{"operation":"document","citation":"LAC 43:XIII §2931","title":"Compressor Stations: Inspection and Testing of Relief Devices [49 CFR 192.731]","source_type":"regulation","agency":"Louisiana Office of Conservation","status":"current","official":true,"published_on":null,"effective_on":null,"summary":"A. Except for rupture discs, each pressure relieving device in a compressor station must be inspected and tested in accordance with §§2939 and 2943, and must be operated periodically to determine that it opens at the correct set pressure. [49 CFR 192.731(a)] B. Any defective or inadequate equipment ","machine_formats":{"json":"https://regulus.evalyn.ai/document/la-lac-43-xiii-2931.json","markdown":"https://regulus.evalyn.ai/document/la-lac-43-xiii-2931.md"},"app_url":"https://regulus.evalyn.ai/document/la-lac-43-xiii-2931","source_url":"https://www.doa.la.gov/doa/osr/louisiana-administrative-code/","body":"A. Except for rupture discs, each pressure relieving device in a compressor station must be inspected and tested in accordance with §§2939 and 2943, and must be operated periodically to determine that it opens at the correct set pressure. [49 CFR 192.731(a)]\n\nB. Any defective or inadequate equipment found must be promptly repaired or replaced. [49 CFR 192.731(b)]\n\nC. Each remote control shutdown device must be inspected and tested at intervals not exceeding 15 months, but at least once each calendar year, to determine that it functions properly. [49 CFR 192.731(c)]\n\nAUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.\n\nHISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:246 (April 1983), amended LR 10:538 (July 1984), LR 30:1270 (June 2004).","truncated":false,"body_characters":811}