# Transmission Lines: Leakage Surveys

- **operation:** document
- **citation:** 192.706
- **title:** Transmission Lines: Leakage Surveys
- **source type:** regulation
- **agency:** Arkansas Public Service Commission
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** Not available
- **summary:** § 192.706 Transmission Lines: Leakage Surveys Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas in conformity with § 192.625 without an odor or odorant,
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/ar-car-23-500-192-706.json
- **markdown:** https://regulus.evalyn.ai/document/ar-car-23-500-192-706.md
- **app url:** https://regulus.evalyn.ai/document/ar-car-23-500-192-706
- **source url:** https://codeofarrules.arkansas.gov/Rules/Rule?chapterID=40&levelType=part&partID=1394&subChapterID=392&titleID=23
**body:**

§ 192.706 Transmission Lines: Leakage Surveys Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas in conformity with § 192.625 without an odor or odorant, leakage surveys using leak detector equipment must be conducted: (a) In Class 3 locations, at intervals not exceeding 7 1/2 months, but at least twice each calendar year; and (b) In Class 4 locations, at intervals not exceeding 4 1/2 months, but at least four times each calendar year.
- **truncated:** false
- **body characters:** 586