<<<PAGE 1>>>

u.s. Department
of Transportation
Pipeline and Hazardous Materials
Safety Administration
1200 New Jersey Ave .. SE
Washington, DC 20590
'JUL 1 62010
CERTIFIED MAIL - RETURN RECEIPT REQUESTED [7009 1410000024722674]
Ms. Lisa M. Tonery
Fulbright & Jaworski L.L.P.
666 Fifth Avenue, 31 st Floor
New York, NY 10103-3198
RE: Request for Written Interpretation on the Applicability of 49 C.F.R. Part 193 to
Proposed LNG Import Terminal in Robbinston, Maine
Dear Ms. Tonery:
As counsel for Downeast LNG, Inc. (Downeast or the Company), you have asked for a written
interpretation on two questions related to your client's proposal to build a liquefied natural gas
(LNG) import terminal in the town of Robbinston, Maine (Robbinston LNG Import Terminal or
the Terminal). Specifically, you have asked whether Downeast may use its alternative source
term model (DLNG Source Term Model) to comply with the vapor-gas exclusion zone
requirements in 49 C.F .R. § 193.2059 . You have also asked whether the Company must
examine the effects of jetting and flashing to comply with those same requirements.
Under the conditions described in this letter, Downeast may use the DLNG Source Term Model
to calculate the vapor-gas exclusion zone for the sumps at the Robbinston LNG Import Terminal.
The Company must also examine the effects of jetting and flashing in siting appropriate facilities
at the Terminal, including pressurized piping or equipment, to comply with our vapor-gas
dispersion exclusion zone requirements.
Question 1
The Pipeline and Hazardous Materials Safety Administration (PHMSA) issues federal safety
standards for siting LNG facilities.! Those regulations require that an operator or governmental
authority control the activities that occur within a specified distance around the facilities at an
LNG plant, to protect the public from unsafe levels of thermal radiation and flammable vapor-
gas dispersion in the event of an accident. Certain mathematical models and other parameters
must be used to calculate the dimensions of these "exclusion zones."
In the case of vapor-gas dispersion, two different computational models are already authorized
for use by regulation: (1) the DEGADIS Dense Gas Dispersion Model (DEGADIS), a model
developed by the U.S. Coast Guard and Gas Research Institute (GR!) to simulate the downwind
I Pipeline Safety Act of 1979, Pub. L. No. 96-129, § 152, 93 Stat. 989 (1979) (currently codified at 49 U.S.C.
§ 60103(a)).
1

<<<PAGE 2>>>

dispersion of dense gases in the atmosphere, and (2) FEM3A, another dispersion model designed
"to account for additional cloud dilution which may be caused by the complex flow patterns
induced by tank and dike structure.,,2
Downeast intends to calculate the vapor-gas dispersion exclusion zone for the Robbinston LNG
Import Terminal with DEGADIS, an integral model that requires the user to input a "source
term." The source term is designed to simulate the physical phenomena that occur immediately
after an LNG release, but prior to atmospheric dispersion.3
You have asked whether the Company may use a new source term model, the DLNG Source
Term Model, to perform the exclusion zone analysis for the sumps at the Terminal. You state
that this new model uses conservative assumptions for the effects of pool spreading, vapor
production, and vapor retention. In your opinion, that makes it suitable for use with DEGADIS
under our regulations.
The source term used as the input for DEGADIS must have a suitable basis to comply with our
Siting Requirements. "Otherwise, a user could select whatever source term is likely to produce
the most favorable outcome, e.g., the smallest or largest possible exclusion zone, or even at
random.,,4 Such a result would not be consistent with the limitations of DEGADIS or our
statutory obligation to protect the public from the hazards associated with an LNG plant. For
these reasons, the utmost care must also be exercised in evaluating the suitability of any such
model, a task that involves "making predictions, within [PHMSA' s] area of special expertise. ,,5
We further note that the proponent of an alternative source term model previously had to petition
for, and receive, the Administrator's approval to use that model to comply with our vapor-gas
dispersion exclusion zone requirements.6 However, our predecessor agency repealed that
requirement in a March 2000 final rule.7 Consequently, the Administrator's approval is no
249 C.F.R. § 193.2059 (2010). The Administrator may also approve the use ofaltemative vapor-gas dispersion
models that "take into account the same physical factors and have been validated by experimental test data." 49
C.F.R. §§ 193.2057(a), 193.2059(a); 49 C.F.R. § 190.1 I (2010) (authorizing the submission of petition for finding
or approval with the Administrator).
3 Ivings, et a!., LNG Source Term Models for Hazard Analysis: A review of the State-of-the-Art and an
Approach to Model Assessment, p. vi (Mar. 2009) (on file with PHMSA).
4 In the Matter ofMssrs. Keppel and Miozza, PHMSA Interp. (July 7, 2010) (to be available at
www.phmsa.dot.gov).
5 Baltimore Gas and Electric Company v. Natural Resources Defense Council, 462 U.S. 87, 103 (1983); see
Wisconsin Electric Power Company v. Costle, 715 F.2d 323, 329 (7th Cir. 1983) (upholding EPA's use of a
particular dispersion model and stating that its "choice to rely on an air quality model is a policy judgment deserving
great deference.").
6 Liquefied Natural Gas Facilities; New Federal Safety Standards, 45 Fed. Reg. 9 I 84 (Feb. II, 1980); Liquefied
Natural Gas Facilities; Reconsideration of Safety Standards for Siting, Design, and Construction, 45 Fed. Reg.
57402,57418 (Aug. 28, 1980) (denying, in part, and granting, in part, a petition for reconsideration); see In the
Matter of Energy Terminal Services Corporation, PHMSA Interp. 82-05-28 (May 28, 1982); In the Matter of Mr.
George H. Lawrence, President, American Gas Association, PHMSA Interp. 83-06-29 (June 29, 1983); see also
Liquefied Natural Gas Regulations-Miscellaneous Amendments, 62 Fed. Reg. 8402, 8404 (Feb. 25, 1997)
(amending 49 C.F.R. § I93.2059(d)(l)(ii)).
7 Pipeline Safety: Incorporation of Standard NFPA 59A in the Liquefied Natural Gas Regulations 65 Fed. Reg.
10950, 10953 (March 1,2000).
2

