<<<PAGE 1>>>

U.S. Department Washington. DC 20590
1200 New Jersey Avenue SE
of Transportation
Pipeline and Hazardous
Materials Safety
Administration
FEB 1 6 2012
Mr. Frank Drayton
Fire Division Chief
650 Merchant Street
Vacaville, CA 95688
Ref. No. 11-0284
Dear Chief Drayton:
This responds to your November 15,2011 and November 24,2011 follow-up email concerning
the requirements for cylinders under the Hazardous Materials Regulations (HMR; 49 CFR Parts
171-180). Specifically, you ask whether the HMR apply to DOT specification 3AA and 3AAX
cylinders used by local fire departments for non-commercial purposes.
In accordance with Federal hazardous materials transportation law (49 U.S.C. 5101 et seq.), the
HMR apply to the transportation ofhazardous materials in commerce. Hazardous materials
transported by a government entity in vehicles operated by government personnel for noncommercial
purposes are not subject to the HMR However, this provision may not fully except
a government agency from the HMR A cylinder manufactured and marked in accordance with
the requirements established in the HMR must be maintained in accordance with applicable
specification requirements whether or not it is in transportation in commerce at any particular
time. Ifa government agency, such as a local fire department, uses cylinders marked in
accordance with the HMR, the government agency is subject to the HMR relating to the
maintenance and use of those cylinders.
I hope this information is helpful. If you have further questions, please contact this office.
Sincerely,
~::;#--
Ben Supko
Acting Chief, Standards Development
Standards and Rulemaking Division

<<<PAGE 2>>>

LeaC!J
~ 11 G· 3'7
N • c • F.M.A •
~ I,nriers
Northern California Fire Mechanics Association 1/- DZ B4
Code ofFederal Regulations
Code Compliance Section
Re: Cal-OSHA regulation negating DOT Regulation
California Fire Service Pressure Vessel compliance
DOT Inspection and Testing Standards
Petition for DOT regulations ruling
Sirs:
Historically, from the time the fire service first began the installation of pressurized breathing air cylinders on
mobile fire apparatus, the fire service has utilized DOT classified pressure vessels (prior service was ICC certified
pressure vessels). In some cases, where removal ofcylinders was problematic, ASME bottles were utilized but
created special mounting issues, substantial weight increases, and exorbitant costs. When legal issues arise and the
fire service is SUbjected to court of law events, the fire service wins or loses cases predicated to whether the fire
service complies with NFPA Standards, or not.
Recent issues in California have arisen revolving around whether pressurized mobile pressure vessels fall under
Federal DOT/CFR regulations and compliance as is indicated in NFPA 1901,2009 Edition, Section 24, et ai, or not.
Cal-OSHA has stipulated that fines will be initiated if all mobile breathing air pressure vessels are not removed and
replaced with ASME pressure vessels. They have taken this stance because they have a ruling from Federal DOT
that DOT cylinders are not California compliant because Federal DOT is not responsible for DOT inspection,
testing, and recertification requirements for DOT cylinders in non-commercial intrastate use. This determination is
in direct conflict with the chapter and verse by which the fire service (both locally and nationally) designs and builds
fire apparatus. The inference is that all DOT cylinders in use by the California fire service are not subject to DOT
regulatory inspection, testing and recertification. This is completely contrary to the DOT Standard by which the
California fire service has inspected, tested and recertified the extensive list of existing cylinders Statewide. To be
able to purchase a fire apparatus that will meet mandates ofthe Laws, Regulations, and Standards, fire apparatus are
designed and manufactured to meet NFPA 1901,2009 Edition (current and past), Standard for Automotive Fire
Apparatus. This is the Standard by which all members ofthe Fire Apparatus Manufacturers Association (FAMA)
build fire apparatus. It is the litmus test by which court issues are decided.
To quote NFPA 1901, the following is the Standard by which we comply:
24.5.1 Transportable Air Tanks
24.5.1.1 Transportable air tanks shall comply with 49 CFR 178.37, "Specification 3AA and 3AAX seamless
steel cylinders," or 29 CFR 1910.169, "Air Receivers."
24.5.1.2 The air tank manufacturer shall provide a copy of either the U.S. Department of Transportation
(DOT) certificate Report of Inspection of Gas Cylinders or the ASME certificate Manufacturers Data Report
for Pressure Vessels, and the certificate shall be delivered with the apparatus.
Because ofthis Standard, both ASME and DOT bottles are used in the fire service across the country.
By the CFR (Code of Federal Regulations)
(a) General qualification for use ofcylinders. (See §§ 173.1 through 173.30 for requirements apply.)
(b) Grandfather clause. A cylinder in domestic use previous to the date upon which the specification therefore
was first made effective in thesc regulations may be used if the cylinder has been properly tested and
otherwise complies with the requirements applicable for the gas with which it is charged.

