{"operation":"document","citation":"81 FR 70987","title":"Pipeline Safety: Expanding the Use of Excess Flow Valves in Gas Distribution Systems to Applications Other Than Single-Family Residences","source_type":"rulemaking","agency":"Pipeline and Hazardous Materials Safety Administration","status":"historical","official":true,"published_on":"2016-10-14","effective_on":"2017-04-14","summary":"Excess flow valves (EFV), which are safety devices installed on natural gas distribution pipelines to reduce the risk of accidents, are currently required for new or replaced gas service lines servicing single-family residences (SFR), as that phrase is defined in 49 CFR 192.383(a). This final rule makes changes to part 192 to expand this requirement to include new or replaced branched service lines servicing SFRs, multifamily residences, and small commercial entities consuming gas volumes not exceeding 1,000 Standard Cubic Feet per Hour (SCFH). PHMSA is also amending part 192 to require the use of either manual service line shut-off valves (e.g., curb valves) or EFVs, if appropriate, for new or replaced service lines with meter capacities exceeding 1,000 SCFH. Lastly, this final rule requires operators to notify customers of their right to request installation of an EFV on service lines that are not being newly installed or replaced. PHMSA has left the question of who bears the cost of installing EFVs on service lines not being newly installed or replaced to the operator's rate- setter.","machine_formats":{"json":"https://regulus.evalyn.ai/document/federal-register-2016-24817.json","markdown":"https://regulus.evalyn.ai/document/federal-register-2016-24817.md"},"app_url":"https://regulus.evalyn.ai/document/federal-register-2016-24817","source_url":"https://www.federalregister.gov/documents/2016/10/14/2016-24817/pipeline-safety-expanding-the-use-of-excess-flow-valves-in-gas-distribution-systems-to-applications","body":"Federal Register, Volume 81 Issue 199 (Friday, October 14, 2016) [Federal Register Volume 81, Number 199 (Friday, October 14, 2016)] [Rules and Regulations] [Pages 70987-71002] From the Federal Register Online via the Government Publishing Office [ www.gpo.gov ] [FR Doc No: 2016-24817] ----------------------------------------------------------------------- DEPARTMENT OF TRANSPORTATION Pipeline and Hazardous Materials Safety Administration 49 CFR Part 192 [Docket No. PHMSA-2011-0009; Amdt. No 192-121] RIN 2137-AE71 Pipeline Safety: Expanding the Use of Excess Flow Valves in Gas Distribution Systems to Applications Other Than Single-Family Residences AGENCY: Pipeline and Hazardous Materials Safety Administration (PHMSA), DOT. ACTION: Final rule. ----------------------------------------------------------------------- SUMMARY: Excess flow valves (EFV), which are safety devices installed on natural gas distribution pipelines to reduce the risk of accidents, are currently required for new or replaced gas service lines servicing single-family residences (SFR), as that phrase is defined in 49 CFR 192.383(a). This final rule makes changes to part 192 to expand this requirement to include new or replaced branched service lines servicing SFRs, multifamily residences, and small commercial entities consuming gas volumes not exceeding 1,000 Standard Cubic Feet per Hour (SCFH). PHMSA is also amending part 192 to require the use of either manual service line shut-off valves (e.g., curb valves) or EFVs, if appropriate, for new or replaced service lines with meter capacities exceeding 1,000 SCFH. Lastly, this final rule requires operators to notify customers of their right to request installation of an EFV on service lines that are not being newly installed or replaced. PHMSA has left the question of who bears the cost of installing EFVs on service lines not being newly installed or replaced to the operator's rate- setter. DATES: This final rule is effective April 14, 2017. FOR FURTHER INFORMATION CONTACT: Technical questions: Vincent Holohan, General Engineer, by telephone at 202-366-1933 or by electronic mail at [email&#160;protected] . General information: Robert Jagger, Technical Writer, by telephone at 202-366-4361 or by electronic mail at [email&#160;protected] . SUPPLEMENTARY INFORMATION: I. Executive Summary A. Purpose of the Regulatory Action EFVs can reduce the risk of explosions in natural gas distribution pipelines by shutting off unplanned, excessive gas flows. These events are primarily the result of excavation damage to service lines that occurs between the gas main and the customer's building. Based on the comments to this rulemaking, PHMSA experience, and various studies, PHMSA has determined that the safety benefits of expanding the use of EFVs to new or entirely replaced distribution branch services (gas service lines that begin at an existing service line or that are installed concurrently with primary service lines but serve separate residences), multifamily facilities, and small commercial facilities is appropriate from a technical, economical, and operational feasibility standpoint. B. Summary of the Major Provisions of the Regulatory Action Pursuant to Section 22 of the Pipeline Safety, Regulatory Certainty, and Job Creation Act of 2011, this final