<<<PAGE 3>>>

longer an absolute prere~uisite to using an alternative source term model with DEGADIS under
our Siting Requirements.
In our opinion, the DLNG Source Term Model can be used with DEGADIS to calculate the
vapor-gas dispersion exclusion zones for the sumps at the Robbinston LNG Import Terminal.
Downeast has demonstrated, through the use of a parametric analysis, that an instantaneous pool
spreading scenario across these particular sump floors will produce the longest flammable vapor-
gas cloud. The Company has also shown that its heat transfer methodology is appropriate. As
confirmed in the documents submitted with your letter, that methodology "assum[ es] perfect
thermal contact between [the] pool and [the] ground, and only vertical temperature gradients in
the ground," and the conduction is modeled "by the one-dimensional Fourier conduction
equation in the ground, with an initial state where the ground is uniformly at ambient
temperature, and assumes the boiling temperature of LNG as soon as the spreading pool reaches"
the sump floor. Finally, the model conservatively assumes that none of the produced vapors is
retained by the sump walls.
These conservative assumptions provide the model with a suitable basis for use in this particular
application. Accordingly, we conclude that the DLNG Source Term Model can be used with
DEGADIS to calculate the vapor-gas dispersion exclusion zones for the sumps at the Robbinston
LN G Import Terminal. 9
Question 2
The phenomena known as jetting and flashing can occur if pressurized piping or equipment fails.
Jetting can cause released LNG to propel beyond an impoundment system, or result in
fragmentation and formation of aerosols. It can also erode earthen dikes, expose equipment to
cryogenic liquids, or project LNG or its vapors onto adjacent properties. Flashing is the
instantaneous vaporization of released LNG due to exposure ambient pressure and temperature.
Like jetting, it can cause fragmentation and formation of aerosols and project vapors onto
adjacent properties. Understanding the effect of these phenomena is important to public safety,
as they can create hazards (e.g., cascading failures, the loss of containment, and the
instantaneous formation of a vapor-gas cloud) that are capable of affecting offsite properties and
activities.
You state that Downeast has not considered jetting and flashing in siting the Robbinston LNG
Import Terminal, because the "Part 193 Subpart B LNG Requirements do not speak to either
flashing or jetting and flammable vapor production rate in the event of an LNG leak." You have
asked PHMSA for an opinion to that effect, namely, that "[j]etting and flashing are not to be
considered with respect to the exclusion zone analysis of 49 CFR Section 193.2059." Contrary
to your position, we conclude that these phenomena should be considered in appropriate cases.
8 As in the case of Downeast, those seeking to use an alternative source term model with DEGADIS may obtain an
interpretation from this agency on the suitability of such a model. 49 C.F.R. § 190.11 (2010).
9 Our opinion on the suitability of the DLNG Source Term Model only applies to the sumps and does not address the
adequacy of the exclusion zone analyses performed for any other area at the Robbinston LNG Import Terminal.
3

