{"operation":"document","citation":"192.509","title":"Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage","source_type":"regulation","agency":"Arkansas Public Service Commission","status":"current","official":true,"published_on":null,"effective_on":null,"summary":"§ 192.509 Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage Except for service lines and plastic pipelines, each segment of a pipeline that is to be operated below 100 p.s.i.g. must be leak tested in accordance with the following: (a) The test procedure used must reasonably ","machine_formats":{"json":"https://regulus.evalyn.ai/document/ar-car-23-500-192-509.json","markdown":"https://regulus.evalyn.ai/document/ar-car-23-500-192-509.md"},"app_url":"https://regulus.evalyn.ai/document/ar-car-23-500-192-509","source_url":"https://codeofarrules.arkansas.gov/Rules/Rule?chapterID=40&levelType=part&partID=1394&subChapterID=392&titleID=23","body":"§ 192.509 Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage Except for service lines and plastic pipelines, each segment of a pipeline that is to be operated below 100 p.s.i.g. must be leak tested in accordance with the following: (a) The test procedure used must reasonably ensure discovery of leaks in the segment being tested. (b) Each main that is to be operated at less than 1 p.s.i. (6.9 kPa) gage must be tested to at least 10 p.s.i. (69 kPa) gage and each main to be operated at or above 1 p.s.i. (6.9 kPa) gage must be tested to at least 90 p.s.i. (621 kPa) gage.","truncated":false,"body_characters":597}