{"operation":"document","citation":"61 FR 31449","title":"Excess Flow ValvePerformance Standards","source_type":"rulemaking","agency":"Research and Special Programs Administration","status":"historical","official":true,"published_on":"1996-06-20","effective_on":"1996-07-22","summary":"In the process of routine excavation activities, excavators often sever gas service lines causing loss of life, injury, or property damage by fire or explosion. Excess flow valves (EFVs) restrict the flow of gas by closing automatically when a line is severed, thus mitigating the consequences of service line failures. In this final rule, RSPA has developed standards for the performance of EFVs used to protect single-residence service lines. If an EFV is installed on such a line, it must meet these performance standards.","machine_formats":{"json":"https://regulus.evalyn.ai/document/federal-register-96-15564.json","markdown":"https://regulus.evalyn.ai/document/federal-register-96-15564.md"},"app_url":"https://regulus.evalyn.ai/document/federal-register-96-15564","source_url":"https://www.federalregister.gov/documents/1996/06/20/96-15564/excess-flow-valveperformance-standards","body":"Federal Register, Volume 61 Issue 120 (Thursday, June 20, 1996) [Federal Register Volume 61, Number 120 (Thursday, June 20, 1996)] [Rules and Regulations] [Pages 31449-31459] From the Federal Register Online via the Government Publishing Office [ www.gpo.gov ] [FR Doc No: 96-15564] ======================================================================= ----------------------------------------------------------------------- DEPARTMENT OF TRANSPORTATION Research and Special Programs Administration 49 CFR Part 192 [Docket No. PS-118; Amendment 192-79] RIN 2137-AB97 Excess Flow Valve--Performance Standards AGENCY: Research and Special Programs Administration, (RSPA), DOT. ACTION: Final rule. ----------------------------------------------------------------------- SUMMARY: In the process of routine excavation activities, excavators often sever gas service lines causing loss of life, injury, or property damage by fire or explosion. Excess flow valves (EFVs) restrict the flow of gas by closing automatically when a line is severed, thus mitigating the consequences of service line failures. In this final rule, RSPA has developed standards for the performance of EFVs used to protect single-residence service lines. If an EFV is installed on such a line, it must meet these performance standards. DATES: This final rule takes effect July 22, 1996. FOR FURTHER INFORMATION CONTACT: Mike Israni (202) 366-4571, regarding the subject matter of this final rule, or the Dockets Unit, (202) 366- 4453, regarding copies of this final rule or other material in the docket that is referenced in this rule. SUPPLEMENTARY INFORMATION: Statutory Mandate In 49 U.S.C. 60110 Congress directs the Department of Transportation to issue regulations prescribing the circumstances under which operators of natural gas distribution systems must install EFVs. If the Department determines that there are no circumstances under which EFVs should be installed, the Department is to report this determination, and the reasons for the decision, to Congress. RSPA, on behalf of the Department, has determined that there are no circumstances under which the Department should require the installation of EFVs, primarily because the costs far exceed the benefits of such installation. RSPA has sent the report of its reasons for this determination to Congress. The report to Congress (April 4, 1995) and the cost/benefit analysis of mandatory EFV installation are available in the docket. Costs and benefits are also discussed later in this document under ``Cost/Benefit Analysis.'' 49 U.S.C. 60110 further requires the Department to develop standards for the performance of EFVs used to protect service lines in a natural gas distribution system. The development of these standards is the subject of this rulemaking. The statute also requires the Department to issue a rule requiring operators to notify customers about EFV availability and to offer to install EFVs that meet the performance standards, if the customer pays for the installation. RSPA will initiate a separate notice of proposed rulemaking for customer notification. The Problem Despite efforts, such as damage prevention programs, to reduce the frequency of excavation-related service line incidents on natural gas distribution service lines, such incidents persist and continue to result in death, injury, fire, or explosion. During the period from March 1991 through February 1994, 30 incidents with consequences that might have been mitigated by an EFV were reported to RSPA. These incidents, mostly excavation-related, resulted in 2 fatalities, 16 injuries, and an estimated $3,249,595 in property damage. Incident history is explained in the November 1991 and January 1995 cost/benefit studies evaluating mandatory EFV installation. Because damage prevention measures are not foolproof, RSPA has sought to identify ways to mitigate the consequences of these incidents. The National Transportation Safety Board (NTSB) and