified as "3"
and "4". Note that when installed on the outlet the entire assembly remains adequately protected.
Note that the dark colored (red) component shown in the attached sectioned isometric
drawings of the IBC drain assembly (i.e.., the drawings identified as "3", "4" and "5") is a part of the
IBC pallet base. While most of the IBCs affected by the new EPA requirements conform to this
the outlet valves (including as described in Alternative 2) are located within a recess in the IBC body
particular arrangement, all do not. However, even when not fitted with a pallet base as illustrated,

<<<PAGE 6>>>

HMI ASSOCIATES, L.L.C.
Mr. Edward T. Mazzullo
April 8, 2009
Page 4
Importantly, the original outlet valve remains installed on the IBC and continues to provide the basic
product containment capability. The "new" component necessary to conform the outlet to the new
EPA requirement is simply a "downstream" addition to the current item of service equipment. In
this connection, nothing in the HMR appears to preclude adding a coupler extension to the outlet of
an existing bottom discharge valve (i.e., a valve of the design used when the IBC design qualification
tests were performed) and transporting the IBC with the coupler extension installed.
It is estimated that implementation of Alternative 2 would entail only approximately half the
expense of Alternative 1. Therefore, given the very large number of IBCs that must be brought into
conformance with the new EPA requirement, this would be the preferred approach. Consequently,
your confirmation is requested that the addition described above will not result in the creation of a
"different IBC design type". This conclusion could be based either on the fact that nothing in the
HMR precludes the addition of a coupler extension to the outlet of an the existing discharge valve,
or on the basis that the original Banjo ball valve (with which the IBCs subjected to the design
qualification tests were equipped) is "representative" of the arrangement in which the coupler (with
integral one-way valve) is added to the outlet of the original Banjo ball valve. In either case, this
operation would not appear to constitute "routine maintenance" as defined in § 180.350(c), and your
confirmation of this understanding would also be appreciated.
Thank you for your consideration in this matter. Please do not hesitate to contact me if you
have questions concerning this request, or if you require additional information.
Sincerely,
Elle
E. A. Altemos
TBC Representative Service Equipment Letter. wpd

## Provenance

- Official: Yes
- Source: <https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2009/090080.pdf>
- Source ID: `phmsa`
- SHA-256: `472687d14662b88e92509c566f72554fea5e5a052ca5099f8c8162308bae0762`
- Retrieved: 2026-08-20T00:59:31.977Z
- Exported: 2026-08-26T19:56:09.680Z
- Document slug: `phmsa-interpretation-09-0080`

### Source metadata

```json
{
  "materialSubtype": "interpretation",
  "interpretationArea": "hazardous_materials",
  "representation": "full_text_from_official_pdf",
  "companies": [
    "HMT Associates, LLC"
  ],
  "individuals": [
    "Mr. E.A. Altemos"
  ],
  "refIds": [
    "09-0080"
  ],
  "catalogDates": [
    "2009-05-26"
  ],
  "catalogParts": [
    178,
    180
  ],
  "catalogRowCount": 2,
  "sourceRecordUrls": [
    "https://www.phmsa.dot.gov/node/45801"
  ],
  "linkedAttachmentUrls": [],
  "unavailableResponseUrls": [],
  "duplicateRepresentationUrls": [],
  "citedSections": [
    "178.801",
    "180.350",
    "180.350(c)(l)(ii)",
    "178.80",
    "180.352(e)",
    "178.802(c)(7)(iv)"
  ],
  "catalogPageUrls": [
    "https://www.phmsa.dot.gov/regulations/title49/section/178801",
    "https://www.phmsa.dot.gov/regulations/title49/section/180350"
  ],
  "pdfUrls": [
    "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2009/090080.pdf"
  ],
  "representations": [
    {
      "viewUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2009/090080.pdf",
      "detailUrl": null,
      "detailHtmlPath": null,
      "pdfUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2009/090080.pdf",
      "pdfArtifactPath": "data/sources/phmsa-interpretations/09-0080-a409088eb3.pdf",
      "pdfArtifactSha256": "b635588fdbf9b868a35026c14a16e4eee801966e9816c67aa17a7c569fc9f425",
      "extractedTextPath": "data/sources/phmsa-interpretations/09-0080-a409088eb3.v2.txt",
      "extractedTextSha256": "f11f6593a773caddf01a36670e75a045216df68990827e401c11fc0aebd3b730",
      "pageCount": 6,
      "extractionVersion": 2
    }
  ],
  "caveat": "Interpretations apply regulations to the facts presented and do not create independently enforceable requirements.",
  "jurisdiction": "US"
}
```
