# Pipeline location.

- **operation:** document
- **citation:** 49 CFR 195.210
- **title:** Pipeline location.
- **source type:** regulation
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** 2026-08-18
- **summary:** (a) Pipeline right-of-way must be selected to avoid, as far as practicable, areas containing private dwellings, industrial buildings, and places of public assembly.

(b) No pipeline may be located within 50 feet (15 meters) of any private dwelling, or any industrial building or place of public assem
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/49-cfr-195-210.json
- **markdown:** https://regulus.evalyn.ai/document/49-cfr-195-210.md
- **app url:** https://regulus.evalyn.ai/document/49-cfr-195-210
- **source url:** https://www.ecfr.gov/on/2026-08-18/title-49/section-195.210
**body:**

(a) Pipeline right-of-way must be selected to avoid, as far as practicable, areas containing private dwellings, industrial buildings, and places of public assembly.

(b) No pipeline may be located within 50 feet (15 meters) of any private dwelling, or any industrial building or place of public assembly in which persons work, congregate, or assemble, unless it is provided with at least 12 inches (305 millimeters) of cover in addition to that prescribed in § 195.248.

[Amdt. 195-22, 46 FR 39360, July 27, 1981, as amended by Amdt. 195-63, 63 FR 37506, July 13, 1998]
- **truncated:** false
- **body characters:** 569
