{"operation":"document","citation":"RCSA § 16-280b-C9","title":"Odorization of Petroleum Gas","source_type":"regulation","agency":"Connecticut Public Utilities Regulatory Authority","status":"current","official":true,"published_on":"2025-06-11","effective_on":"2025-06-11","summary":"The periodic sampling required pursuant to 49 CFR 192.625(f), as amended from time to time, shall be performed: (1) at least 4 times each calendar year, but at intervals not exceeding 4½ months unless the Operator justifies a reduced frequency in their Procedures; and (2) at sufficient locations to ensure that all Petr","machine_formats":{"json":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-c9.json","markdown":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-c9.md"},"app_url":"https://regulus.evalyn.ai/document/ct-rcsa-16-280b-c9","source_url":"https://eregulations.ct.gov/eRegsPortal/Search/getDocument?guid=%7BE04F6097-0000-CC1C-9D68-25A0BA411C82%7D","body":"The periodic sampling required pursuant to 49 CFR 192.625(f), as amended from time to time, shall be performed: (1) at least 4 times each calendar year, but at intervals not exceeding 4½ months unless the Operator justifies a reduced frequency in their Procedures; and (2) at sufficient locations to ensure that all Petroleum Gas within each Petroleum Gas Distribution System contains the required odorant concentration.","truncated":false,"body_characters":420}