99-0228 response to Texas Farm Bureau concerning 173.315.

## Document text

<<<PAGE 1>>>

• •
of Transportation
US. Department
400 Seventh Street, S.W.
Washingion. D.C.
research and
20590
administrations
MAR - 3 2000
Mr. Ned Meister
Director, Commodity and
Ref. No: 99-0228
Texas Farm Bureal
Regulatory Activities
P.O. Box 2689
Waco, Texas 76702-3030
Dear Mr. Meister:
This is in response to your letter, and subsequent telephone conversation with Diane LaValle, of my
I apologize for the delay in response.
staff, requesting clarification of the Hazardous Materials Regulations (HMR; 49 CFR Parts 171-180).
Your questions are answered as follows:
Q1. Are nurse tanks with a capacity of 3000 gallons or less that meet construction specifications
required at the time of manufacture authorized for the transportation of anhydrous ammonia?
A. As provided by § 173.315(m) a nurse tank transporting anhydrous ammonia, operated by a private
carrier exclusively for agricultural purposes does not have to meet the specification requirements of 49
it was manufactured.
CFR Part 178 if, among other criteria, it meets the requirements of the ASME code in effect at the time
Q2. As provided by § 173.315(m)(5), a nurse tank transporting anhydrous ammonia may be loaded to
a filling density no greater than 56 percent. Using the water weight factor of 8.32828 pounds per
gallon, would a 3000 gallon tank loaded to 56% by weight have a maximum loaded weight of
13,991.51? [3000 X 8.32828 X 56%]
A. The maximum weight of anhydrous ammonia authorized in this cargo tank is 13,991 pounds which
does not include the weight of the cargo tank and motor vehicle.
Q3. There is a difference in the maximum permitted filling densities in § 173.315(a) and § 173.304.
Please explain the difference.
A. Section 173.315 pertains to cargo tanks, whereas § 173.304 pertains to cylinders.
990228
173.315

<<<PAGE 2>>>

Q4. What arc the requirements of the Compressed Gas Association's (CGA) pamphlet S1.2?
A. Pamphlet S1.2 may be purchased from the CGA. They may be contacted at (703) 412-0900.
I hope this information is helpful.
Sincerely,
Delmer F. Billings
Chief, Standards Development
Office of Hazardous Materials Standards

<<<PAGE 3>>>

TEXAS
OFFICERS:
BOARD OF DIRECTORS:
-farm
BOB STALLMAN
President
DAVID NOBLE
BUREAU
DONALD PATMAN
DELMAS MCCORMICK
BEGAN KIRK
Vice President
Floydada
HORE SURAN
DELMAS MCCORMICK
IM SMITT
Secretary-Treasurer
DONALD PATMAN
Vaxahachi
MES MAXTO
ANTONY HANER
San Angel DERSCHKE
unt Please
Coshara
URT MOWER
ZACHARY X XANTA
P.О. Box 2689 • Waco, exas 76702-2689 • 254-772-3030
DATE. ESKE
talkelle.
August 9, 19g99
Office of Standards
Edward T. Mazzullo, Director
Research and Special Programs Administration
99-0228
U.S. Department of Iransportation
400 Seventh Street, S.W.
Washington, DC 20590
Dear Mr. Mazzullo:
Texas farmers are concerned that state and federal agencies have a difference in the
issues relating to anhydrous ammonia nurse tanks with a capacity of 3000 gallons or less
are still unclear.
Tank Specifications - Please verify that anhydrous ammonia nurse tanks with a capacity
of 3000 gallons or less that meet construction specifications required at time of
manufacture are compliant.
Filling Density - A nurse tank can be loaded to a filling density no greater than 56
ensity at 56 percent by weight and 82 percent by volume. Using the water weight facts
arcent [173.315 (m)(5)]. The table in 173.315 (a) lists the maximum permitted fillin
of 8.32828 pounds per gallon (173.315 Note 1), would a 3000 gallon tank loaded to 56
X 56%)?*
percent by weight have a maximum loaded weight of 13,991.51 pounds (3000 X 8.32828
Are the volume gauging devices correlated to the to the weight filling density?
There is a difference in maximum permitted filling densities in the table in 173.315 (a)
(56%) and the table in 173.304 (54%). Please explain the difference.
( Safety Relier Valves - Nurse tanks are to be equipped with safety relief valves that meet,
Charging cylinders
the requirements of CGA pamphlet S1.2 [173.315 (m)(2)]. What are these requirements?
Financial Responsibility - What are the minimum levels of financial responsibility for
the following scenarios (common farm truck and nurse tank combinations):
1.
2.
Farm truck pulling a single nurse tank intrastate from supplier to farm?
3.
F'arm truck pulling two nurse tanks intrastate from supplier to farm?
Farm truck pulling a single nurse tank intrastate from farm to farm?
4.
Farm truck pulling two nurse tanks intrastate from farm to farm?
5.
Would the minimum levels of financial responsibility in the above four scenarios
change if the nurse tanks were moved interstate?

