{"operation":"document","citation":"49 CFR 193.2817","title":"Fire equipment.","source_type":"regulation","agency":"Pipeline and Hazardous Materials Safety Administration","status":"historical","official":true,"published_on":null,"effective_on":"1999-10-01","summary":"(a) Each operator shall determine: (1) The types and sizes of fires that may reasonably be expected to occur within and adjacent to each LNG plant that could affect the safety of components; and\n\n(2) The foreseeable consequences of these fires, including the failure of components or buildings due to","machine_formats":{"json":"https://regulus.evalyn.ai/document/49-cfr-193-2817.json","markdown":"https://regulus.evalyn.ai/document/49-cfr-193-2817.md"},"app_url":"https://regulus.evalyn.ai/document/49-cfr-193-2817","source_url":"https://www.govinfo.gov/app/details/CFR-1999-title49-vol3/CFR-1999-title49-vol3-sec193-2817","body":"(a) Each operator shall determine: (1) The types and sizes of fires that may reasonably be expected to occur within and adjacent to each LNG plant that could affect the safety of components; and\n\n(2) The foreseeable consequences of these fires, including the failure of components or buildings due to heat exposure.\n\n(b) Each operator shall provide and maintain fire control equipment and supplies in accordance with the applicable requirements of ANSI/NFPA 59A to protect or cool components that could fail due to heat exposure from fires determined under paragraph (a) of this section and either worsen an emergency or endanger persons or property located outside the plant. Protection or cooling must be provided for as long as the heat exposure exists. The fire control equipment and supplies must include the following:\n\n(1) Portable fire extinguishers suitable for types of fires identified under paragraph (a) of this section; and\n\n(2) If the total inventory of LNG is 265 m3 (70,000 gal.) or more, a water supply and associated delivery system.\n\n(c) Each operator shall determine the type, size, quantity and location of the fire control equipment and supplies required under paragraph (b) of this section.\n\n(d) Each operator shall provide each facility person who may be endangered by exposure to fire or the products of combustion in performing fire control duties protective clothing and equipment, including, if necessary, a self-contained breathing apparatus.\n\n(e) Portable fire control equipment, protective clothing and equipment for personnel use, controls for fixed fire control equipment, and fire control supplies must be conspicuously located, marked for easy recognition, and readily available for use.\n\n(f) Fire control equipment must have operating instructions. Instructions must be attached to portable equipment and placed at the location of controls for fixed equipment.\n\n[45 FR 9203, Feb. 11, 1980, as amended at 58 FR 14522, Mar. 18, 1993]","truncated":false,"body_characters":1968}