<<<PAGE 4>>>

The source tenn model used as the input for DEGADIS must have a suitable basis to comply
with our vapor-gas exclusion zone requirements. In the case of jetting and flashing, there is no
dispute that a failure of pressurized piping or equipment may cause LNG to vaporize in the air.
Using a source tenn model that ignores that effect (or any other phenomena that has a similar
influence on the discharge, vaporization, or conveyance of LNG) could distort the downwind
dispersion of vapor gas and compromise the integrity of an operator's exclusion zone analysis.
Such a result would not ensure that the siting of an LNG facility occurs in a manner consistent
with our statutory obligations. Consequently, a source tenn model should account for the effects
of jetting and flashing in appropriate cases, including where a design-spill scenario involves a
failure of pressurized piping or equipment.
Consideration of jetting and flashing might also be required outside the confines of an exclusion
zone analysis. lo For example, steps must be taken to ensure that any released LNG is retained
within the limits of plant property. I That includes "grad[ing], drain[ing], or provid[ing]" certain
areas "with [an] impoundment" to reduce "the possibility of accidental spills and leaks that could
endanger im;ortant structures, equipment, or adjoining property or that could reach
waterways." I Similarly, site-specific factors that have a bearing on the safety of plant personnel
or the surrounding public must be evaluated in siting an LNG facility, and appropriate responsive
safety measures must be incorporated into the design or operation of that facility. 13 However, as
you did not request an interpretation of these or any other provisions, we simply note in closing
that an operator must demonstrate that a new LNG facility complies with our Siting
Requirements. 14
Conclusion
Downeast may use the DLNG Source Tenn Model to calculate the vapor-gas exclusion zone for
the sumps at the Robbinston LNG Import Tenninal. The Company must also examine the
effects of jetting and flashing in calculating the vapor-gas dispersion exclusion zone for any
appropriate LNG facilities, including pressurized piping or equipment, to comply with the Siting
Requirements in Subpart B of 49 C.F.R. Part 193.
Sincerely,
~~
Jeffrey D. Wiese
Associate Administrator
for Pipeline Safety
10 49 C.F.R. § 193.2051 (2010).
II 2001 NFPA 59A, 2.1.2.
12 2001 NFPA 59A, 2.2.1.2.
J3 2001 NFPA 59A, 2.1.1(d).
14 See e.g., 5 U.S.c. § 556(d); Schaffer v. Weast, 546 U.S. 49, 56-57 (2005).
4

<<<PAGE 5>>>

FULBRIGHT & .JAWORSKI L.L.P.
A REGISTERED LIMITED l_IABILITY PARTNERSHIP
666 FIFTH AVENUE. 31ST FLOOR
NEW YORK. NEW YORK 10103-3198
WWW.FULBRIGHT.COM
LISA TONERY
PARTNER
L TO N ERy(oJFU LBRIGHT .CO M
DIRECT DIAL:
TELEPHONE:
FACSIMILE:
( 2 I 2) 3 I 8-3009
( 2 I 2) 3 I 8-3000
(2 I 2) 318-3400
May 10,2010
MAY 11 2010
JetTrey D. Wiese
Associate Administrator for Pipeline Safety
PMHSA
U. S. Department of Transportation
1200 New Jersey Avenue, SE
Washington, DC 20590-0001
Re: Request fOl' Interpretation of 49 CFR Part 193
Dear Mr. Wiese:
Downeast LNG, Inc. (Downeast LNG) has an application pending before the Federal
Energy Regulatory Commission (FERC) in Docket No. CP07-52-000 for authorization to site,
construct and operate a liquefied natural gas (LNG) impOli tenl1inal and associated natural gas
pipeline in Washington County, Maine. In conjunction with that pending application, pursuant to
4() CFR Section 190.11(b)(l), we are requesting an interpretation of the Part 193 Subpart B LNG
Facilities Federal Safety Standards Siting Requirements. Specifically, we seek a written
intcqJretation conceming 49 CFR Section 193.2059 for the items set tcnih below.
Flammable Vapor Source Term
By way of background, in an efTort to develop LNG dispersion model evaluation tools for
the NFPA 59A Committee, the Fire Protection Research Foundation (FPRF) funded research on
LNG spill source teml modeling and, in March, 2009 its findings were included in a repOli
entitled "LNG Source Term Models for Hazard Analysis: A Review of the State-of-the-Art and
an Approach to Model Assessment". The report presented a methodology for assessing the
suitability of LNG source tenl1 models used in determining pool spread and vaporization. The
report concluded that the SOURCE model generally used within the LNG industry, and which
was also used by Downeast LNG in its initial detemlination of flammable vapor dispersion
Exclusion Zones, could result in under-prediction of hazard distances in some cases because it
does not accurately represent:
• Pool spreading and the resulting flammable vapor "tlashing", and
• V apor accumulation within impoundments,
Downeast LNG has prepared a source tem1 calculation that addresses these specific concems and
provides input to the DEGADIS Dense Gas Dispersion Model that is specified in 49 CFR
193.2059. A copy of the calculation (previously filed with FERC on October 30, 2009) is

