# Design Factor (F) for Steel Pipe [49 CFR 192.111]

- **operation:** document
- **citation:** LAC 43:XIII §911
- **title:** Design Factor (F) for Steel Pipe [49 CFR 192.111]
- **source type:** regulation
- **agency:** Louisiana Office of Conservation
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** Not available
- **summary:** A. Except as otherwise provided in Subsections B, C, and D of this Section, the design factor to be used in the design formula in §905 is determined in accordance with the following table. [49 CFR 192.111(a)] Class Location Design Factor (F) 1 0. 72 2 0. 60 3 0. 50 4 0. 40 B. A design factor of 0.60
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/la-lac-43-xiii-911.json
- **markdown:** https://regulus.evalyn.ai/document/la-lac-43-xiii-911.md
- **app url:** https://regulus.evalyn.ai/document/la-lac-43-xiii-911
- **source url:** https://www.doa.la.gov/doa/osr/louisiana-administrative-code/
**body:**

A. Except as otherwise provided in Subsections B, C, and D of this Section, the design factor to be used in the design formula in §905 is determined in accordance with the following table. [49 CFR 192.111(a)]

Class Location

Design Factor (F)

1

0. 72

2

0. 60

3

0. 50

4

0. 40

B. A design factor of 0.60 or less must be used in the design formula in §905 for steel pipe in Class 1 locations that: [49 CFR 192.111(b)]

1. crosses the right-of-way of an unimproved public road, without a casing; [49 CFR 192.111(b)(1)]

2. crosses without a casing, or makes a parallel encroachment on, the right-of-way of either a hard surfaced road, a highway, a public street, or a railroad; [49 CFR 192.111(b)(2)]

3. is supported by a vehicular, pedestrian, railroad, or pipeline bridge; or [49 CFR 192.111(b)(3)]

4. is used in a fabricated assembly, (including separators, mainline valve assemblies, cross-connections, and river crossing headers) or is used within five pipe diameters in any direction from the last fitting of a fabricated assembly, other than a transition piece or an elbow used in place of a pipe bend which is not associated with a fabricated assembly. [49 CFR 192.111(b)(4)]

C. For Class 2 locations, a design factor of 0.50, or less, must be used in the design formula in §905 for uncased steel pipe that crosses the right-of-way of a hard surfaced road, a highway, a public street, or a railroad. [49 CFR 192.111(c)]

D. For Class 1 and Class 2 locations, a design factor of 0.50, or less, must be used in the design formula in §905 for: [49 CFR 192.111(d)]

1. steel pipe in a compressor station, regulating station, or measuring station; and [49 CFR 192.111(d)(1)]

2. steel pipe, including a pipe riser, on a platform located offshore or in inland navigable waters. [49 CFR 192.111(d)(2)]

AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.

HISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:222 (April 1983), amended LR 10:513 (July 1984), LR 30:1230 (June 2004).