# Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage

- **operation:** document
- **citation:** 192.509
- **title:** Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage
- **source type:** regulation
- **agency:** Arkansas Public Service Commission
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** Not available
- **summary:** § 192.509 Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage Except for service lines and plastic pipelines, each segment of a pipeline that is to be operated below 100 p.s.i.g. must be leak tested in accordance with the following: (a) The test procedure used must reasonably 
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/ar-car-23-500-192-509.json
- **markdown:** https://regulus.evalyn.ai/document/ar-car-23-500-192-509.md
- **app url:** https://regulus.evalyn.ai/document/ar-car-23-500-192-509
- **source url:** https://codeofarrules.arkansas.gov/Rules/Rule?chapterID=40&levelType=part&partID=1394&subChapterID=392&titleID=23
**body:**

§ 192.509 Test Requirements for Pipelines to Operate Below 100 P.S.I. (689 kPa) Gage Except for service lines and plastic pipelines, each segment of a pipeline that is to be operated below 100 p.s.i.g. must be leak tested in accordance with the following: (a) The test procedure used must reasonably ensure discovery of leaks in the segment being tested. (b) Each main that is to be operated at less than 1 p.s.i. (6.9 kPa) gage must be tested to at least 10 p.s.i. (69 kPa) gage and each main to be operated at or above 1 p.s.i. (6.9 kPa) gage must be tested to at least 90 p.s.i. (621 kPa) gage.
- **truncated:** false
- **body characters:** 597