{"operation":"document","citation":"LAC 43:XIII §1129","title":"Compressor Stations: Pressure Limiting Devices [49 CFR 192.169]","source_type":"regulation","agency":"Louisiana Office of Conservation","status":"current","official":true,"published_on":null,"effective_on":null,"summary":"A. Each compressor station must have pressure relief or other suitable protective devices of sufficient capacity and sensitivity to ensure that the maximum allowable operating pressure of the station piping and equipment is not exceeded by more than 10 percent. [49 CFR 192.169(a)] B. Each vent line ","machine_formats":{"json":"https://regulus.evalyn.ai/document/la-lac-43-xiii-1129.json","markdown":"https://regulus.evalyn.ai/document/la-lac-43-xiii-1129.md"},"app_url":"https://regulus.evalyn.ai/document/la-lac-43-xiii-1129","source_url":"https://www.doa.la.gov/doa/osr/louisiana-administrative-code/","body":"A. Each compressor station must have pressure relief or other suitable protective devices of sufficient capacity and sensitivity to ensure that the maximum allowable operating pressure of the station piping and equipment is not exceeded by more than 10 percent. [49 CFR 192.169(a)]\n\nB. Each vent line that exhausts gas from the pressure relief valves of a compressor station must extend to a location where the gas may be discharged without hazard. [49 CFR 192.169(b)]\n\nAUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.\n\nHISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:225 (April 1983), amended LR 10:517 (July 1984), LR 30:1236 (June 2004).","truncated":false,"body_characters":708}