{"operation":"document","citation":"P-70-038","title":"NTSB Safety Recommendation P-70-038","source_type":"guidance","agency":"National Transportation Safety Board","status":"guidance","official":true,"published_on":"1970-10-14","effective_on":"1970-10-14","summary":"THE NTSB RECOMMENDS THAT IOWA SOUTHERN UTILITIES, INC., TAKE THE FOLLOWING ACTION: ESTABLISH A WRITTEN PROCEDURE FOR PREVENTING DAMAGE TO UNDERGROUND FACILITIES. THE PROGRAM SHOULD CONTAIN THE SAME METHODS RECOMMENDED TO THE OFFICE OF PIPELINE SAFETY.","machine_formats":{"json":"https://regulus.evalyn.ai/document/ntsb-recommendation-p-70-038.json","markdown":"https://regulus.evalyn.ai/document/ntsb-recommendation-p-70-038.md"},"app_url":"https://regulus.evalyn.ai/document/ntsb-recommendation-p-70-038","source_url":"https://data.ntsb.gov/carol-main-public/sr-details/P-70-038","body":"NTSB safety recommendation P-70-038.\n\nTHE NTSB RECOMMENDS THAT IOWA SOUTHERN UTILITIES, INC., TAKE THE FOLLOWING ACTION: ESTABLISH A WRITTEN PROCEDURE FOR PREVENTING DAMAGE TO UNDERGROUND FACILITIES. THE PROGRAM SHOULD CONTAIN THE SAME METHODS RECOMMENDED TO THE OFFICE OF PIPELINE SAFETY.\n\nPriority: CLASS II\n\nOverall Status: Closed - Acceptable Alternate Action\n\nIssued Date: 1970-10-14\n\nAdopted Date: 1970-10-14\n\nOverall Date Closed: 1976-07-20\n\nSynopsis: ON NOVEMBER 6, 1969, DURING A HIGHWAY CONSTRUCTION PROJECT IN BURLINGTON, IOWA, A BULLDOZER WEIGHING 70,000 POUNDS DROVE OVER AND PARTIALLY COLLAPSED THE STEEL COVERS OF A GAS REGULATOR PIT, DAMAGING THE REGULATOR. WHILE THE PRESSURE WAS PARTIALLY CONTROLLED BY A MONITORING OR SAFETY REGULATOR, GAS, REPORTEDLY AT FOUR TO FIVE TIMES THE NORMAL OPERATING PRESSURE, ENTERED THE DISTRIBUTION SYSTEM. GAS CUSTOMERS IN THE AFFECTED AREA STARTED REPORTING HIGH GAS PILOTS AND FIRES TO ISU AND THE FIRE DEPARTMENT. THE HIGH-PRESSURE GAS SOURCE WAS TURNED OFF BUT FIRES CONTINUED TO BE REPORTED, THE FIRES WROUGHT MAJOR DAMAGE TO THE INTERIORS OF 10 HOUSES AND MINOR DAMAGE TO KITCHENS AND APPLIANCES IN 42 OTHERS. PROPERTY DAMAGE WAS ESTIMATED AT $80,000.\n\nProbable Cause: The probable cause of the fires in the houses was the continued overpressure condition of the low-pressure distributions system for an extended period of time, which allowed pressure to build up until high gas flames ignited nearby objects. The initiation of the overpressure was caused by a bulldozer which damaged the largest primary working regulator which, with other regulators, controlled the gas pressure entering the low-pressure systems; and by inadequate performance of the monitoring regulator which failed to operate to limit the gas pressure to a safe level.\n\nNtsbnumber: DCA70MP001\n\nReport Number: PAR-70-01\n\nAddressee Name: Iowa Southern Utilities, Inc.\n\nAddressee Status: Closed--No Longer Applicable\n\nAddressee Date Closed: 1976-07-20\n\nAddressee Acronym: ISU\n\nAddressee Organization Type: P-Private Industry\n\nCommunication Date: 1971-07-07\n\nCommunication Type: Official Correspondence\n\nCommunication Contents: THE BOARD WAS INFORMED BY LETTER THAT THE FOLLOWING ACTION HAS BEEN TAKEN: THE DISTRICT SUPERVISOR SHALL CONTACT TELEPHONE COMPANY MANAGERS, CONTRACTORS, AND LOCAL AUTHORITIES IN THE GAS TOWNS WITHIN HIS DISTRICT TO INITIATE PERIODIC MEETINGS BETWEEN ALL UTILITIES, CONTRACTORS, AND OTHER AGENCIES WHICH WILL BENEFIT FROM AN INTERCHANGE OF CURRENT AND PROPOSED CONSTRUCTION PROGRAMS IN THE TERRITORY WHERE OUR FACILITIES MAY BE IN CLOSE PROXIMITY TO OTHERS. MEETINGS SHOULD BE SCHEDULED JUST PRIOR TO AND DURING CONSTRUCTION SEASON. WHEN OUR FACILITIES ARE WITHIN OR ADJACENT TO A CONSTRUCTION AREA, THE GAS SUPERVISOR IS EXPECTED TO EXERCISE GOOD JUDGMENT AND COMMON SENSE IN PROVIDING, WHEN WARRANTED, ADDITIONAL PROTECTION BY POSTING WARNING SIGNS, STAKING, FENCING, PROVIDING A REPRESENTATIVE, ETC., FOR THE FACILITY AFFECTED. CORRESPONDENCE DOCUMENTATION INCOMPLETE.\n\nAddressee Acronym: ISU\n\nAddressee Organization Type: P-Private Industry\n\nCommunication Date: 1971-06-02\n\nCommunication Type: Official Correspondence","truncated":false,"body_characters":3174}