others have proposed EFVs as a means of mitigation. NTSB Recommendations NTSB has recommended EFVs as a means of reducing or preventing injury or death from incidents resulting from service line breaks or ruptures. Since 1971, NTSB has issued seven recommendations regarding the use of EFVs in service lines. NTSB's recommendations are summarized and discussed in the Notice of Proposed Rulemaking on this rulemaking (58 FR 21524; April 21, 1993). The Advance Notice of Proposed Rulemaking (ANPRM) RSPA issued an ANPRM (55 FR 52188; December 20, 1990) seeking information on the desirability of requiring the installation of EFVs on gas distribution service lines to reduce the damage from service line ruptures. The ANPRM also contained a questionnaire to collect current operational data on the use of EFVs by natural gas distribution operators. The results of the [[Page 31450]] ANPRM were summarized in the NPRM and are available in the docket. The Notice of Proposed Rulemaking (NPRM) In 1993, RSPA published an NPRM (Notice 2: 58 FR 21524; April 21, 1993), titled ``Excess Flow Valve Installation on Service Lines,'' that proposed to amend 49 CFR Part 192 to require installation of EFVs on new and replaced single residence service lines operating at a pressure of 10 psig or more. This NPRM also proposed performance standards for EFVs and conditions under which EFVs must be installed. The initial comment period for this NPRM closed June 21, 1993. The NPRM is available in the docket. RSPA received 140 written comments in response to the NPRM: 14 from industry associations, 1 from an EFV manufacturer, 102 from local distribution companies, 2 from consultants, 17 from Congress, state agencies, and regulatory associations, 3 from transmission companies, and 1 from a group of commenters, designated hereafter as the Joint Commenters (see below). The Public Meeting RSPA held a public meeting on June 18, 1993 (58 FR 33064; June 15, 1993) to enable interested parties to present additional comments on several of the issues presented in the NPRM. In the notice announcing the public meeting, RSPA also extended the comment period to July 6, 1993, to allow those not able to attend the meeting to have access to the transcript. Representatives of the American Gas Association (AGA), UMAC (an EFV manufacturer), the Gas Safety Action Council (GASAC), the National Association of Pipeline Safety Representatives (NAPSR), and NTSB spoke at the meeting. The AGA representative objected to the proposed rule, especially to the expected benefits estimated in the cost/benefit study. GASAC, NTSB, and UMAC supported an EFV rule, but not as proposed. The NAPSR representative noted that in NAPSR's experience EFVs have not been cost beneficial. The Joint Commenters On December 20, 1993, a group, designating itself as the Joint Commenters, filed comments that recommended language to include in an EFV rule. The Joint Commenters included GASAC, EFV manufacturers, and two gas pipeline distribution associations. Although not a signatory to the comments, NTSB sent two letters to a pipeline association supporting the Joint Commenters' recommendations. The NTSB letters are available in the docket. The Joint Commenters did not include representatives from the two major state pipeline safety associations, NAPSR, and the National Association of Regulatory Utility Commissioners (NARUC). NAPSR originally participated in discussions with the Joint Commenters but later dropped out because NAPSR members oppose a federal requirement to install EFVs. The comments from NAPSR are available in the docket. The Joint Commenters recommended regulatory language that their signatories would support if RSPA were to adopt this recommendation as a final rule. In a Notice of Reopening Comment Period, RSPA reopened the comment period to solicit comment on the safety merits of the Joint Commenters' recommended language (59 FR 39319; August 2, 1994). The reopened comment period closed October 3, 1994. In addition to seeking comments on the safety merits of the recommendation, RSPA also sought comment on: whether to allow EFVs with a bypass feature; whether, and to what extent, the presence of contaminants in the gas stream should preclude installation of an EFV; and whether RSPA should delay issuing a rule until industry performance standards for EFVs are developed. An additional 70 comments were received in response to the Notice of Reopening Comment Period: 7 from industry associations, 1 from an EFV manufacturer, 56 from local distribution companies, 5 from Congress, state agencies, and regulatory associations, and 1 from a transmission company. A discussion of the 140 comments to the NPRM and 70 comments to the Notice of Reopening Comment Period and RSPA disposition of these comments is found below. Advisory Committee Review The Technical Pipeline Safety Standards Committee (TPSSC) was established by statute to evaluate the technical feasibility, reasonableness, and practicability of proposed regulations. The TPSSC met on August 3, 1993, in Washington, DC, to consider the EFV standards proposed in the April 1993 NPRM. The TPSSC