# HAR 6-77-175 Transmission lines: leakage surveys

- **operation:** document
- **citation:** HAR 6-77-175
- **title:** HAR 6-77-175 Transmission lines: leakage surveys
- **source type:** regulation
- **agency:** Hawaii Public Utilities Commission
- **status:** current
- **official:** true
- **published on:** 1994-04-15
- **effective on:** 1994-09-03
- **summary:** line shall provide for periodic leakage surveys of the line in its operating and maintenance plan. (b) Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/hi-har-har-6-77-175.json
- **markdown:** https://regulus.evalyn.ai/document/hi-har-har-6-77-175.md
- **app url:** https://regulus.evalyn.ai/document/hi-har-har-6-77-175
- **source url:** https://puc.hawaii.gov/wp-content/uploads/2026/04/HAR-6-77-Transp-of-Gas-03-31-2026.pdf
**body:**

line shall provide for periodic leakage surveys of the line in its operating and maintenance plan. (b) Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas in conformity with section 6-77-169 without an odor or odorant, leakage surveys using leak detector equipment must be conducted: (1) In Class 3 locations, at intervals not exceeding 7-1/2 months, but at least twice each calendar year; and (2) In Class 4 locations, at intervals not exceeding 4-1/2 months, but at least four times each calendar year. [Eff ] (Auth: HRS '269-6) (Imp: 49 C.F.R. '192.706, October 1, 1990)
- **truncated:** false
- **body characters:** 719