rule amends the Federal pipeline safety regulations by adding four new categories of service for which EFV installation will be required. These four new categories are for new and entirely replaced services. The existing EFV installation requirement for SFRs served by a single service line remains unchanged. The new categories of service are as follows: Branched service lines to a SFR installed concurrently with the primary SFR service line (a single EFV may be installed to protect both lines); Branched service lines to a SFR installed off a previously installed SFR service line that does not contain an EFV; [[Page 70988]] Multifamily installations, including duplexes, triplexes, fourplexes, and other small multifamily buildings (e.g., apartments, condominiums) with known customer loads at time of service installation, based on installed meter capacity, up to 1,000 SCFH per service; \\1\\ and --------------------------------------------------------------------------- \\1\\ The average single-family home uses about 200 standard cubic feet of gas per day and individual apartment units use even less. --------------------------------------------------------------------------- A single, small commercial customer served by a single service line, with a known customer load at time of service installation, based on installed meter capacity, of up to 1,000 SCFH per service. Operators will be required to give all customers notice of the option to request an EFV installation, except where such installation is not required under Sec. 192.383(c) (i.e., where the service line does not operate at a pressure of 10 psig or greater through the year, the operator has experienced contaminants in the gas stream that could interfere with EFV operation, an EFV could interfere with operation and maintenance activities, or an EFV meeting performance standards in Sec. 192.381 is not available). Finally, this final rule also amends the Federal pipeline safety regulations by requiring curb valves, or EFVs, if appropriate, for applications operating above 1,000 SCFH. C. Costs and Benefits PHMSA estimates a total impacted community of 4,448 operators for this rule (3,119 master meter/small LPG operators who will need to comply with notification requirements and 1,329 natural gas distribution operators who will need to install valves and comply with notification requirements) and 222,114 service lines per year on average. It is expected to generate safety benefits in the form of reduced fatalities, injuries, lost product, and other property damage from certain types of preventable incidents in gas distribution pipelines. The overall benefits over a 50-year period were estimated at the annual equivalent of $5.5 million per year versus $10.6 million in compliance costs when calculated using a 7 percent discount rate. When using a 3 percent discount rate, the total benefits of the rule were estimated at $10.5 million while the costs were estimated at $12.0 million. II. Background A. Excess Flow Valves and Curb Valves An EFV is a mechanical safety device installed inside a natural gas distribution service line between the street and residential meter. If there is a significant increase in the flow of gas (e.g., due to a damaged line), the EFV will ``trip'' or close to minimize the flow of gas through the line and thus, the amount of gas escaping into the atmosphere. During normal use, the valve is kept pushed open against oncoming gas flow by a spring. EFVs are designed so that general usage, such as turning on appliances, will not shut the valve. However, during a significant increase in the flow of gas (e.g., due to a damaged line), the spring cannot overcome the force of gas, and the valve will close and stay closed until the correct pressure is restored. When the correct pressure is restored, the EFV automatically resets itself. Curb valves are installed below grade in a service line at or near the property line with a protective curb box or standpipe for quick subsurface access and are operated by use of a removable key or specialized wrench. B. The South Riding, VA, Incident On July 7, 1998, in South Riding, VA, an explosion stemming from a residential service line resulted in one death and three injuries. It is not known if the explosion occurred on a branched or non-branched service line, but PHMSA believes that this final rule or PHMSA's previous rule requiring EFVs on single lines serving SFRs \\1\\ would, at a minimum, have mitigated the consequences of the explosion. --------------------------------------------------------------------------- \\1\\ ``Pipeline Safety: Integrity Management Programs for Gas Distribution Pipelines,'' 74 FR 63906 (December 4, 2009), RIN 2137- AE15. --------------------------------------------------------------------------- An investigation by the National Transportation Safety Board (NTSB) found the explosion likely would not have occurred if an EFV had been installed on the service line leading to this single-family home. As a result of its investigation, on June 22, 2001, the NTSB issued Safety Recommendation P-01-2, recommending that PHMSA ``require that EFVs be installed in all new and renewed gas service lines, regardless of a customer's