voted 11 to 0 against adopting the proposed rule as written. In addition, the TPSSC voted 10 to 1 against RSPA issuing any rule on EFVs. However, the TPSSC voted 10 to 1 to respect the wishes of Congress and to provide support for the Congressional mandate as implemented by RSPA. RSPA addresses each of the TPSSC's recommendations in the discussion of comments below. Petition for Rulemaking On July 14, 1995, AGA submitted a petition for rulemaking on EFV performance standards and customer notification requirements. In this petition, AGA urged OPS to adopt industry performance and manufacturing standards as soon as they are available and, in the interim, to adopt the performance standards recommended by the Joint Commenters. RSPA is not required to consider those comments in the petition pertaining to performance standards since the comments were received well after the close of the re-opened comment period. However, RSPA notes that those comments do not raise any issues not already raised in prior comments and addressed in this rule. RSPA will consider the bulk of AGA's petition dealing with customer notification requirements in the customer notification rulemaking. Cost/Benefit Analysis (Mandating EFV installation) RSPA recognizes the beneficial safety effects of EFVs. However, after extensive study and rulemaking, RSPA has decided not to require the installation of EFVs, primarily because the costs far exceed the benefits of such installation. Many comments to the NPRM and Notice of Reopening Comment Period cited the need for RSPA to redo the cost/benefit study that had been prepared to accompany the NPRM. Commenters said incident frequency, fire and police response costs, and property damage costs were overstated. The most frequent objection was that RSPA overestimated property loss and fire fighting costs for incidents with less than $5,000 in property damage. Commenters pointed out that leaks occur with greater frequency than incidents and that, by equating leak repair reports with incident reports, RSPA overstated the benefits to be gained. Many commenters also said that the $20 estimated cost to install an EFV was too low. In light of the commenters' criticisms, RSPA thoroughly reexamined the cost/benefit study. The revised study included updated data regarding service line incidents and revised information on related costs and anticipated benefits. In the most significant benefit change, RSPA reduced its estimate of the number of nonreportable incidents that could have benefitted from an EFV installation. Criticisms of its estimates on nonreportable incidents led RSPA to conclude that the original estimate, over [[Page 31451]] 143 thousand per year, significantly overstated the number of nonreportable incidents whose consequences might be mitigated by EFVs. RSPA used a different approach to develop a more reasonable estimate, approximately 13 thousand per year, for the final study. This revised number of nonreportable incidents is largely responsible for the decrease in the present value of the benefits from $21.02-$35.00 per service in the draft study to $7.42 per service in the final study. In other changes, RSPA revised its cost estimate by using the mid- point of the cost-range in EFVs. The original estimate looked only at the EFV cost to the largest current installers of EFVs, whereas the revised estimate considered the EFV cost to all current installers of EFVs. RSPA also used newer incident data to develop better estimates of the consequences of incidents before and after an EFV installation. As a result of RSPA's reexamination of the cost/benefit study, the present value of costs changed from the draft study figure of $20.20 per installed EFV with a bypass to a final study figure of $30.29. In addition, in the final study, the present value of costs for an EFV with positive shutoff was estimated to be $37.09 per installed EFV. The final cost/benefit study found the cost of installing an EFV to exceed the benefits by a 4.5:1 ratio. This result, along with consideration of other criticisms of a rule requiring installation, discussed in more detail below, led RSPA to determine that it would not require installation but would require that any EFV installed meet certain performance criteria. The final cost/benefit study explains in detail how each cost and benefit was calculated. Both the draft and final cost/benefit studies examining EFV installation are available in the docket. The Final Rule The final rule establishes a new section in the pipeline safety regulations, Sec. 192.381, ``Service lines: Excess flow valve performance standards.'' For the reasons previously explained, the final rule does not require installation of EFVs. In accordance with 49 U.S.C. 60110, the rule sets performance standards for any EFV that will be used in a single-residence gas service line operating continuously at not less than 10 psig. The final rule incorporates almost all the performance standards that the Joint Commenters recommended, rather than those RSPA proposed in the NPRM. An EFV will have to be manufactured and tested by the manufacturer according to an