# Customer meter installations: Operating pressure.

- **operation:** document
- **citation:** 49 CFR 192.359
- **title:** Customer meter installations: Operating pressure.
- **source type:** regulation
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** 2026-08-18
- **summary:** (a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure.

(b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage.

(c) A rebuilt or repaired tinned steel case meter ma
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/49-cfr-192-359.json
- **markdown:** https://regulus.evalyn.ai/document/49-cfr-192-359.md
- **app url:** https://regulus.evalyn.ai/document/49-cfr-192-359
- **source url:** https://www.ecfr.gov/on/2026-08-18/title-49/section-192.359
**body:**

(a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure.

(b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage.

(c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing.

[35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-1, 35 FR 17660, Nov. 17, 1970; Amdt. 192-85, 63 FR 37503, July 13, 1998]