classification (i.e., not just lines serving single-family residences), when the operating conditions are compatible with readily available valves.'' C. PHMSA's EFV Studies and Evaluation Report In December 2005, a multi-stakeholder group convened by PHMSA published a report titled: ``Integrity Management for Gas Distribution: Report of Phase I Investigations.'' \\2\\ The report recommended that ``[A]s part of its distribution integrity management plan, an operator should consider the mitigative value of EFVs. EFVs meeting performance criteria in Sec. 192.381 and installed in accordance with Sec. 192.383 may reduce the need for other mitigation options.'' --------------------------------------------------------------------------- \\2\\ http://www.regulations.gov/contentStreamer?documentId=PHMSA-RSPA-2004-19854-0070&attachmentNumber=1&disposition=attachment&contentType=pdf --------------------------------------------------------------------------- In an effort to study the possible benefits of expanding EFVs beyond SFR applications, PHMSA began development of an Interim Evaluation in early 2009. In June and August of that year, PHMSA held public meetings on NTSB Recommendation P-01-2 with participants from the following major stakeholder groups: the National Association of Regulatory Utility Commissioners, the National Association of Pipeline Safety Representatives, the International Association of Fire Chiefs, the National Association of State Fire Marshals, natural gas distribution operators, trade associations, manufacturers, and the Pipeline Safety Trust. On December 4, 2009, PHMSA amended the pipeline safety regulations to require the use of EFVs for new or replaced gas lines servicing SFRs.\\3\\ While this requirement met the mandate of the Pipeline Inspection, Protection, Enforcement, and Safety Act enacted in 2006, other distribution lines, including those that served branched SFRs, apartment buildings, other multi-residential dwellings, commercial properties, and industrial service lines, were still not required to use EFVs. These structures are susceptible to the same risks as SFR service lines. --------------------------------------------------------------------------- \\3\\ ``Pipeline Safety: Integrity Management Programs for Gas Distribution Pipelines,'' December 4, 2009, (74 FR 63906) RIN 2137- AE15. --------------------------------------------------------------------------- PHMSA, already aware of this risk, issued a report in 2010 titled: ``Interim Evaluation: NTSB Recommendation P-01-2 Excess Flow Valves in Applications Other Than Service Lines Serving One SFR'' (Interim Evaluation),\\4\\ which studied the possible expansion of EFVs beyond SFRs and the challenges involved with such expansion. The Interim Evaluation also addressed other [[Page 70989]] practical alternatives, such as the use of manual isolation devices (e.g., curb valves) to quickly cut off the uncontrolled flow of gas in an emergency. The Interim Evaluation also identified challenges related to the feasibility and practicality of the proposed solutions, as well as significant cost and benefit factors. The report found that there were no other devices or viable options to shut off gas supply quickly when gas service lines ruptured. --------------------------------------------------------------------------- \\4\\ The purpose of the Interim Evaluation was to respond to NTSB Safety Recommendation P-01-02 and evaluate the possibility of expansion of EFVs to applications other than service lines serving one single-family residence (above 10 psig). The report also built a foundation for an economic analysis, considered the need for enhanced technical standards or guidelines, and suggested that any new technical standards include criteria for pressure drops across the EFV. The Interim Evaluation can be found at the following link: http://www.regulations.gov/contentStreamer?documentId=PHMSA-2011-0009-0002&attachmentNumber=1&disposition=attachment&contentType=pdf . The Interim Evaluation was finalized in 2015 based on comments to the Interim Report. --------------------------------------------------------------------------- The Evaluation \\5\\ was finalized in 2015, based on comments to the Interim Evaluation, input from the meetings, and comments to the Advance Notice of Proposed Rulemaking (ANPRM) discussed below. Both reports can be found in Docket PHMSA-2011-0009. --------------------------------------------------------------------------- \\5\\ http://www.regulations.gov/contentStreamer?documentId=PHMSA-2011-0009-0027&attachmentNumber=1&disposition=attachment&contentType=pdf . --------------------------------------------------------------------------- D. Advance Notice of Proposed Rulemaking PHMSA published an ANPRM for gas pipelines on November 25, 2011 (76 FR 72666), asking the public to comment on the findings of the Interim Evaluation and issues relating to the expanded use of EFVs in gas distribution systems. PHMSA also sought comments from gas distribution operators on their experiences using EFVs, including: Technical challenges of installing EFVs on services other than SFRs; Categories of service to be considered for expanded EFV use; Cost factors; Data analysis in the