industry specification or a manufacturer's written specification to ensure that the EFV will function properly up to its rated maximum operating pressure and at all temperatures expected in the service line's operating environment. An EFV, like any other valve, will have to comply with subparts B and D of Part 192. The required tolerance has been raised so that an EFV will be required to close at, or not more than 50 percent above the rated flow, instead of at the proposed 10 percent. As commenters requested, an operator will have the choice of using an EFV with either a positive shutoff or bypass feature. Upon closure an EFV must reduce the gas flow to no more than 5 percent of the manufacturer's specified minimum flow rate, up to a maximum of 20 cubic feet per hour for a bypass-type EFV or 0.4 cubic feet per hour for a positive shut off-type EFV. An operator will have to mark or otherwise identify the presence of an EFV in the service line. Several proposed performance requirements have not been adopted. An EFV will not have to comply with the requirements of Secs. 192.363 and 192.365 that apply to other service line valves. Service line capacity will not have to exceed the manufacturer's EFV flow rating by 50 percent. An EFV will not be required to be tested upon installation and each time a customer's meter is removed or replaced, or to close automatically if the customer's meter, regulator or service valve is sheared off. Furthermore, an operator will not be required to verify the rated flow or replace an EFV that does not close automatically. The final rule recommends that an operator locate an EFV beyond the hard surface and as near as practical to the fitting connecting the service line to its source of gas supply to ensure that the EFV protects the maximum length of service line and to assist in locating the EFV. The final rule also recommends that to augment performance reliability, an operator not install an EFV where the contaminants in the gas stream will cause the valve to malfunction or interfere with necessary operation and maintenance activities on the service line, such as blowing liquids from the line. Discussion of Comments Although comments were submitted in response to the proposal to require installation of EFVs, these comments were also relevant to developing a performance standards rule. Many of the comments focussed on the performance criteria RSPA included in the proposal. General Comments--Except for NTSB, valve manufacturers, and GASAC, virtually all of the 140 commenters to the NPRM objected to the proposed rule on installation. The major objections were that EFV installation should not be federally mandated, that each state pipeline authority should be allowed to establish the rules for its state; that a positive shutoff EFV should not be required; that testing an EFV while in service is unnecessary and overly expensive; that EFV installation should be delayed until industry standards are developed; and, that the cost/benefit study supporting the proposed rule is flawed. The majority of commenters also maintained that EFV installation should not be required where contaminants could cause the EFV to malfunction and inadvertently shutoff service to the customer. Nearly all of the 70 commenters responding to the Notice of Reopening Comment Period proposed that RSPA adopt the Joint Commenters' recommendations on performance language because the recommended language was less objectionable than the NPRM's proposed language. The commenters also favored giving an operator the option to install either a bypass or positive shutoff EFV. Overall, because of concerns about EFV reliability, gas distribution operators favored waiting until industry standards are developed and accepted before requiring installation of EFVs. Many commenters restated their objection to the findings of the cost/benefit study. Six large operators operating at least 9 million service lines (18 percent of all U.S. service lines) opposed both the NPRM's proposal and the Joint Commenters' recommendations. The operators' major objections were that the cost/benefit study grossly overstated benefits, that industry standards are needed because EFVs do not operate reliably, and that costs to remove EFVs after a malfunction are high. Comments about the cost/benefit study have previously been discussed. Other general comments are discussed below, as well as specific comments about each RSPA-proposed performance standard and the associated Joint Commenters' recommendation. To avoid repetition, similar comments are discussed in only one section. Discussion on State vs. Federal Mandate Comments--NAPSR expressed opposition to any federal mandate to install EFVs, arguing that any such regulatory requirements should be at the state level. On two occasions NARUC passed resolutions proposing that any requirement for EFVs be determined by [[Page 31452]] the individual state pipeline safety agencies. The NARUC Subcommittee for Pipeline Safety polled the state regulatory agencies, gathered data, and prepared a report of its findings. NARUC found that only two states, Massachusetts and