{"operation":"document","citation":"192.706","title":"Transmission Lines: Leakage Surveys","source_type":"regulation","agency":"Arkansas Public Service Commission","status":"current","official":true,"published_on":null,"effective_on":null,"summary":"§ 192.706 Transmission Lines: Leakage Surveys Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas in conformity with § 192.625 without an odor or odorant,","machine_formats":{"json":"https://regulus.evalyn.ai/document/ar-car-23-500-192-706.json","markdown":"https://regulus.evalyn.ai/document/ar-car-23-500-192-706.md"},"app_url":"https://regulus.evalyn.ai/document/ar-car-23-500-192-706","source_url":"https://codeofarrules.arkansas.gov/Rules/Rule?chapterID=40&levelType=part&partID=1394&subChapterID=392&titleID=23","body":"§ 192.706 Transmission Lines: Leakage Surveys Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas in conformity with § 192.625 without an odor or odorant, leakage surveys using leak detector equipment must be conducted: (a) In Class 3 locations, at intervals not exceeding 7 1/2 months, but at least twice each calendar year; and (b) In Class 4 locations, at intervals not exceeding 4 1/2 months, but at least four times each calendar year.","truncated":false,"body_characters":586}