# Customer Meter Installations: Operating Pressure

- **operation:** document
- **citation:** 192.359
- **title:** Customer Meter Installations: Operating Pressure
- **source type:** regulation
- **agency:** Arkansas Public Service Commission
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** Not available
- **summary:** § 192.359 Customer Meter Installations: Operating Pressure (a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure. (b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) g
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/ar-car-23-500-192-359.json
- **markdown:** https://regulus.evalyn.ai/document/ar-car-23-500-192-359.md
- **app url:** https://regulus.evalyn.ai/document/ar-car-23-500-192-359
- **source url:** https://codeofarrules.arkansas.gov/Rules/Rule?chapterID=40&levelType=part&partID=1394&subChapterID=392&titleID=23
**body:**

§ 192.359 Customer Meter Installations: Operating Pressure (a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure. (b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage. (c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing.
- **truncated:** false
- **body characters:** 483