New York, favored a federal mandate to install EFVs. Six major operators (three operating in California) opposed any federal requirement to install EFVs, arguing that states should be allowed to determine the need for EFVs based on state- developed criteria. Response--Because of RSPA's decision not to issue a rule requiring the installation of EFVs, each state will be able to determine if it should require such installation based on circumstances unique to that state. Industry Standards In the absence of standards by an industry-sponsored safety standards committee, RSPA proposed several requirements for the manufacture and operation of any EFV that would be installed in a single-residence gas service line. The Joint Commenters' recommendation also included performance standards for single- residence gas service lines. Comments on NPRM--Many commenters said RSPA should not issue a final rule until industry manufacturing and performance safety standards are prepared and adopted. The TPSSC recommended that RSPA initiate the development of standards by The American National Standards Institute (ANSI), American Society of Testing Materials (ASTM), or other nationally recognized and accredited organization for the manufacture, testing, and operation of EFVs. The TPSSC further recommended that when such standards are enacted, RSPA should issue an NPRM for EFVs incorporating such standards for TPSSC review. The Gas Piping Technology Committee (GPTC) commented that its ANSI/GPTC Z380 committee was developing performance, operating, and installation guidelines for EFVs. GPTC said guidance will be offered on choosing operating pressure ranges, flow rates, bleed-by, and reset characteristics, length and diameter of service piping, inline contaminants, purging procedures, joining methods, and service line locations. Comments to Notice of Reopening Comment Period--Many commenters said RSPA should take no final action until industry standards are available because standards would assure EFV reliability. Many others said RSPA should issue a final rule but grant a one year delay in implementation to give the industry committees time to complete manufacturing and operational standards. Several commenters said the ASTM F17 committee is preparing testing standards and the ANSI/GPTC Z380 committee is preparing guidelines that should be completed in 1995. Response--RSPA agrees that to achieve performance reliability and the desired safety benefits, specifications are necessary to ensure uniformity among EFVs installed in service lines. Because the NPRM proposing required installation only sought comment on performance standards applicable to EFVs installed in single-residence service lines, this final rule limits EFV performance standards to that application. Once industry standards are developed for EFVs used in other applications, such as multiple residences and commercial enterprises, RSPA will consider seeking comment on proposed performance standards for those applications. The final rule requires that when an EFV is installed in a single residence service line, the EFV must be manufactured and tested by the manufacturer according to an industry specification, or to a manufacturer's written specification to ensure the EFV performs specified minimum functions. These specifications will ensure that an EFV functions properly up to the maximum operating pressure at which it is rated and at all temperatures reasonably expected in the service line's operating environment. These specifications will further ensure that an EFV is sized to close within 50 percent of the rated closure rate, to reduce gas flow upon closure to specified rates, and to not close when the pressure and flow rates are less than the manufacturer's specified minimums. In addition, an EFV must comply with the general requirements of Subparts B and D of part 192. While subparts B and D do not include operational requirements specific to an EFV, they do include general material and design standards applicable to any valve in a pipeline system. Many commenters, including several industry committees, indicated that EFV standards are forthcoming. However, until industry finalizes EFV standards, the requirement that an EFV perform specified functions according to a manufacturer's written specifications will ensure that an EFV performs reliably and safely. Moreover, final industry performance specifications are likely to be similar to manufacturers' specifications, because valve manufacturers are often members of the industry organizations that develop such specifications. Proposed Section 192.381(a)--(regarding Secs. 192.363 and 192.365 gas pipeline valve requirements)--RSPA proposed in the NPRM that EFVs must comply with the requirements of Secs. 192.363 and 192.365. These existing sections establish requirements for all valves in gas service lines. Comments--Several commenters stated that Secs. 192.363 and 192.365 should not apply to EFVs. Commenters pointed out that these requirements apply to the design of service line manual shut-off valves and would conflict with the proposed EFV requirements. For example, commenters