{"operation":"document","citation":"LAC 43:XIII §1907","title":"Customer Meters and Regulators: Installation [49 CFR 192.357]","source_type":"regulation","agency":"Louisiana Office of Conservation","status":"current","official":true,"published_on":null,"effective_on":null,"summary":"A. Each meter and each regulator must be installed so as to minimize anticipated stresses upon the connecting piping and the meter. [49 CFR 192.357(a)] B. When close all-thread nipples are used, the wall thickness remaining after the threads are cut must meet the minimum wall thickness requirements ","machine_formats":{"json":"https://regulus.evalyn.ai/document/la-lac-43-xiii-1907.json","markdown":"https://regulus.evalyn.ai/document/la-lac-43-xiii-1907.md"},"app_url":"https://regulus.evalyn.ai/document/la-lac-43-xiii-1907","source_url":"https://www.doa.la.gov/doa/osr/louisiana-administrative-code/","body":"A. Each meter and each regulator must be installed so as to minimize anticipated stresses upon the connecting piping and the meter. [49 CFR 192.357(a)]\n\nB. When close all-thread nipples are used, the wall thickness remaining after the threads are cut must meet the minimum wall thickness requirements of this Subpart. [49 CFR 192.357(b)]\n\nC. Connections made of lead or other easily damaged material may not be used in the installation of meters or regulators. [49 CFR 192.357(c)]\n\nD. Each regulator that might release gas in its operation must be vented to the outside atmosphere. [49 CFR 192.357(d)]\n\nAUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.\n\nHISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:234 (April 1983), amended LR 10:526 (July 1984), LR 30:1248 (June 2004).","truncated":false,"body_characters":841}