Interim Evaluation; Technical standards for EFV devices; and Potential safety and societal benefits, small-business and environmental impacts, and the costs of modifying the existing regulatory requirements. PHMSA reviewed all of the comments received in response to the ANPRM. The comments received from the trade associations largely supported expanded EFV use, with certain limitations. Individual operators raised concerns about expanded EFV use that were generally related to logistics and implementation. Comments from municipalities reflected a concern that State laws that were already in place could conflict with new Federal requirements. The NTSB expressed strong support for increased EFV use. The ANPRM comments collectively helped PHMSA finalize the Interim Evaluation and determine what regulatory changes to propose in the Notice of Proposed Rulemaking (NPRM). E. Pipeline Safety, Regulatory Certainty, and Job Creation Act of 2011 In January of 2012, President Obama signed the Pipeline Safety, Regulatory Certainty, and Job Creation Act of 2011, which required PHMSA to study the possibility of expanding the use of EFVs beyond SFRs and issue a final report to Congress on the evaluation of the NTSB's recommendation on EFVs within 2 years after enactment of the Act. PHMSA was also required to issue regulations, if appropriate, requiring the use of EFVs or equivalent technology for new or entirely replaced gas distribution branch services, multifamily facilities, and small commercial facilities if economically, technically and operationally feasible. F. Notice of Proposed Rulemaking PHMSA published an NPRM (80 FR 41460) on July 15, 2015, asking the public to comment on the findings of the finalized Evaluation and PHMSA's proposals relating to the expanded use of EFVs in gas distribution systems. PHMSA proposed a rule that would: Expand the EFV requirement to include new or replaced branched service lines servicing SFRs, multifamily residences, and small commercial entities consuming gas volumes not exceeding 1,000 SCFH; Require the use of manual service line shut-off valves (e.g., curb valves) for new or replaced service lines with meter capacities exceeding 1,000 SCFH; Require operators to notify customers of their right to request installation of an EFV on existing service lines; and Leave the question of who bears the cost of installing EFVs on service lines not being newly installed or replaced to the operator, customer, and the appropriate State regulatory agency. III. Gas Pipeline Advisory Committee The Technical Pipeline Safety Standards Committee (otherwise commonly referred to as the Gas Pipeline Advisory Committee (GPAC)) is a statutorily mandated advisory committee that advises PHMSA on proposed safety standards, risk assessments, and safety policies for natural gas pipelines. The GPAC was established under the Federal Advisory Committee Act (Pub. L. 92-463, 5 U.S.C. App. 1-16) and the Federal Pipeline Safety Statutes (49 U.S.C. Chap. 601). The committee consists of 15 members, with membership equally divided among Federal and State agencies, the regulated industry, and the public. The GPAC advises PHMSA on the technical feasibility, practicability, and cost- effectiveness of each proposed natural gas pipeline safety standard. On December 17, 2015, the GPAC met via a teleconference facilitated by PHMSA at PHMSA's headquarters in Washington, DC. During the meeting, the GPAC considered the specific regulatory proposals set forth in the NPRM and discussed the various comments and edits to the NPRM proposed by the pipeline industry and the public. The GPAC, in a unanimous 8-0 vote, found the NPRM, as published in the Federal Register, and the Draft Regulatory Evaluation to be technically feasible, reasonable, cost-effective, and practicable, if (1) changes were made relative to Sec. 192.385 paragraphs (a) and (c), as amended during the meeting; and (2) PHMSA incorporated the preamble language regarding documentation of customer notification in Sec. 192.383(f). The GPAC recommended that PHMSA adopt the following changes: Curb Valve Accessibility for First Responders: PHMSA's proposal in the NPRM stated that manual service line shut-off valves are ``a curb valve or other manually operated valve located near the service main or a common source of supply that is accessible to first responders and operator personnel [. . .] in the event of an emergency.'' The GPAC recommended that the final rule remove language requiring proposed manual service line shut-off valves be accessible to ``first responders and operator personnel.'' Instead, the GPAC suggested that the rule require such valves be ``accessible to operator personnel or other personnel authorized by the operator.'' Several members of the GPAC shared the concerns of industry commenters that first responders would attempt to operate these manual service line shut-off valves without operator consent or authorization, which might lead to further or otherwise unforeseen consequences, including service outages. By allowing such valves to be used by ``other personnel authorized by the operator,'' operators could have discretion to ensure that people familiar with the gas distribution systems in question