<<<PAGE 4>>>

•
Edward Mazzullo
Page 2
8-9-99
6.
What is the financial responsibility of a supplier who delivers anhydrous
What is the financial responsibility of a supplier who makes that delivery
ammonia in a nurse tank intrastate to the farm?
interstate?
Part 172 Requirements
Subpart C - Shipping Papers
Not required [173.315 (m)(7)].
1. Does this exception apply to nurse tanks moved interstate?
Subpart D - Marking.
1. What are the marking requirements for nurse tanks used to transport
Subpart E - Labeling
properly placarded?
1. Is there additional labeling required for nurse tanks if the tank is
2. if so, is there an illustration that shows the proper placement and
content of the additional labels?
Subpart F - Placarding
1. Please describe the placards required for nurse tanks by content and
2. Is there an illustration that shows the proper placement and content of
placement.
required placards?
Subpart G - Emergency Response Information
apers are not required for nurse tanks under 173.315 (m)(7
ot required if shipping papers are not required [172.600 (d)]. Shippin
Subpart H - Training
1. Are farmers who use anhydrous ammonia nurse tanks required t
rovide training to emplovees under 172.704?
Other Issues in need of Clarification
Mileage Limitation
1. Are all exemptions and exceptions limited to the intrastate
transportation of anhydrous ammonia nurse tanks within a 150 mile radius
of the farm?
2. Is the 150 mile radius rule applicable to transporting anhydrous
ammonia nurse tanks interstate from farm to farm? Interstate from

<<<PAGE 5>>>

Edward Mazzullo
Page 3
8-9-99
Hours of Service
1. Is there an hours of service standard that must be met by a farmer or
Vehicle Maintenance
intrastate subject to DOT inspections? Are they subject to DOT
Are farm trucks used to transport anhydrous ammonia nurse tanks
inspection if they are used interstate?
Drug and Alcohol Testing
requirements if transporting anhydrous ammonia nurse tanks?
Are farmers or their employees subject to drug and alcohol testing
Driver Qualifications
Are there federal driver qualifications required for a farmer or his
mployee when transporting anhydrous ammonia nurse tanks whe
!
ngaged in normal farming activities
Thank you for clarifying these important issues. It is our goal to assist farmers in Texas
to be compliant when transporting anhydrous ammonia nurse tanks.
Pet meister
Ned Meister, Director
Commodity and Regulatory Activities

## Provenance

- Official: Yes
- Source: <https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/1999/990228.pdf>
- Source ID: `phmsa`
- SHA-256: `67a3a3b4ce0bf6209e064bb0b587497db238430e1b787388ac1a563d261a3e39`
- Retrieved: 2026-08-20T00:59:31.977Z
- Exported: 2026-08-25T04:14:02.513Z
- Document slug: `phmsa-interpretation-99-0228`

### Source metadata

```json
{
  "materialSubtype": "interpretation",
  "interpretationArea": "hazardous_materials",
  "representation": "full_text_from_official_pdf",
  "companies": [
    "Texas Farm Bureau"
  ],
  "individuals": [
    "Mr. Ned Meister"
  ],
  "refIds": [
    "99-0228"
  ],
  "catalogDates": [
    "2000-03-03"
  ],
  "catalogParts": [
    173
  ],
  "catalogRowCount": 1,
  "sourceRecordUrls": [
    "https://www.phmsa.dot.gov/node/69601"
  ],
  "linkedAttachmentUrls": [],
  "unavailableResponseUrls": [],
  "duplicateRepresentationUrls": [],
  "citedSections": [
    "173.315",
    "173.315(m)",
    "173.304",
    "172.600",
    "172.704"
  ],
  "catalogPageUrls": [
    "https://www.phmsa.dot.gov/regulations/title49/section/173315"
  ],
  "pdfUrls": [
    "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/1999/990228.pdf"
  ],
  "representations": [
    {
      "viewUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/1999/990228.pdf",
      "detailUrl": null,
      "detailHtmlPath": null,
      "pdfUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/1999/990228.pdf",
      "pdfArtifactPath": "data/sources/phmsa-interpretations/99-0228-3a73dc776d.pdf",
      "pdfArtifactSha256": "153edc175a1485b314fed937c4d051acff3feb06c8498a54c6081620aaa458a5",
      "extractedTextPath": "data/sources/phmsa-interpretations/99-0228-3a73dc776d.v2.txt",
      "extractedTextSha256": "78853b7eb1b3c7ae6eb043c8826aa38f5c9104eb34230261c40eb13be4925404",
      "pageCount": 5,
      "extractionVersion": 2
    }
  ],
  "caveat": "Interpretations apply regulations to the facts presented and do not create independently enforceable requirements.",
  "jurisdiction": "US"
}
```