<<<PAGE 3>>>

[Recipient Name]
November 4,2011
Page 2
However, under NFPA 190], a change since previous editions, in the Addenda section for mobile breathing air
supply, it reads as follows:
A.24.S: In some states in the United States, the regulations of the Occupational Safety and Health
Administration (OSHA) of the Department of Labor have been interpreted to require that DOT cylinders be
used for mobile air tanks to transport air on state highways. If DOT cylinders are not required by state
regulations, ASME cylinders should be utilized as air tanks if the design of the apparatus presents a severe
difficulty in the removal of the cylinders for testing. (It is not a difficult task to remove the DOT bottles every 5
years for hydrostatic testing) The bottles are firmly attached to the vehicles with brackets manufactured by the
apparatus builder and certified to perfonn the function as required.
Then, the question becomes ............. What authorization or exemption has been given to Cal OSHA to transpOit
charged ASME cylinders on the highways? I do not find any reference to ASME bottles listed as the approved
cylinders for highway transportation while charged. The fire service MUST alrive on scene, fully prepared to fight
fire and activate breathing air systems.
CCR: Subchapter 7. General Industry Safety Orders
Group 2. Safe Practices and Personal Protection
Altide 10.1. Personal Protective Clothing and Equipment for Fire Fighters
§3409. Respiratory Protection.
(6) Air Cylinders. Approved self-contained compressed air breathing apparatus may be used with approved
cylinders from other approved self-contained compressed air breathing apparatus provided that such cylinders are of
the same capacity and pressure rating. All compressed ail' cylinders used with self-contained breathing
apparatus (SCBA) shall meet United States Department of Transportation (BOT) and NIOSH criteria.
The DOT standard for DOT cylinder hydrostatic testing eliminates the] 0 year rule and mandates a 5 year hydro.
Please note that on aerial fire apparatus, when at the tip of an elevated ladder and when a firefighter's SCBA
breathing air cylinder on his back (30, 45 or 60 minute cylinders) is depleted, the firefighter then connects his
umbilical line to the on-board apparatus SCBA supply cylinders (244cfair capacity typical) which then becomes the
SCBA life support breathing air supply.
A local fire department has complied with the Cal-OSHA ruling and changed out their 8 (eight) DOT rated bottles
at their fire department at a cost of $28,000. Can you see the issue of the cost statewide? [t will be in the $M's. In
this single case it did result in a substantial weight increase for the associated mobile chassis. Luckily for this
agency, it did not result in the need for a complete chassis replacement to meet CA Gross Vehicle Weight Ratings
(GVWR). In many cases, it will result in not simply replacing the pressure vessels, but the mobile chassis as well or
substantially reduce the quantity of live saving air due to the decrease in the numbers of pressurized vessels.
The best case scenario, especially in these times ofcritical monetary shortfalls, is to rule that all DOT classified
pressure vessels/cylinders continue to be inspected, maintained, tested and re-certified to existing DOT standards
and falls under the authority ofFederal DOT. Following a yet to be detennined date, all pressurized breathing air
cylinders in use by California emergency services agencies will confonn to Cal-OSHA Regulations, i.e. ASME
pressure vessels.
Respectfully submitted,
Anthony D. Bulygo
California Fire Chief's Association
Safety Committee Member/Consultant