be qualified and authorized to operate manual service line shut-off valves, which might include properly trained emergency responders. Curb Valve Maintenance: PHMSA's proposal in the NPRM defined a manual service line shut-off valve as ``a curb valve or other manually operated valve located near the service main or a common source of supply that is accessible to first responders and [[Page 70990]] operator personnel to manually shut off gas flow to the service line in the event of an emergency.'' Several commenters noted that this definition could cause confusion and the potential misinterpretation that these curb valves would be subject to the maintenance requirements at Sec. 192.747, which states that ``each valve, the use of which may be necessary for the safe operation of a distribution system, must be checked and serviced at intervals not exceeding 15 months but at least once each calendar year.'' The GPAC recommended that manual service line shut-off valves installed under section Sec. 192.385 be subject to regular, but less prescriptive, scheduled maintenance, as documented by the operator and consistent with the valve manufacturer's specification. Documentation of Customer Notification: PHMSA's proposal in the NPRM stated operators ``must provide written notification to the customer of their right to request the installation of an EFV,'' and that ``each operator must maintain a copy of the customer EFV notice for three years.'' Several commenters noted that the term ``written'' seemed to exclude forms of electronic notification, and they also noted that documenting individual notifications would be a costly, overly burdensome task. The GPAC recommended that PHMSA incorporate language from the NPRM preamble indicating broader options for stakeholder communication, including statements printed on customer bills or mailings or certain forms of electronic communication, including Web site postings, would satisfy the customer notification requirement, and that operators could keep a single copy of a particular method of communication for purposes of fulfilling the documentation requirement. This final rule adopts all three recommendations of the GPAC. Additional discussion of the amendments and associated comments of the GPAC are provided below as a part of the comment discussion. IV. Comment Summary and Discussion In the NPRM published July 15, 2015, PHMSA solicited public comment on whether the proposed amendments would enhance the safety of natural gas distribution systems, as well as the cost and benefit figures associated with these proposals. PHMSA received 12 comments from a broad array of stakeholders, including trade organizations, pipeline operators, a government agency, and a public citizen safety watchdog group. Below is a list of organizations that submitted comments in response to the NPRM as well as the individual docket number for each comment. All comments and corresponding rulemaking materials received may be viewed on the www.regulations.gov Web site under docket ID PHMSA-2011-0009. The majority of the comments specifically supported expanding EFV installation requirements. Major concerns included whether first responders should have access to curb valves, whether curb valves required inspection and maintenance, and what methods were being proposed for customer notification and documentation. Minor concerns included EFV installation, the effective date of the rule, and exceptions to EFV installation and notification. The substantive comments received on the proposed regulations are organized by topic and are discussed in the appropriate sections below, along with PHMSA's responses. Pipeline Operators (5) New Mexico Gas Company (NMG) PHMSA-2011-0009-0032 Southwest Gas Corporation (SWG) PHMSA-2011-0009-0044 NiSource (NS) PHMSA-2011-0009-0042 Sierra Pacific Power Company (SPPC) PHMSA-2011-0009-0041 MidAmerican Energy Company (MAE) PHMSA-2011-0009-0034 Trade Associations (5) American Gas Association (AGA) PHMSA-2011-0009-0037 National Propane Gas Association (NPGA) PHMSA-2011-0009- 0045 Gas Piping Technology Committee (GPTC) PHMSA-2011-0009- 0036 American Public Gas Association (APGA) PHMSA-2011-0009- 0024 Northeast Gas Association (NGA) PHMSA-2011-0009-0039 Government/Municipalities (1) National Transportation Safety Board (NTSB) PHMSA-2011- 0009-0035 Public Citizen Groups (1) Pipeline Safety Trust (PST) PHMSA-2011-0009-0040 A. Expansion of EFVs to Multifamily Residences, Branch Service Lines, and Small Commercial Buildings Proposal: EFVs can reduce the risks of explosions by shutting off unplanned, excessive gas flows, primarily from excavation damage to service lines between gas mains and buildings. Gas distribution pipeline operators are currently required to install EFVs in new and replacement service lines supplying SFRs, per the final rule titled ``Integrity Management Programs for Gas Distribution Pipelines,'' issued on December 4, 2009. In the NPRM, PHMSA proposed adding four new categories of service for which EFV installation will be required on new and entirely replaced gas distribution services. These four new categories are as follows: Branched service lines to an SFR installed concurrently with the primary SFR service