<<<PAGE 6>>>

Jeffrey D. Wiese
May 10,2010
Page 2
attached to this letter (see Appendix I, "Thcrll/a/ Radiation (flld Vapor Dispersioll Ca/cli/ations
for [)()',Vlleast LNG") and the following summarizes how Downeast LNG has addressed the
particular concems raised by the FPRF:
Pool Spreading and Flammable Vapor Production
The SOURCES pool spreading model on land uses an adaptation of a fairly standard
model for spreading on water. However. it has been known since the mid 1980s to have no
justi fication for spreading on land I . In order to overcome this limitation, the approach proposed
by Downeast LNG has considered a range of spreading speeds across the sump floor, including
instantaneous spreading to identify the speed that generates the longest ignitable vapor cloud
using DEGADIS. In its calculation filed with the FERC on October 30, 2009, Downeast LNG
stated that the instantaneous spreading scenario is the most conservative since it would result in
the longest ignitable vapor cloud. Downeast confil111ed this assumption by parametrically
varying the LNG spreading speed to calculate the rate of evaporation over time. A copy of the
parametric analysis and associated findings is attached to this letter (see Appendix 2, "Dowllcast
LNG - Parametric St/l(!1' oj'the Sensitivi(l' oj'the Vapor Dispersion Distallce to the Rate of
5j)f'('adillg oj'LNG in a SZltlZp").
As the pool spreads, it cools the ground below it. Initially (at least) by far the dominant
mode of heat transfer to a cryogenic pool spilt on land is conduction from the solid ground
below. As the pool spreads over the area of the sump, the ground beneath it will cool very
rapidly, and the heat flux into the pool will decrease with time. The FPRF report found the
SOURCES method of quantifying the rate of evaporation unclear based on an edition of the TNO
Yellow Book which had long been superseded. In the method proposed by Downeast LNG, the
heat transfer to the spreading contlned pool has been calculated assuming perfect thel111al contact
between pool and ground, and only vertical temperature gradients in the ground. The conduction
has been modeled by the one-dimensional Fourier conduction equation in the ground, with an
initial state where the ground is unifonnly at ambient temperature, and assumes the boiling
temperature of LNG as soon as the spreading pool reaches it. This is considered a good model in
the early stages of the spill when rates of evaporation are high according to the FPRF report.
Flammable Vapor Retention
The SOURCES model defines the source of vapor to be precisely zero until the liquid
depth, plus the depth of vaporized (but undiluted) LNG, becomes equal to the height of the dike
wall. This is not credible if there is any wind at all. Flllihennore, air entrainment and mixing
during the evaporation process will also dilute the LNG vapors. For these reasons, the calculation
prepared by Downeast LNG does not take credit for any vapor retention or hold-up within the
sump. This approach results in an earlier release of vapors at a time when the rate of evaporation
;'vlodel Assessment Report on SOURCE5 Version 5 revision I. LNG Source Term Models tCll' Hazard Analysis: a
Review of the State-of-the-Art and an Approach to Model Assessment, Final Report, .. Prepared by: Dr D.M.
Webber, Dr S.E. Gant. DrMLlvings arrdS.F. Jagger, Health & Safety Laooratury, March lBB(}.

