# NTSB Safety Recommendation P-81-002

- **operation:** document
- **citation:** P-81-002
- **title:** NTSB Safety Recommendation P-81-002
- **source type:** guidance
- **agency:** National Transportation Safety Board
- **status:** guidance
- **official:** true
- **published on:** 1981-05-13
- **effective on:** 1981-05-13
- **summary:** THE NTSB RECOMMENDS THAT THE UNION LIGHT, HEAT AND POWER COMPANY: INCLUDE PROCEDURES FOR RAPID AND COMPLETE SHUTDOWN IN AN EMERGENCY IN WRITTEN COMPANY UPRATING PLANS.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/ntsb-recommendation-p-81-002.json
- **markdown:** https://regulus.evalyn.ai/document/ntsb-recommendation-p-81-002.md
- **app url:** https://regulus.evalyn.ai/document/ntsb-recommendation-p-81-002
- **source url:** https://data.ntsb.gov/carol-main-public/sr-details/P-81-002
**body:**

NTSB safety recommendation P-81-002.

THE NTSB RECOMMENDS THAT THE UNION LIGHT, HEAT AND POWER COMPANY: INCLUDE PROCEDURES FOR RAPID AND COMPLETE SHUTDOWN IN AN EMERGENCY IN WRITTEN COMPANY UPRATING PLANS.

Priority: CLASS II

Overall Status: Closed - Acceptable Action

Issued Date: 1981-05-13

Adopted Date: 1981-04-28

Overall Date Closed: 1983-02-02

Synopsis: ON OCTOBER 9, 1980, A 2-INCH-DIAMETER COMPRESSION COUPLING LOCATED ON THE UPSTREAM SIDE OF A GAS METER SET ASSEMBLY IN THE BOILERROOM OF THE SIMON KENTON HIGH SCHOOL IN INDEPENDENCE, KENTUCKY, PULLED OUT OF ITS CONNECTION WITH A 2-INCH-DIAMETER GAS SERVICE LINE. NATURAL GAS AT 165-PSIG PRESSURE ESCAPED THROUGH THE 2-INCH-DIAMETER OPENING AND, SECONDS LATER, EXPLODED AND BURNED. A BASEMENT WALL WAS BLOWN DOWN, AN ADJACENT CLASSROOM WAS DAMAGED, AND ONE STUDENT WAS KILLED. ABOUT 30 MINUTES LATER, A SECOND EXPLOSION OCCURED, WHICH INJURED 37 PERSONS AND EXTENSIVELY DAMAGED THE SHCOOL. THE GAS SERVICE LINE WAS CONNECTED TO A 4-INCH-DIAMETER GAS MAIN OWNED BY THE UNION LIGHT, HEAT AND POWER COMPANY (GAS COMPANY), A SUBSIDIARY OF THE CINCINNATI GAS AND ELECTRIC COMPANY, WHICH WAS UPRATING THE GAS MAIN BY CONTROLLED PRESSURE INCREASES AT THE TIME OF THE ACCIDENT.

Ntsbnumber: DCA81AP001

Report Number: PAR-81-01

Addressee Name: Union Light, Heat and Power Company

Addressee Status: Closed--No Longer Applicable

Addressee Date Closed: 1983-02-02

Addressee Organization Type: P-Private Industry

Communication Date: 1982-10-25

Communication Type: Official Correspondence

Communication Contents: UNION LIGHT, HEAT AND POWER COMPANY LTR: ON DECEMBER 21, 1981, UNION LIGHT FILED ITS REVISED EMERGENCY PLAN WITH THE KENTUCKY PUBLIC SERVICE COMMISSION. THE PLAN COVERS EMERGENCY SHUTDOWN AND/OR PRESSURE REDUCTION MEASURES. UNION LIGHT HAS REVISED ITS UPRATING PROCEDURES TO ASSURE THAT UPRATING PLANS FOR SPECIFIC PROJECTS WILL INCLUDE PROCEDURES FOR RAPID AND COMPLETE SHUTDOWN IN THE EVENT OF AN EMERGENCY.

Addressee Organization Type: P-Private Industry

Communication Date: 1983-02-02

Communication Type: Official Correspondence

Addressee Organization Type: P-Private Industry

Communication Date: 1982-10-08

Communication Type: Official Correspondence
- **truncated:** false
- **body characters:** 2232