line (a single EFV may be installed to protect both lines); Branched service lines to an SFR installed off a previously installed SFR service line that does not contain an EFV; Multifamily installations, including duplexes, triplexes, fourplexes, and other small multifamily buildings (e.g., apartments, condominiums) with known customer loads at time of service installation, based on installed meter capacity, up to 1,000 SCFH per service; and A single, small commercial customer, served by a single service line, with known customer load at time of service installation, based on installed meter capacity, up to 1,000 SCFH per service. Comments: The majority of the commenters from trade associations, industry, citizen groups, and government entities explicitly supported the expanded use of EFVs in all categories and recognized the benefits of their use. The NTSB was ``pleased that PHMSA is now proposing to expand the requirements for installing EFVs'' and understood ``that the expanded coverage is based on a comprehensive examination of the practical operating limits of EFVs and comments on the ANPRM.'' The NTSB stated that it ``supports the measures proposed in the NPRM and believes that they will improve the safety of natural gas distribution pipeline systems.'' The PST noted the publication ``fulfill[s] the NTSB's recommendation from 2001 to its full scope,'' and they ``join[ed] with the NTSB in supporting this proposed expansion.'' Industry trade associations, such as the AGA, which represents more than 200 local energy companies throughout the United States and provides gas to 94 percent of U.S. customers, stated in their comments that they and ``their member utilities completely support expanding EFV installation to multifamily residential service lines and small commercial services.'' The APGA, the national, non-profit association of publicly owned natural gas distribution [[Page 70991]] systems with over 700 members serving 37 States, also supported the expansion of EFVs, stating that ``EFVs are the one tool that distribution operators can use to reduce the risk posed when natural gas service lines are ruptured by excavation.'' The APGA also noted that ``in written comments submitted in response to PHMSA's ANPRM published November 25, 2011, APGA and other commenters suggested EFV installation requirements virtually identical to what PHMSA has proposed,'' and ``commend[ed] PHMSA for adopting APGA's recommendation.'' NMGC ``commend[ed] and support[ed] expanding the use of excess flow valves to new and fully replaced branch services, small multifamily facilities, and small commercial facilities where economically, technically, and operationally feasible.'' SWG ``support[ed] the practical and reasonable expansion of EFVs to new and fully replaced service lines beyond single family residential applications,'' in part ``evident by its EFV installation policy and number of EFVs installed [on its existing system].'' Likewise, the NGA ``support[ed] PHMSA's proposal to expand the use of excess flow valves in gas distribution services for newly constructed applications other than single-family residences and when existing services are excavated or replaced,'' recognizing that ``installing EFVs, under conditions where they are effective, when new services are installed, or existing services are exposed, repaired or replaced, is a cost-effective measure to improve pipeline safety.'' The NGA also noted that it ``supported this proposal in its initial comments to the advanced notice of proposed rulemaking related to this issue in 2012.'' PHMSA Response: PHMSA has been attempting to address issues involving the broad installation of EFVs since at least 1990, and the NTSB has issued several recommendations to PHMSA and the regulated industry regarding the installation of EFVs on particular services as far back as the 1970s. NTSB Recommendation P-01-2, which asks PHMSA to ``require that excess flow valves be installed in all new and renewed gas service lines, regardless of a customer's classification, when the operating conditions are compatible with readily available valves,'' is one of PHMSA's oldest, unclosed NTSB recommendations. Prior attempts to require the installation of EFVs on certain gas distribution services were not supported by both industry and State pipeline safety partners; for years, EFVs were perceived as unreliable, costly pieces of equipment that might accidentally close and interfere with normal service, interfere with maintenance activities, or be difficult to size and use at varying line pressures. Further, in the Pipeline Inspection, Protection, Enforcement, and Safety Act of 2006, Congress provided PHMSA with a mandate to focus its resources on requiring EFV installation on service lines serving single-family residences as part of PHMSA's gas distribution integrity management program (DIMP) rulemaking. Following the issuance of the DIMP rulemaking and the EFV regulations in 2009, EFVs became more technologically feasible and cost-effective to a point where it became a realistic possibility for PHMSA to address fully the NTSB recommendation. PHMSA performed several studies and surveys to evaluate the feasibility of its position on high-volume