noted that the Sec. 192.365(c) requirement to locate valves in a covered durable box or standpipe is intended to allow for ready operation of a service line manual shut-off valve. Therefore, it would be unnecessary and costly to apply this requirement to an EFV, which is an automatic valve not requiring access for manual operation. Response--After further study, RSPA agrees that valve requirements concerning the use of a durable box or standpipe do not apply to EFVs, and the other requirements of Secs. 192.363 and 192.365 apply only to manual shut-off type valves, not EFVs. Accordingly, the proposed requirement that EFVs comply with Secs. 192.363 and 192.365 has not been adopted. Proposed Section 192.381(a)--(10 psig requirement)-RSPA proposed that an EFV be installed on each newly installed or replaced single residence service line that operates at a pressure not less than 10 psig. Comments--Many commenters to both the NPRM and the Notice of Reopening Comment Period requested clarification of the 10 psig threshold. Many commenters asked if the requirement would apply if pressure in the pipeline system drops below 10 psig at any time during the year. Response--RSPA is not requiring operators to install EFVs on any single-residence service line, whatever its operating pressure. However, RSPA does not want an EFV, if installed, to cause a loss in service, especially at a time when the service is most needed by the consumer, such as during the winter heating season. Thus, the performance standards have been established for EFVs that are installed on a service line that operates at or above 10 psig continuously during the year. Setting the performance standards at this threshold is influenced by two of the largest users of EFVs who, as standard practice, limit EFV installation to service lines in systems where service line inlet pressure does not drop below 10 psig during the year. [[Page 31453]] Because service line pressure will most likely be at its lowest level during the coldest weather, especially in colder climates, an operator should consider the pressure drop in the service line due to the restriction of gas flow caused by an EFV. If pressure drop is considered, an EFV should not cause a reduction in safety or loss of service in any service line. Proposed Section 192.381(a)--(replaced service lines)--RSPA proposed that EFVs be installed on certain new and replaced service lines. Response--This proposal is no longer relevant since EFV installation is not being required. Proposed Section 192.381(b)(1)--(installation)--RSPA proposed in the NPRM that an EFV be installed as close to the main or transmission line as practicable. The Joint Commenters recommended installation in or as near as practicable to the service line fitting connecting the service line to its gas supply. Comments--Many commenters suggested RSPA remove any reference to transmission lines in the rule. Several commenters said EFVs are not available that will withstand transmission line pressures. Others stated that the statutory mandate was intended to apply only to distribution systems. The TPSSC voted 7 to 4 that all references to transmission lines be dropped from the proposed rule. A few commenters objected to what they thought was the proposed requirement to install EFVs immediately downstream of the service-to- main connection when the line serves more than one residence (branch service). Other commenters were concerned that the proposed rule would require EFV installation below hard surfaces such as asphalt or concrete, making installation very costly. Response--In the NPRM, RSPA intended that all new and replaced service lines, whether from a main or transmission line, where the source of gas supply consistently operates above 10 psig, be required to have an EFV installed. The reference to ``main'' and ``transmission'' lines was intended to cover farm taps, as farm taps are also subject to the type of incident that could benefit from an EFV. The final rule deletes the reference to ``main'' and ``transmission'' and sets performance standards for EFVs installed on single-residence gas service lines. By referring to ``service'' line, RSPA intends for the standards to apply if an EFV is installed on a farm tap. A farm tap operates as a service line when a local distribution company operates a metered farm tap on a transmission line delivering gas to a farmer or other landowner. Accordingly, although the rule does not require installation on any single-residence service line, an EFV that meets the required performance standards can be installed on a service line from a main or a branch off a transmission line. RSPA never intended that an EFV serve more than one family residence. RSPA recognizes that an EFV would be difficult to size when the gas supply is serving multiple residences because of widely varying gas volume through the EFV. Because of this difficulty, the performance standards in this final rule are limited to EFVs that are installed on single-residence service lines. RSPA agrees that removing an EFV under a hard surface would be overly expensive if an EFV failed to