{"operation":"document","citation":"RCSA § 16-280b-A47","title":"Active Corrosion","source_type":"regulation","agency":"Connecticut Public Utilities Regulatory Authority","status":"current","official":true,"published_on":"2025-06-11","effective_on":"2025-06-11","summary":"(a) For purposes of this section and the Federal Regulations, \"Active Corrosion\" has the same meaning as provided in 49 CFR 192.3, as amended from time to time, and anywhere there are 3 or more corrosion leaks within any 400-foot diameter in the previous 10 years on non-cathodically protected Pipelines. (b) Pipelines s","machine_formats":{"json":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-a47.json","markdown":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-a47.md"},"app_url":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-a47","source_url":"https://eregulations.ct.gov/eRegsPortal/Search/getDocument?guid=%7BE04F6097-0000-CC1C-9D68-25A0BA411C82%7D","body":"(a) For purposes of this section and the Federal Regulations, \"Active Corrosion\" has the same meaning as provided in 49 CFR 192.3, as amended from time to time, and anywhere there are 3 or more corrosion leaks within any 400-foot diameter in the previous 10 years on non-cathodically protected Pipelines. (b) Pipelines shall be cathodically protected not later than 1 year or replaced not later than 3 years after Active Corrosion is identified.","truncated":false,"body_characters":445}