EFVs and used its experience in the prior EFV rulemaking to assist in formulating this proposal. PHMSA is pleased that there is now such widespread support, both from industry and public groups, for expanding the installation of EFVs beyond SFRs. Accordingly, this final rule amends the Federal Pipeline Safety Regulations by adding the proposed four new categories of service to require EFV installation on branched service lines (both branched lines to SFRs installed concurrently with the primary SFR service line and branched lines to SFRs installed off a previously installed SFR service lines not containing an EFV), lines serving multifamily installations, and lines serving small commercial and industrial customers. B. Curb Valve Accessibility to First Responders Proposal: In the NPRM, PHMSA proposed requiring operators to install curb valves for applications that operate above 1,000 SCFH, are not suitable for EFV installation, and do not meet the exemptions in the existing Sec. 192.383. Curb valves are the most feasible alternative to EFVs in locations that exceed 1,000 SCFH or have other issues that prevent EFV use. Although they cannot be operated instantaneously like EFVs, curb valves can still mitigate the effects of gas line explosions and are an effective safety measure. Therefore, PHMSA proposed that any curb valves installed under this section be accessible to first responders. PHMSA's experience indicates that, frequently, first responders arrive at the scene of an incident before operator personnel do. If first responders have access to a curb valve during an emergency and can operate it, the valve can be closed to mitigate further consequences. Comments: The NTSB was pleased to note that PHMSA's proposal to require that operators ``install a manual service line shut-off valve on new or replaced service lines in such a manner that emergency personnel can access the valve [. . .] goes beyond the original intent of [the NTSB's] recommendation, to further ensure safety.'' The PST joined the NTSB in supporting this measure. Several of the commenters representing trade associations and operators supported the use of curb valves where EFVs are not feasible but strongly opposed requiring that curb valves always be accessible to first responders. These commenters generally indicated that it should be the operator's responsibility to operate these select portions of gas distribution systems and that it should be up to the operator's discretion to allow other personnel to operate these valves, if needed. Certain operators noted the ``Pipeline Emergencies'' training manual, a document developed by a team of respected emergency response and industry experts in partnership with the National Association of Fire Marshals and PHMSA, states that emergency responders should consult the local gas company to determine local procedures for fire department use of curb valves. The AGA indicated there are a few unique situations where operators have properly trained first responders to operate curb valves, but such a practice is not followed by most utilities. Certain industry operators, including the SPPC, commented that they specifically train first responders in their service territories, for safety reasons, not to manually shut off gas flows. If manual service line shut-off valves are accessible to first responders, first responders may operate the wrong valve, may not have the proper equipment to operate the valve, or may incorrectly operate the valve. Operators and trade associations also asserted that, given the complexity of gas distribution systems, emergency shut-off valves should only be operated by operator-qualified personnel who are familiar with the specific gas distribution system in question. NS suggested that, as operators have engineering records indicating the location of all valves and which ones they control, operator personnel can verify the location and purpose of a valve, thereby eliminating the possibility of operating the wrong one and creating a greater hazard. The AGA noted there are many accounts of first responders who, [[Page 70992]] without the approval of the gas company, have inadvertently closed the wrong valve or opened a valve that should have been closed. Several operators argued that allowing first responders to operate manual service line shut-off valves would create additional inconveniences or safety risks, including loss of service to other customers or additional property damage, injuries, or even deaths. Some operators indicated that giving first responders immediate access to curb valves would distract them from their primary mission, which is to perform safety assessments, make locations safe for people, and conduct evacuations from areas of danger. Instead, they would suddenly have responsibility for locating valves, determining which valves should be closed, and closing them--tasks which could potentially interfere with their primary mission and for which they might not be trained. At the GPAC meeting, members of the committee expressed concerns similar to those raised by industry regarding unauthorized or improper manual service line shut-off valve usage. The committee debated whether there could be a requirement