function. Therefore, RSPA recommends that an EFV be located beyond the hard surface and as near as practical to the fitting connecting the service line to its source of gas supply. Proposed Section 192.381(b)(2)--(Section 192 Subparts B & D)--As noted above, the NPRM proposed and the Joint Commenters recommended that EFVs meet the applicable requirements of subparts B and D of part 192. Comments--No substantive comments were received on this proposal. Response--Subpart B establishes minimum requirements for selection and qualification of materials to be used in pipelines. Subpart D prescribes minimum requirements for the design and installation of pipeline components and facilities. Since these requirements are general performance requirements that apply to all valves, they are included in the performance requirements applicable to EFVs. Proposed Section 192.381(b)(3)--(bypass)--RSPA proposed that an EFV be designed to prevent pressure equalization across the EFV after the EFV closes, thereby prohibiting an operator from installing an EFV with a bypass feature. The bypass feature allows pressure to equalize and the EFV to automatically reopen after closure because it allows a small amount of gas to pass through the EFV. In contrast, a positive shutoff feature allows only minute amounts of gas to pass through the EFV after it closes, and requires backpressuring downstream to reset the EFV. The Joint Commenters' recommendation would allow either type of EFV. In the Notice of Reopening Comment Period, RSPA sought comment on the safety of using EFVs with or without the bypass feature and gave two examples, provided by two large local distribution operators, of potential dangers that might be caused by the bypass feature. RSPA also asked for comments on the conditions under which automatically resetting EFVs should or should not be required in residential service lines and on the linkage between the bypass feature and unauthorized repairs to damaged service lines. Comments to NPRM--Many commented on the proposal prohibiting the use of EFVs with a bypass feature. Commenters, including several at the public meeting, were virtually unanimous in favor of an operator having the option to select an EFV with either the bypass or positive shutoff feature. Similarly, the TPSSC voted 9 to 2 in favor of an operator having this option. Various reasons were given for not prohibiting the installation of bypass EFVs. Several commenters, including an industry association, complained that RSPA proposed the positive shutoff requirement without sufficient justification in the cost/benefit study. One commenter said that additional costs of at least $250 per utility crew would be incurred to provide backpressure downstream of the EFV to equalize the pressure and reset the valve. This commenter said these services would necessitate extra equipment, including a compressed natural gas tank or portable natural gas compressor, and additional piping, fittings, and hoses. Other commenters mentioned additional hazards to personnel in hauling and connecting compressed natural gas. Another commenter was concerned with customer inconvenience because a service call would be necessary to backpressure the EFV, delaying restoration of service. Many commenters argued that bypass-type EFVs do not pose a significant safety risk. Commenters maintained that operators that regularly install EFVs have had no incidents resulting from use of bypass-type EFVs. Three of the largest voluntary users of EFVs (with over 300,000 EFVs in service) commented that their data did not show an incident having occurred due to a bypass- type EFV. An EFV manufacturer commented that it has no knowledge of bypass gas ever contributing to a natural gas incident. NTSB and many operators echoed these assurances. Several commenters, including EFV users, said RSPA's concern that the bypass feature would allow irresponsible excavators to make repairs is unfounded. A few commenters said that positive shutoff EFVs would cause more safety problems than bypass-type EFVs because an excavator could sever a service line unknowingly if the [[Page 31454]] positive shutoff were to completely stop the gas flow and any released odor from reaching the atmosphere. Conversely, these commenters argued that a failed service line with a bypass would continuously release gas and leave a readily detectable odor. Commenters noted other potential problems with positive shutoff EFVs. For example, a commenter in Alaska pointed out that an earthquake in the winter could cause EFVs to engage and, if positive shutoff EFVs were used, each would have to be backpressured and each customer's appliance re-lighted. During an Alaskan winter this could take days. The Gas Research Institute (GRI) stated that its tests of EFV models showed all the tested models were affected by pressure surges of 5 psi or more and that opening, closing, or throttling a main line valve could activate an EFV, causing a false closure. The research organization said RSPA could infer from these results that the use of EFVs without the bypass could cause extended distribution service