<<<PAGE 4>>>

N.C.F.M.A.
Northern California Fire Mechanics Association
Code of Federal Regulations
Code Compliance Section
Re: Cal-OSHA regulation negating DOT Regulation
California Fire Service Pressure Vessel compliance
DOT Inspection and Testing Standards
Supplemental to White Letter of November 04,2011
Sirs:
Cal-OSHA states that a safety issue exists whereby the absence of regulations in place for DOT pressure vessels in
use by non-commercial end users is not acceptable. The absence of regulations for DOT pressure vessels requires
that Cal-OSHA mandate the removal of DOT pressure vessels from use by the fire and emergency service agencies
in California. Cal-OSHA states it has come to this conclusion following contact with Fed DOT which has stated to
Cal-OSHA that Fed CPR mandates do not apply to non-commercial users. The end result of the Fed DOT statement
is that Cal-OSHA has ruled that DOT pressure vessels in use by the FirelEmergency services sector in California are
unregulated and must be removed from service and replaced with ASME pressure vessels which are under the
regulatory control of Cal-OSHA.
The California rITe service does, in fact, stipulate that all pressure vessels must be maintained and tested regularly to
regulatory standards.
In a recent meeting with Cal-OSHA officials, Mr. Don Cook, Principal Engineer, stated very plainly: IfFed DOT
were to issue a letter to Cal-OPSHA stating that DOT pressure vessels in use by the FirelEmergency Service
services in California fall under the same guidelines and regulations as commercial users for inspection,
maintenance and testing/recertification, the issue would go away. All of which leads to a single question to Fed
DOT: Why would Fed DOT not mandate regulation of DOT pressure vessels in CA and why would Fed DOT not
issue a letter stating that the appropriate CPR pertains to those DOT cylinders in use in this vocation?
California Fire Service desires to comply with any and all Laws, Regulations, and Standards in place for any safety
issue. The fire service believes we have been doing the right thing and complying for the past 40 years. A letter to
Cal-OSHA, assuring them that the DOT pressure vessels in use by the California FirelEmergency services are, in
fact, covered by CPR regulations.
Respectfully submitted,
Anthony D. Bulygo
California Fire Chief's Association
Safety Committee Member/Consultant
November 21, 2011

## Provenance

- Official: Yes
- Source: <https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2011/110284.pdf>
- Source ID: `phmsa`
- SHA-256: `3fa5774314c6850a802399147bb0b362b2cbcba1b0f67582dc3850231a60e260`
- Retrieved: 2026-08-20T00:59:31.977Z
- Exported: 2026-08-23T04:11:11.080Z
- Document slug: `phmsa-interpretation-11-0284`

### Source metadata

```json
{
  "materialSubtype": "interpretation",
  "interpretationArea": "hazardous_materials",
  "representation": "full_text_from_official_pdf",
  "companies": [
    "Northern California Fire Mechanics Association"
  ],
  "individuals": [
    "Mr. Frank Drayton"
  ],
  "refIds": [
    "11-0284"
  ],
  "catalogDates": [
    "2012-02-16"
  ],
  "catalogParts": [
    178
  ],
  "catalogRowCount": 1,
  "sourceRecordUrls": [
    "https://www.phmsa.dot.gov/node/64276"
  ],
  "linkedAttachmentUrls": [],
  "unavailableResponseUrls": [],
  "duplicateRepresentationUrls": [],
  "citedSections": [
    "178.37",
    "173.1",
    "173.30"
  ],
  "catalogPageUrls": [
    "https://www.phmsa.dot.gov/regulations/title49/section/17837"
  ],
  "pdfUrls": [
    "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2011/110284.pdf"
  ],
  "representations": [
    {
      "viewUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2011/110284.pdf",
      "detailUrl": null,
      "detailHtmlPath": null,
      "pdfUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2011/110284.pdf",
      "pdfArtifactPath": "data/sources/phmsa-interpretations/11-0284-8656597c55.pdf",
      "pdfArtifactSha256": "cdc1827ecd86c6c545d81a5b99d07ebf05bd4d6094c119819ad2a7a01a78a7b9",
      "extractedTextPath": "data/sources/phmsa-interpretations/11-0284-8656597c55.v2.txt",
      "extractedTextSha256": "c3d2f3dcc6aa875dbe9e1b79b1833c511ce0f2dc0a85b37e0d20cad79a9534a9",
      "pageCount": 4,
      "extractionVersion": 2
    }
  ],
  "caveat": "Interpretations apply regulations to the facts presented and do not create independently enforceable requirements.",
  "jurisdiction": "US"
}
```