<<<PAGE 7>>>

, '
Jeffrey D. Wiese
May 10,2010
Page 3
is at its highest and higher than the rate of evaporation when the vapors begin to spill out of
retention in the SOURCES model. In reality, sump walls do provide some degree of vapor
retention and hold-up. Therefore, the method used by Downeast LNG results in a rate of vapor
fonmltion that is larger than would be expected in reality. 2
Jetting and Flashing
In the Draft Environmental Impact Statement (DEIS) issued by FERC for the Downeast
LNG project in May 2009, FERC included a condition that requires Downeast LNG to "examine
provisions to minimize any effects from flashing or jetting on the downward dispersion distance
of vapor fr0111 a release from pressurized piping at the LNG terminal.'"
The previously referenced FPRF study considered jetting and flashing and its repOli states
that a leak from a pressurized pipeline may lead initially to jetting of the liquid, and if the jet is
unobstructed, a large fraction of the LNG may vaporize in the air before the liquid rains out and
forms a pool. The FPRF repOli also states that the nature of the jet, and hence the amount of
vaporization from the jet, will depend upon the ambient temperature, the pressure and
temperature of the LNG, the initial velocity of the liquid, the orifice size and shape, the fluid
traj cctory, atomization of the liquid spray, and the entrainment rate of fresh air.
Notably, since the Part 193 Subpart B LNG Siting Requirements do not speak to either
flashing or jetting and flammable vapor production rate in the event of an LNG leak the
DO\vneast LNG application did not specifically address the considerations in its design.
Request for Interpretation of 49 CFR Part 193
Downeast LNG is requesting an interpretation that:
( 1 ) Use of the foregoing methodology as summarized above and described in greater
detail in Appendices 1 and 2 is consistent and in compliance with 49 CFR Section
193.2059; and
(2) Jetting and flashing are not to be considered with respect to the exclusion zone
analysis of 49 CFR Section 193.2059.
Downeast LNG respectfully requests that the above-requested guidance be provided at the
earliest date possible so that the Downeast LNG project may move forward in the FERC
2 See p. J 4 Model Assessment Report on SOURCES Version S revision 1. Ref No. CE51{)4 iv/A RIHSUSOUR,
\' ersion 4 February 2009, in Appendix A of "LNG Source Term Models for Hazard Analysis: a Review of the
State-of-the-Art and an Approach to Model Assessment, Final Report, " Prepared by: Dr D.M. Webber, Dr S.E.
Ciant, Dr M.J. Ivings and S.F. Jagger, Health & Safety Laboratory. March 2009
3 See Dowrieast LNG DEIS Condition 40 (May 2009)

<<<PAGE 8>>>

Jeffrey D. Wiese
May 10,2010
Page 4
pellnitting process. To that end, please feel free to contact the undersigned with any questions
conceming the foregoing.
ectfully submitted,
.. ~.\~~:r'Z;\
i a M. T onery (':::J
Attorncv {or Dml'IIC{{st LNG. file.
Attachments
cc: Charles Helm
Keith Coyle
TeITY Turpin
Dean Girdis
Arthur Ransome
HaITi Kytomaa

## Provenance

- Official: Yes
- Source: <https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/2010/PI-10-0005.pdf>
- Source ID: `phmsa`
- SHA-256: `babc28bb4cac8f1acdad11c7f4d27dec3201c63d38a2b6eb62537bb17dd491e1`
- Retrieved: 2026-08-20T00:59:31.977Z
- Exported: 2026-08-23T23:56:21.615Z
- Document slug: `phmsa-interpretation-pi-10-0005`

### Source metadata

```json
{
  "materialSubtype": "interpretation",
  "interpretationArea": "pipeline_safety",
  "representation": "full_text_from_official_pdf",
  "companies": [
    "Fulbright & Jaworski L.L.P."
  ],
  "individuals": [
    "Ms. Lisa M. Tonery"
  ],
  "refIds": [
    "PI-10-0005"
  ],
  "catalogDates": [
    "2010-07-16"
  ],
  "catalogParts": [
    193
  ],
  "catalogRowCount": 1,
  "sourceRecordUrls": [
    "https://www.phmsa.dot.gov/node/56896"
  ],
  "linkedAttachmentUrls": [],
  "unavailableResponseUrls": [],
  "duplicateRepresentationUrls": [],
  "citedSections": [
    "193.2059",
    "193.2057(a)",
    "190.1",
    "190.11",
    "193.2051"
  ],
  "catalogPageUrls": [
    "https://www.phmsa.dot.gov/regulations/title49/section/1932059"
  ],
  "pdfUrls": [
    "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/2010/PI-10-0005.pdf"
  ],
  "representations": [
    {
      "viewUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/2010/PI-10-0005.pdf",
      "detailUrl": null,
      "detailHtmlPath": null,
      "pdfUrl": "https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/2010/PI-10-0005.pdf",
      "pdfArtifactPath": "data/sources/phmsa-interpretations/pi-10-0005.pdf",
      "pdfArtifactSha256": "8ba4214ef46580b6306666e3f87e6dc9adf9d1c9a69494924dde963d9879d34c",
      "extractedTextPath": "data/sources/phmsa-interpretations/pi-10-0005.v2.txt",
      "extractedTextSha256": "7c12bdfb8d0fe6e7f8df7deae55d57fc37285a359fdf291d84cb30eb2c992885",
      "pageCount": 8,
      "extractionVersion": 2
    }
  ],
  "caveat": "Interpretations apply regulations to the facts presented and do not create independently enforceable requirements.",
  "jurisdiction": "US"
}
```