outages. GRI further stated that it knows of no reports of bypass flow in an EFV having led to or increased the severity of an accident. GASAC commented that RSPA should allow each operator to determine the type of valves for its system. Other commenters echoed this statement. Even among those operators opposed to a mandatary rule, most said that if a rule were issued, the choice of which type of EFV to use should be left to the operator. Comments on the Joint Commenters' Recommendation - Many commenters supported the Joint Commenters' recommendation to allow the use of a bypass-type EFV. Many commenters said it is not appropriate to depend on an EFV's design to prevent unauthorized repairs. Rather, unauthorized repairs should be controlled by stiffer penalties and better enforcement of damage prevention laws. These commenters maintained that EFVs are used to provide safety when a service line is severed, and should not be expected to perform functions beyond their intended purpose. Many commenters said excavators who damage service lines may make unauthorized repairs regardless of whether a bypass-type EFV, a positive shutoff EFV, or no EFV is installed. RSPA recognizes the validity of this statement and that EFVs with either feature are not likely to have a substantial effect in either reducing or increasing the frequency of unauthorized repairs on a broken service line. To dispel RSPA's concern about the potential danger of bypass- type EFVs and gas discharge into a residence, an operator explained that since natural gas is only about 0.6 times the density of air, any raw gas passing through a vented appliance would exhaust to the atmosphere through the chimney. The operator concluded that household gas ranges (or space heaters) without burner safety pilots are the only paths for raw gas to disperse through a building. The operator cited a recent study by NOVA, a Canadian chemical and pipeline company, that demonstrated that a rate of raw gas buildup in a small residence (300 square feet) would have to be about 60 cubic feet per hour to reach an ignitable level in five hours. This allows a five hour period for someone to discover the gas release before the ignitable level is reached. A bypass-type EFV allows 20 cubic feet of gas per hour. Therefore, natural gas that is passing through an EFV with a bypass would take several hours to accumulate to the ignitable range in a building. Response--RSPA has been concerned that excavators could repair a service line break equipped with an EFV with a bypass feature, the EFV would automatically reset, and service would be restored without the operator knowing that the line had been damaged. Consequently, gas could then pass into and accumulate in a residence where the pilot light on a gas appliance had been extinguished during the service line break. RSPA was also concerned that restoration of gas service with unvented appliances would cause a rapid buildup of the gas/air mixture to an ignitable level. Commenters have posed circumstances under which such a buildup could occur. However, in response to its questions about this problem, RSPA did not receive any information that such an incident has actually occurred. Furthermore, an EFV manufacturer and AGA have assured RSPA that bypass-type EFVs operate properly to avoid unintended gas buildup within a building. An operator with 20,000 installed bypass-type EFVs stated that bypass gas from a tripped EFV had never caused or contributed to an unsafe situation on its system. Other operators made comparable statements. The NOVA study, described above, further allays RSPA's concern. Therefore, based on the record in this rulemaking, RSPA accepts the premise that EFVs with a bypass feature are safe. RSPA also finds acceptable the Joint Commenters' recommendation to limit gas flow to 20 cubic feet per hour for bypass-type EFVs and to 0.4 cubic feet per hour for positive shutoff-type EFVs. Because EFVs with positive shutoff features were proposed in the NPRM, RSPA did not propose EFV flow limits. However, RSPA agrees that the limits recommended by the Joint Commenters are reasonable and feasible design requirements. Accordingly, the final rule allows either bypass or positive shutoff EFVs. Closure flow rates will be limited to 20 cubic feet per hour for the bypass-type EFV and 0.4 cubic feet per hour for the positive shutoff EFV. Proposed Section 192.381(b)(4)--(installation testing)--RSPA proposed that upon original installation of an EFV and each time the meter is removed or replaced, the EFV be tested to determine if it closes automatically. The Joint Commenters' recommendation deleted the requirement. Comments--All 37 commenters on this proposed requirement asked that it be deleted. Most commenters stated that the test would require that the service line be disconnected from the meter set, the service valve at the meter opened, and gas vented to the atmosphere to trip the EFV. Many commenters said that venting of the gas near the residence, or inside the residence when the meter is indoors, would be hazardous and would needlessly rele","truncated":true,"body_characters":72664}