# HAR 6-77-110 Customer meter installations: operating pressure

- **operation:** document
- **citation:** HAR 6-77-110
- **title:** HAR 6-77-110 Customer meter installations: operating pressure
- **source type:** regulation
- **agency:** Hawaii Public Utilities Commission
- **status:** current
- **official:** true
- **published on:** 1994-04-15
- **effective on:** 1994-09-03
- **summary:** used at a pressure that is more than sixty-seven percent of the manufacturer's shell test pressure. (b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i.g. (c) A rebuilt or repaired tinned steel case meter may not be used at a pressure t
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/hi-har-har-6-77-110.json
- **markdown:** https://regulus.evalyn.ai/document/hi-har-har-6-77-110.md
- **app url:** https://regulus.evalyn.ai/document/hi-har-har-6-77-110
- **source url:** https://puc.hawaii.gov/wp-content/uploads/2026/04/HAR-6-77-Transp-of-Gas-03-31-2026.pdf
**body:**

used at a pressure that is more than sixty-seven percent of the manufacturer's shell test pressure. (b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i.g. (c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than fifty percent of the pressure used to test the meter after rebuilding or repairing. [Eff ] (Auth: HRS '269-6) (Imp: 49 C.F.R. '192.359, October 1, 1990)
- **truncated:** false
- **body characters:** 469