{"operation":"document","citation":"RCSA § 16-280b-A50","title":"Cathodic protection","source_type":"regulation","agency":"Connecticut Public Utilities Regulatory Authority","status":"current","official":true,"published_on":"2025-06-11","effective_on":"2025-06-11","summary":"In accordance with Appendix D to 49 CFR 192, as amended from time to time: (1) only depolarized voltages acquired during the previous 5 years may be used to demonstrate a 100-millivolt shift under section I.A.3; and (2) determination of the voltage measurement in section II shall be made in accordance with one of the f","machine_formats":{"json":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-a50.json","markdown":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-a50.md"},"app_url":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-a50","source_url":"https://eregulations.ct.gov/eRegsPortal/Search/getDocument?guid=%7BE04F6097-0000-CC1C-9D68-25A0BA411C82%7D","body":"In accordance with Appendix D to 49 CFR 192, as amended from time to time: (1) only depolarized voltages acquired during the previous 5 years may be used to demonstrate a 100-millivolt shift under section I.A.3; and (2) determination of the voltage measurement in section II shall be made in accordance with one of the following: (A) for impressed current systems: (i) interrupting the current and measuring the instant-off potential; or (ii) using engineered coupons; or (B) for galvanic anode systems, the reading shall be taken as close to the Pipeline as practical. 18","truncated":false,"body_characters":572}