authorizing first responders to operate those particular valves or whether operators could give discretion to certain first responders to operate valves. One question that was brought up was whether eliminating ``first responders'' from the proposed language (which would leave ``accessible to operator personnel'' remaining) would unintentionally create a requirement that would make manual service line shut-off valves accessible to only company personnel. The committee eventually suggested revising the paragraph by striking the reference to first responders and inserting ``other personnel authorized by the operator.'' The committee believed this would give operators the primacy they sought for operating their own distribution systems while, at the same time, making the valves accessible and usable by non-operator personnel with the operator's consent. PHMSA Response: PHMSA disagrees with those commenters who argued that curb valves should not be accessible to first responders. Many comments PHMSA received seemed to equate valve accessibility with authority or expectation to operate those valves without consent. PHMSA is in no way implying that first responders should have complete autonomy in deciding whether to operate valves on a given gas distribution system. In PHMSA's experience, there have been accidents where the consequences have grown due to operator delays in shutting off curb valves. As a part of an operator's regular liaison with first responders, operators can, if they wish, train first responders to use curb valves properly through regular exercises and communications. Further, if the valve cover plate is clearly marked, there should not be any confusion regarding the operation of the valve in an emergency. However, PHMSA is not advocating the unauthorized operation of these valves. Unless they believe there is imminent threat to human life or extensive property damage, first responders should not operate curb valves without operator input or consent. In this final rule, PHMSA is adopting the language recommended by the GPAC, which would make curb valves accessible to operators and other personnel authorized by the operator to manually shut off gas flow, if needed, in the event of an emergency. PHMSA appreciates the work of the GPAC in proposing a consensus solution that enables first responders, if qualified and authorized, to operate valves if needed, yet retains the operators' right to make decisions regarding the operation of their own systems. C. Curb Valve Maintenance Proposal: In its NPRM, PHMSA proposed requiring operators to install curb valves for applications that operate above 1,000 SCFH, are not suitable for EFV installation, and do not meet the exemptions in the existing Sec. 192.383. Curb valves are the most feasible alternative to EFVs in locations that exceed 1,000 SCFH or have other issues that prevent EFV use. Although they cannot be operated instantaneously like EFVs, curb valves can still mitigate the effects of gas line explosions and are an important safety measure. Under the proposed amendment to Sec. 192.385(c), manual service line shut-off valves for any new or replaced service line must be installed in such a way as to allow accessibility during emergencies. Comments: Just as it supported the proposal to ensure the accessibility of curb valves to first responders, the NTSB also supported this proposal. Comments from industry and trade associations, however, were unified in their concern that this requirement would create confusion regarding maintenance requirements based on earlier PHMSA interpretations. Specifically, operators noted that the addition of Sec. 192.385, as proposed in the NPRM, might lead to the mistaken inference that manual service line shut-off valves would be subject to the valve maintenance requirements set forth in Sec. 192.747, ``Valve maintenance: Distribution systems.'' The AGA, NMGC, SWG, and APGA all noted that PHMSA has issued many letters of interpretation affirming that Sec. 192.747 does not apply to curb valves, but the proposed Sec. 192.385 could be misconstrued to require such annual inspections. The AGA and NMGC support PHMSA's historical position that manual curb valves are not considered a ``critical valve'' for inspection purposes, suggesting that if these valves were to be designated as critical valves, operators would have to hire and train a significantly larger staff to inspect and maintain these valves, which would significantly increase operating costs and impose an administrative burden. The AGA and APGA noted that if it was PHMSA's intent to change its position and require annual inspections on these manual curb valves, this is not indicated in the NPRM, the estimated cost of the rule, or the estimated paperwork burden. Operators suggested PHMSA clearly state in the final rule that curb valves installed under this proposal would not be subject to the requirements at Sec. 192.747. At the GPAC meeting, members of the committee discussed this proposal and whether these valves should be inspected and maintained according to the requirements at Sec. 192.747. Several members agreed that inspecting and maintaining these valves would be an","truncated":true,"body_characters":109165}